Defect No | Defect Type | Regulation | Defect Description | Defect Category |
111001
|
Electricity Safety Act 1998
|
41A
|
Responsible person
|
Technical
|
111002
|
Electricity Safety Act 1998
|
43 (1)
|
Safety of electrical installations
|
Technical
|
112002
|
Electricity Safety Act 1998
|
43 (1)
|
Safety of electrical installations
|
Unsafe
|
111003
|
Electricity Safety Act 1998
|
43 (1A)
|
Safety of electrical installations
|
Technical
|
112003
|
Electricity Safety Act 1998
|
43 (1A)
|
Safety of electrical installations
|
Unsafe
|
111004
|
Electricity Safety Act 1998
|
43 (2)
|
Safety of electrical installations
|
Technical
|
112004
|
Electricity Safety Act 1998
|
43 (2)
|
Safety of electrical installations
|
Unsafe
|
111005
|
Electricity Safety Act 1998
|
43(4)
|
Safety of electrical installations
|
Technical
|
112005
|
Electricity Safety Act 1998
|
43(4)
|
Safety of electrical installations
|
Unsafe
|
111006
|
Electricity Safety Act 1998
|
43A
|
Safety of electrical installations-building work
|
Technical
|
112006
|
Electricity Safety Act 1998
|
43A
|
Safety of electrical installations-building work
|
Unsafe
|
111007
|
Electricity Safety Act 1998
|
44 (1)(a)
|
Compliance and testing of electrical installation work
|
Technical
|
111008
|
Electricity Safety Act 1998
|
44 (1)(b)
|
Compliance and testing of electrical installation work
|
Technical
|
111009
|
Electricity Safety Act 1998
|
44 (3)
|
Compliance and testing of electrical installation work
|
Technical
|
111010
|
Electricity Safety Act 1998
|
45(1)
|
Inspection of electrical installation work
|
Technical
|
111011
|
Electricity Safety Act 1998
|
45(2)
|
Inspection of electrical installation work
|
Technical
|
111012
|
Electricity Safety Act 1998
|
45A
|
Certificates of Electrical Safety
|
Technical
|
111013
|
Electricity Safety Act 1998
|
45A
|
Certificates of Electrical Safety
|
Technical
|
111014
|
Electricity Safety Act 1998
|
45A (6)
|
Certificates of Electrical Safety
|
Technical
|
111015
|
Electricity Safety Act 1998
|
45A (1)(b)
|
Certificates of Electrical Safety
|
Technical
|
111016
|
Electricity Safety Act 1998
|
45A (2)
|
Certificates of Electrical Safety
|
Technical
|
111017
|
Electricity Safety Act 1998
|
45A
|
Certificates of Electrical Safety - incorrect certificate type
|
Technical
|
111018
|
Electricity Safety Act 1998
|
45A
|
Certificates of Electrical Safety - CoC errors
|
Technical
|
111019
|
Electricity Safety Act 1998
|
63
|
Prohibition notice
|
Technical
|
112020
|
Electricity Safety Act 1998
|
63
|
Prohibition notice
|
Unsafe
|
111021
|
Electricity Safety Act 1998
|
65
|
Recall Notice
|
Technical
|
211056
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.1.2
|
Selection and installation
|
Technical
|
211059
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.1.1
|
ARRANGEMENT OF ELECTRICAL INSTALLATION - Circuits - General
|
Technical
|
211060
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.1.2
|
Origin of submains and final subcircuits
|
Technical
|
211061
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.1.3
|
Common neutral
|
Technical
|
211062
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.1.4
|
Electric vehicle charging circuits
|
Technical
|
211063
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.2
|
Maximum demand
|
Technical
|
211064
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.3
|
Selection and installation of conductors
|
Technical
|
211065
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.4
|
Operating characteristics of equipment
|
Technical
|
211066
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.4.1
|
General
|
Technical
|
211067
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.4.2
|
Voltage
|
Technical
|
211068
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.4.3
|
Current
|
Technical
|
211069
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.4.4
|
Frequency
|
Technical
|
211070
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.4.5
|
Power
|
Technical
|
211071
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.2.4.6
|
Effects on operator or other equipment
|
Technical
|
211073
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.1
|
CONTROL OF ELECTRICAL INSTALLATION - General
|
Technical
|
211075
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.2.1.1
|
Common control requirements - General - All systems
|
Technical
|
211076
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.2.1.2
|
Alternating current systems
|
Technical
|
211077
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.2.1.3
|
Direct current systems
|
Technical
|
211080
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.2.2.1
|
Devices for isolation - General
|
Technical
|
211081
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.2.2.2
|
Identification
|
Technical
|
211083
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.3.1
|
Main switches - Introduction
|
Technical
|
211084
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.3.2
|
General
|
Technical
|
211085
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.3.3
|
Number of main switches
|
Technical
|
211086
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.3.4
|
Location and operation
|
Technical
|
211087
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.3.5
|
Identification
|
Technical
|
211088
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.3.6
|
Remote control
|
Technical
|
211090
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.4.1
|
Additional isolating switches - Electrical installation in an outbuilding
|
Technical
|
211091
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.4.2
|
Submains and final subcircuits greater than 100 A
|
Technical
|
211092
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.4.3
|
Alternative supply
|
Technical
|
211093
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.4.4
|
Identification
|
Technical
|
211094
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.4.5
|
Appliances and accessories
|
Technical
|
211096
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.5.1
|
Emergency switching including emergency stopping - General
|
Technical
|
211097
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.5.2
|
Emergency switching devices
|
Technical
|
211098
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.5.3
|
Installation
|
Technical
|
211099
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.5.4
|
Identification
|
Technical
|
211101
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.6.1
|
Shutting down for mechanical maintenance - General
|
Technical
|
211102
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.6.2
|
Devices for shutting down
|
Technical
|
211103
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.6.3
|
Installation
|
Technical
|
211104
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.6.4
|
Identification
|
Technical
|
211106
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.7.1
|
Functional (control) switching - General
|
Technical
|
211107
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.7.2
|
Functional switching devices
|
Technical
|
211108
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.7.3
|
Identification
|
Technical
|
211109
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.3.7.4
|
Control circuits
|
Technical
|
211111
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.4.1
|
FAULT PROTECTION - General
|
Technical
|
211112
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.4.2
|
Protection by automatic disconnection of supply
|
Technical
|
211113
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.4.3
|
Types of devices
|
Technical
|
211114
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.4.4
|
Auto-reclose devices
|
Technical
|
211117
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.1.1
|
PROTECTION AGAINST OVERCURRENT - General requirements
|
Technical
|
211118
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.1.2
|
Consumer mains
|
Technical
|
211119
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.1.3
|
Submains and final subcircuits-General arrangement
|
Technical
|
211120
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.1.4
|
Omission of protective device for safety reasons
|
Technical
|
211121
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.2
|
Devices for protection against both overload and short-circuit currents
|
Technical
|
211123
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.3.1
|
Protection against overload current - Coordination between conductors and protective devices
|
Technical
|
211124
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.3.2
|
Position of overload protective device-General arrangement
|
Technical
|
211125
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.3.3
|
Alternative position of overload protective device
|
Technical
|
211126
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.3.4
|
Omission of overload protective device
|
Technical
|
211128
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.4.1
|
Protection against short-circuit current - Determination of prospective short-circuit current
|
Technical
|
211129
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.4.2
|
Characteristics of short-circuit protective devices
|
Technical
|
211130
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.4.3
|
Position of devices for short-circuit protection
|
Technical
|
211131
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.4.4
|
Alternative position of short-circuit protective device
|
Technical
|
211132
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.4.4.1
|
General
|
Technical
|
211133
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.4.4.2
|
Condition 1
|
Technical
|
211134
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.4.4.3
|
Condition 2
|
Technical
|
211135
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.4.5
|
Omission of devices for short-circuit protection
|
Technical
|
211137
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.5.1
|
Protection against switchboard internal arcing fault currents - General
|
Technical
|
211138
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.5.2
|
Reduction of the probability of the initiation of a switchboard internal arcing fault
|
Technical
|
211139
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.5.3
|
Limitation of the harmful effects of a switchboard internal arcing fault
|
Technical
|
211141
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.6.1
|
Coordination of overload and short-circuit protective devices - Protection afforded by one device
|
Technical
|
211142
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.6.2
|
Protection afforded by separate devices
|
Technical
|
211144
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.7.1
|
Reliability of supply - General
|
Technical
|
211145
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.7.2
|
Coordination of protective devices
|
Technical
|
211146
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.7.2.1
|
General
|
Technical
|
211147
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.7.2.2
|
Safety service circuit discrimination (selectivity)
|
Technical
|
211148
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.5.7.2.3
|
General supply circuit discrimination (selectivity)
|
Technical
|
211150
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.1
|
ADDITIONAL PROTECTION BY RESIDUAL CURRENT DEVICES - General
|
Technical
|
211151
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.2
|
Selection and arrangement of devices
|
Technical
|
211152
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.2.1
|
General
|
Technical
|
211153
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.2.2
|
Types of RCD
|
Technical
|
211154
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.2.2.1
|
General
|
Technical
|
211155
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.2.2.2
|
Australia Only
|
Technical
|
211156
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.2.3
|
Protection against initiation of fire
|
Technical
|
211157
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.2.4
|
Arrangement
|
Technical
|
211159
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.1
|
Additional protection by residual current devices - General
|
Technical
|
211160
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.2
|
Installation requirements-Australia only
|
Technical
|
211161
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.2.1
|
General
|
Technical
|
211164
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.2.3.1
|
Types of installations
|
Technical
|
211165
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.2.3.2
|
Location of RCD protection
|
Technical
|
211166
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.2.3.3
|
Requirements for additional protection
|
Technical
|
211167
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.2.4
|
Home care installations-Australia only
|
Technical
|
211168
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.2.5
|
Alterations to installations and replacement of switchboards- Aus only
|
Technical
|
211169
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.6.3.2.6
|
Repairs-Australia only
|
Technical
|
211171
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.7.1
|
PROTECTION AGAINST OVERVOLTAGE - General
|
Technical
|
211172
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.7.2
|
Protection by insulation or separation
|
Technical
|
211173
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.7.3
|
Protection by protective devices
|
Technical
|
211175
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.8.1
|
PROTECTION AGAINST UNDERVOLTAGE - General
|
Technical
|
211176
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.8.2
|
Selection of protective device
|
Technical
|
211178
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.1
|
SWITCHBOARDS - General
|
Technical
|
211180
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.2.1
|
Location of switchboards - General
|
Technical
|
211181
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.2.2
|
Accessibility and emergency exit facilities
|
Technical
|
211182
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.2.3
|
Location of main switchboard
|
Technical
|
211183
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.2.4
|
Identification of main switchboard
|
Technical
|
211184
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.2.5
|
Restricted locations
|
Technical
|
212186
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.3.1
|
Construction - Access to live parts
|
Unsafe
|
211187
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.3.2
|
Suitability
|
Technical
|
211188
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.3.3
|
Minimum clearances and creepage distances
|
Technical
|
211189
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.3.4
|
Orientation and location of fuses and circuit-breakers
|
Technical
|
211190
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.3.4.1
|
Orientation of circuit-breakers
|
Technical
|
211191
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.3.4.2
|
Location of fuses and circuit-breakers
|
Technical
|
211192
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.3.5
|
Screw-in fuses
|
Technical
|
211194
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.4.1
|
Bars - General
|
Technical
|
211195
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.4.2
|
Tunnel-type terminals
|
Technical
|
211196
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.4.3
|
Neutral bar
|
Technical
|
211198
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.5.1
|
Equipment identification - General
|
Technical
|
211199
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.5.2
|
Relationship of electrical equipment
|
Technical
|
211200
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.5.3
|
Bars
|
Technical
|
211201
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.5.4
|
Terminals of switchboard equipment
|
Technical
|
211202
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.5.5
|
Common neutral
|
Technical
|
211203
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.5.6
|
Fuse
|
Technical
|
211204
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.6
|
Wiring
|
Technical
|
211205
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
2.10.7
|
Fire-protective measures
|
Technical
|
211207
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.1.2
|
Wiring Systems - Selection and installation
|
Technical
|
211208
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.2
|
TYPES OF WIRING SYSTEMS
|
Technical
|
211210
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.1
|
EXTERNAL INFLUENCES - General
|
Technical
|
211211
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2
|
Particular influences
|
Technical
|
211212
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.1
|
Ambient temperature
|
Technical
|
211213
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.2
|
External heat sources
|
Technical
|
211214
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.3
|
Water or high humidity
|
Technical
|
211215
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.4
|
Solid foreign bodies
|
Technical
|
211216
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.5
|
Corrosive or polluting substances
|
Technical
|
211217
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.6
|
Mechanical damage
|
Technical
|
211218
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.7
|
Vibration
|
Technical
|
211219
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.8
|
Other mechanical stresses
|
Technical
|
211220
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.9
|
Flora
|
Technical
|
211221
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.10
|
Fauna
|
Technical
|
211222
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.11
|
Solar radiation (direct sunlight)
|
Technical
|
211223
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.12
|
Hazardous areas
|
Technical
|
211224
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.3.2.13
|
Thermal insulation
|
Technical
|
211226
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.4.1
|
CURRENT-CARRYING CAPACITY - General
|
Technical
|
211227
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.4.2
|
Operating temperature limits
|
Technical
|
211228
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.4.3
|
Conductors in parallel
|
Technical
|
211229
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.4.4
|
Coordination between conductors and protective devices
|
Technical
|
211231
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.5.1
|
CONDUCTOR SIZE - General
|
Technical
|
211232
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.5.2
|
Neutral conductor
|
Technical
|
211233
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.5.3
|
Earthing conductor
|
Technical
|
211235
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.6.1
|
VOLTAGE DROP - General
|
Technical
|
211236
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.6.2
|
Value
|
Technical
|
211237
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.6.3
|
Conductors in parallel
|
Technical
|
211239
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.1
|
ELECTRICAL CONNECTIONS - General
|
Technical
|
211240
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2
|
Connection methods
|
Technical
|
211241
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.1.1
|
Common requirements
|
Technical
|
211242
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.1.2
|
Aluminium conductors
|
Technical
|
211243
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.2
|
Preparation for connection
|
Technical
|
211244
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.3
|
Loosening of connections
|
Technical
|
211245
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.3.1
|
General
|
Technical
|
211246
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.3.2
|
Crimp joints (compression joints)
|
Technical
|
211247
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.4
|
Mechanical connection devices
|
Technical
|
211248
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.5
|
Retention of stranded conductors
|
Technical
|
211249
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.6
|
Mechanical stress
|
Technical
|
211250
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.7
|
Soldered connections
|
Technical
|
211251
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.8
|
Flexible cords
|
Technical
|
211252
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.9
|
Aerial conductors
|
Technical
|
211253
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.9.1
|
Joints and connections
|
Technical
|
211254
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.9.2
|
Prohibited joints
|
Technical
|
211255
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.10
|
Underground cables
|
Technical
|
211256
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.2.11
|
Earthing conductors
|
Technical
|
211257
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.3
|
Joints in cables
|
Technical
|
211258
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.7.4
|
Installation couplers
|
Technical
|
211260
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.1
|
IDENTIFICATION - General
|
Technical
|
211261
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.2
|
Colour identification by sleeving or other means
|
Technical
|
211262
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.2.1
|
Colour identification by sleeving or other means
|
Technical
|
211263
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.2.2
|
Sleeving of existing earthing and bonding conductors
|
Technical
|
211264
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.2.3
|
Sleeving of existing live conductors
|
Technical
|
211265
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.3
|
Exceptions and special applications
|
Technical
|
211266
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.3.1
|
General
|
Technical
|
211267
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.3.2
|
Protective earthing and equipotential conductors
|
Technical
|
211268
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.3.3
|
Active and neutral conductors
|
Technical
|
211269
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.3.4
|
Alternative and European cable identification colours
|
Technical
|
211270
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.8.3.5
|
Aerial earthing conductors
|
Technical
|
211272
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.1
|
INSTALLATION REQUIREMENTS - General
|
Technical
|
211273
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.2
|
Methods of installation
|
Technical
|
211274
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.3
|
Support and fixing
|
Technical
|
211275
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.3.1
|
General
|
Technical
|
211276
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.3.2
|
Suspended ceilings
|
Technical
|
211277
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.3.3
|
Wiring systems likely to be disturbed
|
Technical
|
211278
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.3.3.1
|
Location
|
Technical
|
211279
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.3.3.2
|
Support and protection
|
Technical
|
211281
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.4.1
|
Protection against mechanical damage - General
|
Technical
|
211282
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.4.2
|
Wiring systems near building surfaces
|
Technical
|
211283
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.4.3
|
Wiring systems under wall lining or roofing material
|
Technical
|
211284
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.4.3.1
|
Prohibited locations
|
Technical
|
211285
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.4.3.2
|
Protection required
|
Technical
|
211286
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.4.4
|
Protection methods
|
Technical
|
211287
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.5
|
Wiring systems installed vertically
|
Technical
|
211288
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.6
|
Change of direction
|
Technical
|
211290
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.7.1
|
Particular installation requirements - Consumer mains
|
Technical
|
211291
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.7.1.1
|
Protected
|
Technical
|
211292
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.7.1.2
|
Unprotected
|
Technical
|
211293
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.7.2
|
Insulated and sheathed cables
|
Technical
|
211294
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.7.3
|
Mineral insulated metal sheathed (MIMS) cable
|
Technical
|
211295
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.7.4
|
Flexible cords used as installation wiring
|
Technical
|
211296
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.7.5
|
Low voltage track systems
|
Technical
|
211297
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.7.6
|
Under-carpet wiring systems
|
Technical
|
211299
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.8.1
|
Prevention of mutual detrimental effects between services - General
|
Technical
|
211300
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.8.2
|
Different electrical installations
|
Technical
|
211301
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.8.2.1
|
Common enclosure/cable
|
Technical
|
211302
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.8.2.2
|
Segregation
|
Technical
|
211303
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.8.3
|
Segregation of different voltage levels
|
Technical
|
211304
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.8.4
|
Proximity to non-electrical services
|
Technical
|
212306
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.9.1
|
Selection and installation to minimize the spread of fire - General
|
Technical
|
211307
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.9.2
|
Selection and installation to minimize the spread of fire - Precautions
|
Technical
|
211308
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.9.3
|
Penetration of fire barriers
|
Technical
|
211309
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.10
|
Limitation of circulating and eddy currents
|
Technical
|
211310
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.10.1
|
Limitation of circulating and eddy currents - General
|
Technical
|
211311
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.10.2
|
Cables for a.c. circuits-Electromagnetic effects
|
Technical
|
211312
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.10.3
|
Cables with non-ferrous metal sheathing
|
Technical
|
211313
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.9.11
|
Minimization of electromagnetic interference
|
Technical
|
211316
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.1.1
|
ENCLOSURE OF CABLES - Insulated, unsheathed cables
|
Technical
|
211317
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.1.2
|
ENCLOSURE OF CABLES - Insulated and sheathed cables
|
Technical
|
211319
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.2.1
|
Wiring enclosures - Types
|
Technical
|
211320
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.2.2
|
Change of wiring enclosures
|
Technical
|
211321
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.2.3
|
Entry of water
|
Technical
|
211323
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.1
|
Installation of wiring enclosures - General
|
Technical
|
211324
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.2
|
Support
|
Technical
|
211325
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.3
|
Continuity
|
Technical
|
211326
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.4
|
Bending
|
Technical
|
211327
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.5
|
Passage for conductors
|
Technical
|
211328
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.6
|
Terminations
|
Technical
|
211329
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.7
|
Installation in direct sunlight
|
Technical
|
211330
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.8
|
Provision for expansion
|
Technical
|
211331
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.10.3.9
|
Cable trunking
|
Technical
|
211333
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.1
|
UNDERGROUND WIRING SYSTEMS - Suitability and protection
|
Technical
|
211334
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.2
|
Classification of wiring systems
|
Technical
|
211336
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.3.1
|
Category A underground wiring systems
|
Technical
|
211337
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.3.2
|
Category B underground wiring systems
|
Technical
|
211338
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.3.3
|
Category C underground wiring system
|
Technical
|
211340
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.4.1
|
Installation requirements - General
|
Technical
|
211341
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.4.2
|
Unenclosed cables
|
Technical
|
211342
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.4.3
|
Category B wiring system mechanical protection
|
Technical
|
211343
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.4.4
|
Minimum depth of cover
|
Technical
|
211344
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.4.5
|
Identification of underground wiring
|
Technical
|
211345
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.4.6
|
Marking and recording of underground cable location
|
Technical
|
211346
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.11.5
|
Spacing from other underground services
|
Technical
|
211348
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.1
|
AERIAL WIRING SYSTEMS - Types of conductor
|
Technical
|
211350
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.2.1
|
Arrangements - Insulation of aerial conductors
|
Technical
|
211351
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.2.2
|
Minimum size
|
Technical
|
211352
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.3
|
Clearances
|
Technical
|
211353
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.3.1
|
General
|
Technical
|
211354
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.3.2
|
Safety warnings
|
Technical
|
211355
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.4
|
Distance between supports (spans)
|
Technical
|
211356
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.5
|
Aerial conductor supports
|
Technical
|
211357
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.5.1
|
Aerial conductor supports - General
|
Technical
|
211358
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.5.2
|
Pin-type insulators
|
Technical
|
211359
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.5.3
|
Hardware
|
Technical
|
211360
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.5.4
|
Spacing between conductors
|
Technical
|
211361
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.6
|
Poles and posts (including supports, struts and extensions to structures)
|
Technical
|
211362
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.12.7
|
Joints and connections
|
Technical
|
211364
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.13.1
|
CABLES SUPPORTED BY A CATENARY - Types of cables
|
Technical
|
211365
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.13.2
|
Catenary supports
|
Technical
|
211366
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.13.3
|
Clearances
|
Technical
|
211367
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.14
|
SAFETY SERVICES
|
Technical
|
211368
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.15
|
BUSWAYS, INCLUDING RISING MAINS SYSTEMS
|
Technical
|
211369
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
3.16
|
EARTH SHEATH RETURN (ESR) SYSTEM
|
Technical
|
211371
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.1.2
|
Electrical equipment - Selection and installation
|
Technical
|
211372
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.1.3
|
External influences
|
Technical
|
211373
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.1.4
|
Adverse effects and interference
|
Technical
|
211375
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.2.1
|
PROTECTION AGAINST THERMAL EFFECTS - General
|
Technical
|
211377
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.2.2.1
|
Prevention of fire hazard - Installation of electrical equipment
|
Technical
|
211378
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.2.2.2
|
Storage of flammable materials
|
Technical
|
211379
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.2.2.3
|
Protection from high temperatures
|
Technical
|
211380
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.2.2.4
|
Emission of arcs or sparks
|
Technical
|
211381
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.2.2.5
|
Electrical equipment enclosures
|
Technical
|
211382
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.2.2.6
|
Prevention of spread of fire
|
Technical
|
211383
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.2.3
|
Protection against burns
|
Technical
|
211385
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.3.1
|
CONNECTION OF ELECTRICAL EQUIPMENT - General
|
Technical
|
211387
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.3.2.1
|
Direct connection - General
|
Technical
|
211388
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.3.2.2
|
Installation coupler
|
Technical
|
211390
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.3.3.1
|
Installation wiring connected by an installation coupler(s) - General
|
Technical
|
211391
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.3.3.2
|
Socket-outlets
|
Technical
|
211392
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.3.4
|
Socket-outlets in installation wiring
|
Technical
|
211393
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.3.5
|
Other connecting devices
|
Technical
|
211394
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.3.6
|
Equipment wiring
|
Technical
|
211397
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.1.1.1
|
Socket-outlets-Application
|
Technical
|
211398
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.1.1.2
|
Socket-outlets-Alternative pin configurations
|
Technical
|
211399
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.1.1.3
|
Low voltage fixed socket-outlet
|
Technical
|
211400
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.1.2
|
Different systems
|
Technical
|
211401
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.1.3
|
Socket-outlets for electric vehicle charging
|
Technical
|
211403
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.2.1
|
Location - Accessibility
|
Technical
|
211404
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.2.2
|
Protection of socket-outlets
|
Technical
|
211405
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.3
|
Earthing contacts
|
Technical
|
213407
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.4.1
|
Switching device - General
|
Testing
|
211408
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.4.2
|
Rating
|
Technical
|
211409
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.4.3
|
Location and marking
|
Technical
|
211410
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.4.4
|
Pendant-type socket-outlet
|
Technical
|
213411
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.4.5
|
Polarization and phase sequence
|
Testing
|
211414
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.1.1
|
Lampholders, including lampholders incorporated in a luminaire - Location
|
Technical
|
211415
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.1.2
|
Edison screw lampholders
|
Technical
|
211416
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.1.3
|
Festoon lighting
|
Technical
|
211418
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.1
|
Lamps and luminaires - General
|
Technical
|
211419
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.2
|
Lamps near flammable materials
|
Technical
|
211420
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.3
|
Recessed luminaires
|
Technical
|
211421
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.3.1
|
General requirements
|
Technical
|
211422
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.3.2
|
Warning sign
|
Technical
|
211423
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.3.3
|
Installation
|
Technical
|
211424
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.3.4
|
Classifications of recessed luminaires
|
Technical
|
211425
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.3.5
|
Requirements for specific classifications
|
Technical
|
211426
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.5.2.4
|
Suspended ceilings
|
Technical
|
211427
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.6
|
SMOKE ALARMS
|
Technical
|
211429
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.7.1
|
COOKING APPLIANCES - Switching device
|
Technical
|
211430
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.7.3
|
Clearance from open cooking surfaces
|
Technical
|
211432
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.8.1
|
APPLIANCES PRODUCING HOT WATER OR STEAM - General
|
Technical
|
211433
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.8.2
|
Water heaters
|
Technical
|
211434
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.8.2.1
|
Access to easing equipment of pressure-relief and terminals of protective devices
|
Technical
|
211435
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.8.2.2
|
Protective devices fitted to unvented water heaters
|
Technical
|
211436
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.8.2.3
|
Isolating switch
|
Technical
|
211438
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.9.1
|
ROOM HEATERS - General
|
Technical
|
211439
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.9.2
|
Isolating switches
|
Technical
|
211440
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.9.3
|
Functional switches
|
Technical
|
211442
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.10.1
|
ELECTRIC HEATING CABLES FOR FLOORS AND CEILINGS AND TRACE HEATING APPLICATIONS - General
|
Technical
|
211443
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.10.2
|
Heating cables
|
Technical
|
211444
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.10.3
|
Isolating switches
|
Technical
|
211445
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.10.4
|
Functional switches
|
Technical
|
211446
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.10.5
|
Additional protection
|
Technical
|
211447
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.10.6
|
Signs
|
Technical
|
211448
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.11
|
ELECTRIC DUCT HEATERS
|
Technical
|
211450
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.1
|
ELECTRICITY CONVERTERS - General
|
Technical
|
211451
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.2
|
Selection and installation
|
Technical
|
211452
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.3
|
Control
|
Technical
|
211454
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.4.1
|
Isolation - General
|
Technical
|
211455
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.4.2
|
Electricity converters incorporating batteries
|
Technical
|
211457
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.5.1
|
Overcurrent protection - Electricity converter protection
|
Technical
|
211458
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.5.2
|
Circuit protection
|
Technical
|
211459
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.5.2.1
|
General
|
Technical
|
211460
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.5.2.2
|
RCDs
|
Technical
|
211461
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.6
|
Earthing
|
Technical
|
211462
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.7
|
Neutral continuity
|
Technical
|
211463
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.12.8
|
Electrical equipment connected to output
|
Technical
|
211465
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.1
|
MOTORS - Protection against injury from mechanical movement
|
Technical
|
211466
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.1.1
|
Switching devices
|
Technical
|
211467
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.1.2
|
Rating of switches
|
Technical
|
211468
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.1.3
|
Devices for starting and stopping
|
Technical
|
211469
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.1.4
|
Protection against restarting or reversal
|
Technical
|
211470
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.2
|
Protection against overload
|
Technical
|
211472
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.3.1
|
Protection against overtemperature - General
|
Technical
|
211473
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.3.2
|
Protection prohibited
|
Technical
|
211474
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.13.3.3
|
Overtemperature protective device
|
Technical
|
211476
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.1
|
TRANSFORMERS - General
|
Technical
|
211477
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.2
|
Secondary circuit
|
Technical
|
211478
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.2.1
|
General
|
Technical
|
211479
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.2.2
|
Control and protection
|
Technical
|
211480
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.3
|
Low voltage transformer supply
|
Technical
|
211481
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.3.1
|
Isolating transformers
|
Technical
|
211482
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.3.2
|
Other transformers
|
Technical
|
211483
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.4
|
Autotransformers
|
Technical
|
211484
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.14.5
|
Step-up transformers
|
Technical
|
211486
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.1
|
CAPACITORS - General
|
Technical
|
211487
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.2
|
Electrical equipment
|
Technical
|
211488
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.2.1
|
General
|
Technical
|
211489
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.2.2
|
Rating of circuit-breakers, switches or contactors
|
Technical
|
211490
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.2.3
|
Current-carrying capacity of supply conductors
|
Technical
|
211491
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.3
|
Provision for discharge and control
|
Technical
|
211492
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.3.1
|
General
|
Technical
|
211493
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.3.2
|
Capacitors connected in parallel with individual appliances
|
Technical
|
211494
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.15.3.3
|
Capacitors not connected in parallel with individual appliances
|
Technical
|
211496
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.16.1
|
ELECTRICAL EQUIPMENT CONTAINING LIQUID DIELECTRICS - General
|
Technical
|
211497
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.16.2
|
Liquid dielectrics having a flashpoint not exceeding 250?C
|
Technical
|
211498
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.17
|
BATTERIES
|
Technical
|
211501
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.18.1.1
|
GAS APPLIANCES AND EQUIPMENT - General
|
Technical
|
211502
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.18.1.2
|
In Australia only
|
Technical
|
211504
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.18.2
|
Gas cylinders containing heavier-than-air gases-Outdoors
|
Technical
|
211505
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.18.2.1
|
Sources of ignition
|
Technical
|
211506
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.18.2.2
|
Hot particles and surfaces
|
Technical
|
211507
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.18.4
|
Gas relief vent terminal-Natural gas, LP Gas or Biogas
|
Technical
|
211508
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.19
|
AIRCONDITIONING AND HEAT PUMP SYSTEMS
|
Technical
|
211510
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.20.1
|
Lifts - General
|
Technical
|
211511
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.20.2
|
Lift supply arrangement
|
Technical
|
211512
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.20.3
|
Labelling
|
Technical
|
211514
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.20.4.1
|
Motor-room-less lifts (MRLs) - General
|
Technical
|
211515
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.20.4.2
|
MRL switchboards
|
Technical
|
211516
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
4.20.4.3
|
Switchgear
|
Technical
|
211518
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.1.2
|
Earthing - Selection and installation
|
Technical
|
211519
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.1.3
|
MEN earthing system
|
Technical
|
211520
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.1.4
|
Other earthing systems
|
Technical
|
211522
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.2.1
|
EARTHING FUNCTIONS - Protective earthing
|
Technical
|
211523
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.2.2
|
Functional earthing (FE)
|
Technical
|
211524
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.2.3
|
Earthing for combined protective and functional purposes
|
Technical
|
211526
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.1
|
EARTHING SYSTEM PARTS - General
|
Technical
|
211527
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2
|
Earthing conductor material and type
|
Technical
|
211528
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2.1
|
Conductor material
|
Technical
|
211529
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2.1.1
|
Copper conductors
|
Technical
|
211530
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2.1.2
|
Aluminium conductors
|
Technical
|
211531
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2.1.3
|
Other materials
|
Technical
|
211532
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2.2
|
Conductor type
|
Technical
|
211533
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2.3
|
Special conditions
|
Technical
|
211534
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2.4
|
Insulation
|
Technical
|
211535
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.2.5
|
Identification
|
Technical
|
211538
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.3.1.1
|
Earthing conductor size - Protective earthing conductors - General
|
Technical
|
211539
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.3.1.2
|
Selection
|
Technical
|
211540
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.3.1.3
|
Calculation
|
Technical
|
211541
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.3.2
|
Main earthing conductor
|
Technical
|
211542
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.3.3
|
Aerial earthing conductors
|
Technical
|
211543
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.3.4
|
Earthing conductors in cables, flexible cables or flexible cords
|
Technical
|
211544
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.4
|
Main earthing terminal/connection or bar
|
Technical
|
211546
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.5.1
|
MEN connection - General
|
Technical
|
211547
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.5.2
|
Size
|
Technical
|
211548
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.5.3
|
Identification
|
Technical
|
211549
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.6
|
Earth electrodes
|
Technical
|
211550
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.6.1
|
Earth electrodes - General
|
Technical
|
211551
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.6.2
|
Types
|
Technical
|
211552
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.6.3
|
Installation
|
Technical
|
211553
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.6.4
|
Location
|
Technical
|
211554
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.3.7
|
Functional earthing conductors
|
Technical
|
211558
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.4.1.2
|
Conductive building materials
|
Technical
|
211559
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.4.1.3
|
Connection of electrical equipment to earth
|
Technical
|
211560
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.4.2
|
Socket-outlets
|
Technical
|
211561
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.4.3
|
Lighting points
|
Technical
|
211562
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.4.4
|
Luminaires
|
Technical
|
211563
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.4.5
|
Conductive supports for aerial conductors
|
Technical
|
213566
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.4.6.2
|
Connection to protective earthing conductors
|
Testing
|
211567
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.4.7
|
Submersible pumps
|
Technical
|
211571
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.1.1
|
EARTHING ARRANGEMENTS - Main earthing conductor - Arrangement
|
Technical
|
211572
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.1.2
|
Connection to earth electrode
|
Technical
|
211573
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.1.3
|
Labelling
|
Technical
|
211574
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.1.4
|
Resistance
|
Technical
|
211576
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.2.1
|
Protective earthing conductors - Arrangement
|
Technical
|
211577
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.2.2
|
Restricted connections
|
Technical
|
211578
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.2.2.1
|
Circuits
|
Technical
|
211579
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.2.2.2
|
Earthing of equipment
|
Technical
|
211580
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.2.2.3
|
Earthing facilities for distribution boards
|
Technical
|
211582
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.3.1
|
Particular methods of earthing - Outbuildings
|
Technical
|
211583
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.3.2
|
Wiring systems
|
Technical
|
211584
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.3.3
|
Electrical equipment supplied by flexible cord or flexible cable
|
Technical
|
211585
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.3.4
|
Switchboards
|
Technical
|
211586
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.3.5
|
Unprotected consumer mains
|
Technical
|
211588
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.4.1
|
Continuity - General
|
Technical
|
211589
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.4.2
|
Conductive wiring enclosures
|
Technical
|
211590
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.4.3
|
Conductive sheaths, armours and screens of cables
|
Technical
|
211591
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.4.4
|
Connecting devices
|
Technical
|
211593
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.5.1
|
Installation - General
|
Technical
|
211594
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.5.2
|
Protection against mechanical damage
|
Technical
|
211595
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.5.3
|
Protection against corrosion
|
Technical
|
211596
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.5.4
|
Aerial earthing conductors
|
Technical
|
211597
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.5.5
|
Buried earthing conductors
|
Technical
|
211599
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.6.1
|
Connections - Conductors
|
Technical
|
211600
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.5.6.2
|
Connections - Constructional components
|
Technical
|
211602
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.1
|
EQUIPOTENTIAL BONDING - General
|
Technical
|
211604
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.1
|
Arrangement - General
|
Technical
|
211605
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.2
|
Conductive water piping
|
Technical
|
211606
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.3
|
Other conductive piping systems
|
Technical
|
211607
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.4
|
Conductive cable sheaths and conductive wiring enclosures
|
Technical
|
211608
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.5
|
Showers and bathrooms
|
Technical
|
211609
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.6
|
Swimming and spa pools
|
Technical
|
211610
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.6.1
|
Bonding arrangement
|
Technical
|
211611
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.6.2
|
Conductive pool structures
|
Technical
|
211612
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.6.3
|
Pool equipotential bonding conductor connection point
|
Technical
|
211613
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.6.4
|
Electrical equipment
|
Technical
|
211614
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.6.5
|
Conductive fixtures and fittings
|
Technical
|
211615
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.2.7
|
Telephone and telecommunication earthing systems
|
Technical
|
211617
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.3.1
|
Bonding conductors - General
|
Technical
|
211618
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.6.3.2
|
Size
|
Technical
|
211620
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.7.1
|
EARTH FAULT-LOOP IMPEDANCE - General
|
Technical
|
211621
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.7.2
|
Disconnection times
|
Technical
|
211622
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.7.3
|
Earth fault-loop
|
Technical
|
211623
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.7.4
|
Impedance
|
Technical
|
211624
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.7.5
|
Supplementary equipotential bonding
|
Technical
|
211625
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
5.8
|
OTHER EARTHING ARRANGEMENTS
|
Technical
|
211627
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.1.2
|
Damp Situations - Selection and installation
|
Technical
|
211628
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.1
|
BATHS, SHOWERS AND OTHER FIXED WATER CONTAINERS - Scope
|
Technical
|
211629
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.2
|
BATHS, SHOWERS AND OTHER FIXED WATER CONTAINERS - Scope - Classification of zones
|
Technical
|
211630
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.2.1
|
Baths and showers
|
Technical
|
211631
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.2.2
|
Other fixed water containers
|
Technical
|
212632
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.3
|
Protection against electric shock-Prohibited measures
|
Unsafe
|
211633
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.4
|
Selection and installation of electrical equipment
|
Technical
|
211634
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.4.1
|
Degree of protection required
|
Technical
|
211635
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.4.2
|
Socket-outlets
|
Technical
|
211636
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.4.3
|
Switches and other accessories
|
Technical
|
211637
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.4.4
|
Luminaires
|
Technical
|
211638
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.4.5
|
Other electrical equipment
|
Technical
|
211639
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.4.6
|
Switchboards
|
Technical
|
211640
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.2.4.7
|
Electricity generation systems
|
Technical
|
211642
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.2
|
SWIMMING POOLS, PADDLING POOLS AND SPA POOLS OR TUBS - Classification of zones
|
Technical
|
211643
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.2.1
|
Swimming pools and paddling pools
|
Technical
|
211644
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.2.2
|
Spa pools or tubs
|
Technical
|
211645
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.2.2.1
|
General
|
Technical
|
211646
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.2.2.2
|
Water capacity exceeding 5000 L
|
Technical
|
211647
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.2.2.3
|
Water capacity not exceeding 5000 L
|
Technical
|
211649
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.3.1
|
Prohibited measures
|
Technical
|
211650
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.3.2
|
Supplementary equipotential bonding
|
Technical
|
212651
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.3.3
|
Voltage gradients
|
Unsafe
|
211652
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.4
|
Selection and installation of electrical equipment
|
Technical
|
211653
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.4.1
|
Degree of protection required
|
Technical
|
211654
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.4.2
|
Wiring systems
|
Technical
|
211655
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.4.3
|
Socket-outlets
|
Technical
|
211656
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.4.4
|
Switches and other accessories
|
Technical
|
211658
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.4.6
|
Switchboards
|
Technical
|
211659
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.4.7
|
Electricity generation systems
|
Technical
|
211660
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.3.4.8
|
Electricity distributer?s electrical equipment
|
Technical
|
211662
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.2
|
Fountains and water features - Classification of zones
|
Technical
|
212663
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.3
|
Protection against electric shock
|
Unsafe
|
211664
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.3.1
|
Use of SELV
|
Technical
|
212667
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.3.2.2
|
Prohibited measures
|
Unsafe
|
211668
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.4
|
Selection and installation of electrical equipment
|
Technical
|
211669
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.4.1
|
Degree of protection required
|
Technical
|
211670
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.4.2
|
Wiring systems
|
Technical
|
211671
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.4.3
|
Socket-outlets
|
Technical
|
211672
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.4.4
|
Switches and other accessories
|
Technical
|
211674
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.4.6
|
Switchboards
|
Technical
|
211675
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.4.7
|
Electricity generation systems
|
Technical
|
211676
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.4.4.8
|
Electricity distributer?s electrical equipment
|
Technical
|
211678
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.2
|
Saunas - Classification of zones
|
Technical
|
211680
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.3.1
|
Use of SELV
|
Technical
|
212681
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.3.2
|
Protection against electric shock - Prohibited measures
|
Unsafe
|
211683
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.4
|
Selection and installation of electrical equipment
|
Technical
|
211684
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.4.1
|
Degree of protection required
|
Technical
|
211685
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.4.2
|
Requirements in classified zones
|
Technical
|
211686
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.4.3
|
Wiring systems
|
Technical
|
211687
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.4.4
|
Socket-outlets, switches and other accessories
|
Technical
|
211688
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.4.5
|
Sauna heating appliances
|
Technical
|
211689
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.5.4.6
|
Switchboards
|
Technical
|
211692
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.2.1
|
Refrigeration rooms - Protection against electric shock - Use of SELV
|
Technical
|
212693
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.2.2
|
Protection against electric shock - Prohibited measures
|
Unsafe
|
211694
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3
|
Selection and installation of electrical equipment
|
Technical
|
211695
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.1
|
Degree of protection required
|
Technical
|
211696
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.2
|
Wiring systems
|
Technical
|
211697
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.2.1
|
General
|
Technical
|
211698
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.2.2
|
Types permitted
|
Technical
|
211699
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.2.3
|
Sealing
|
Technical
|
211700
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.3
|
Socket-outlets, switches and other accessories
|
Technical
|
211701
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.4
|
Luminaires, lampholders and other equipment
|
Technical
|
211702
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.4.1
|
Luminaires
|
Technical
|
211703
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.4.2
|
Lampholders
|
Technical
|
211704
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.5
|
Fixed appliances and motors
|
Technical
|
211705
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.6
|
Heating elements in door seals
|
Technical
|
211706
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.6.3.7
|
Switchboards
|
Technical
|
211708
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.7.2
|
Sanitization & Hosing down operations - Classification of zone
|
Technical
|
211710
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.7.3.1
|
Protection against electric shock - Use of SELV
|
Technical
|
212711
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.7.3.2
|
Protection against electric shock - Prohibited measures
|
Unsafe
|
211712
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.7.4
|
Selection and installation of electrical equipment
|
Technical
|
211713
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.7.4.1
|
Degree of protection required
|
Technical
|
211714
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.7.4.2
|
Electrical equipment
|
Technical
|
211715
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
6.7.4.3
|
Switchboards
|
Technical
|
211718
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.1.2
|
Safety Services - General
|
Technical
|
211720
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.2.1
|
Supply systems - General
|
Technical
|
211721
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.2.2
|
Wiring systems (mains, submains, main switchboard and supplies to outbuildings)
|
Technical
|
211722
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.2.2.1
|
WS classification provided
|
Technical
|
211723
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.2.2.2
|
WS classification is not provided
|
Technical
|
211724
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.2.3
|
Alternative supply systems
|
Technical
|
211725
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.2.3.1
|
Continued occupation
|
Technical
|
211726
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.2.3.2
|
Fire management system
|
Technical
|
211728
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.3.1
|
Main switchboard and switchgear - General
|
Technical
|
211729
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.3.2
|
Switchgear
|
Technical
|
211730
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.3.3
|
Cables in the same enclosure
|
Technical
|
211731
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.3.4
|
Arrangement
|
Technical
|
211732
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.3.5
|
Discrimination (selectivity) of circuit-protective devices
|
Technical
|
211734
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.4.1
|
Main switches - General
|
Technical
|
211735
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.4.2
|
Number of main switches
|
Technical
|
211736
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.4.3
|
Mechanical protection
|
Technical
|
211737
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.4.4
|
Identification
|
Technical
|
211738
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.4.5
|
Electrical installations in outbuildings
|
Technical
|
211739
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.4.6
|
Fire separated portions of a building
|
Technical
|
211741
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.1
|
Fire pumps and fire pump control equipment - General
|
Technical
|
211742
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.2
|
Wiring systems supplying fire pumps and fire pump control equipment
|
Technical
|
211743
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.2.1
|
Types of wiring systems
|
Technical
|
211744
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.2.2
|
Segregation of cables
|
Technical
|
211745
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.3
|
Switchgear for fire pumps and fire pump control equipment
|
Technical
|
211746
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.4
|
Interposing switches for fire pumps and fire pump control equipment
|
Technical
|
211747
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.5
|
Pump rooms for fire pumps and fire pump control equipment
|
Technical
|
211748
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.6
|
Fire-pump motors
|
Technical
|
211749
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.6.1
|
Isolating switches for fire-pump motors
|
Technical
|
211750
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.6.2
|
Overcurrent protection for fire-pump motors
|
Technical
|
211751
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.6.3
|
Overtemperature protection for fire-pump motors
|
Technical
|
211752
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.5.6.4
|
Control circuits for fire-pump motors
|
Technical
|
211754
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.6.1
|
Fire and smoke detection equipment and fire alarm systems - General
|
Technical
|
211755
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.6.2
|
Wiring systems for fire detection and alarm systems
|
Technical
|
211756
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.6.2.1
|
Types of wiring systems for fire detection and alarm systems
|
Technical
|
211757
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.6.2.2
|
Segregation of cables for fire detection and alarm systems
|
Technical
|
211758
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.6.3
|
Interposing switches for fire detection and alarm systems
|
Technical
|
211760
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.7.1
|
Air-handling systems - General
|
Technical
|
211761
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.7.2
|
Wiring systems for air-handling systems
|
Technical
|
211762
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.7.2.1
|
Types of wiring system for air-handling systems
|
Technical
|
211763
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.7.2.2
|
Segregation of cables for air-handling systems
|
Technical
|
211764
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.7.2.3
|
Interposing switches for air-handling systems
|
Technical
|
211766
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.8.1
|
Evacuation equipment - General
|
Technical
|
211767
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.8.2
|
Wiring systems for evacuation equipment
|
Technical
|
211768
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.8.2.1
|
Types of wiring system forevacuation equipment
|
Technical
|
211769
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.7.2.2
|
Segregation of cables forevacuation equipment
|
Technical
|
211770
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.3
|
Interposing switches for evacuation equipment
|
Technical
|
211772
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.9.1
|
Emergency lifts - General
|
Technical
|
211773
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.9.1.1
|
In Australia
|
Technical
|
212774
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.9.2
|
Control and protection
|
Technical
|
211775
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.9.3
|
Wiring systems for emergency lifts
|
Technical
|
211776
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.9.3.1
|
Types of wiring system for emergency lifts
|
Technical
|
211777
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.9.3.2
|
Segregation of cables
|
Technical
|
211778
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.9.4
|
Interposing switches
|
Technical
|
211779
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.9.5
|
Switchgear
|
Technical
|
211781
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.10.1
|
Emergency motor-room-less lifts - General
|
Technical
|
211782
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.10.2
|
Switchboards
|
Technical
|
211783
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.10.3
|
Switchgear
|
Technical
|
211784
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.10.4
|
Wiring systems
|
Technical
|
211785
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.10.4.1
|
Types of wiring systems for MRL lifts
|
Technical
|
211786
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.2.10.4.2
|
Segregation of cables
|
Technical
|
211788
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.1
|
ELECTRICITY GENERATION SYSTEMS - General
|
Technical
|
211789
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.2
|
Selection and installation of system
|
Technical
|
211790
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.3
|
Control
|
Technical
|
211793
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.4.1
|
Isolation - General
|
Technical
|
211794
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.4.2
|
Electricity generation systems incorporating batteries
|
Technical
|
211796
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.5.1
|
Overcurrent protection - Electricity generation system protection
|
Technical
|
211797
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.5.2
|
Circuit protection
|
Technical
|
211798
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.5.2.1
|
General
|
Technical
|
211799
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.5.2.2
|
RCDs
|
Technical
|
211800
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.6
|
Earthing
|
Technical
|
211801
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.7
|
Connected electrical equipment
|
Technical
|
211804
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.1.1
|
Alternative supplies - General
|
Technical
|
211805
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.1.2
|
Switching
|
Technical
|
211806
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.2
|
Grid-connected inverter systems
|
Technical
|
211807
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.2.1
|
General
|
Technical
|
211808
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.2.2
|
Switching
|
Technical
|
211809
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.2.3
|
Connection
|
Technical
|
211810
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.3
|
Stand-alone power systems
|
Technical
|
211811
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.3.1
|
General
|
Technical
|
211812
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.3.2
|
Switching
|
Technical
|
211813
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.3.8.3.3
|
Connection
|
Technical
|
211815
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.1
|
PROTECTION BY ELECTRICAL SEPARATION (ISOLATED SUPPLY) - General
|
Technical
|
211816
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.2
|
Source of supply
|
Technical
|
211817
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.3
|
Arrangement of circuits
|
Technical
|
211818
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.4
|
Switching devices
|
Technical
|
211819
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.5
|
Supply to single item of electrical equipment
|
Technical
|
211820
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.6
|
Supply to multiple items of electrical equipment
|
Technical
|
211821
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.7
|
Variable speed drive (VSD) EMI filters
|
Technical
|
213823
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.8.1
|
Testing - General
|
Testing
|
213824
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.8.2
|
Single items of electrical equipment
|
Testing
|
213825
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.8.3
|
Multiple items of electrical equipment
|
Testing
|
213826
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.4.8.4
|
Bonding conductor continuity
|
Testing
|
211828
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.2
|
EXTRA-LOW VOLTAGE ELECTRICAL INSTALLATIONS - Application
|
Technical
|
211829
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.3
|
Sources of supply to SELV and PELV systems
|
Technical
|
211830
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.4
|
Separation requirements for SELV and PELV circuits
|
Technical
|
211831
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.5
|
Arrangement of SELV circuits
|
Technical
|
211832
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.6
|
Arrangement of PELV circuits
|
Technical
|
211833
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.7
|
Voltage drop in conductors
|
Technical
|
211834
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.8
|
Control of an electrical installation
|
Technical
|
211835
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.8.1
|
Main switches
|
Technical
|
211836
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.8.2
|
Other switches
|
Technical
|
211837
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.9
|
Overcurrent protection
|
Technical
|
211838
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.9.1
|
General
|
Technical
|
211839
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.9.2
|
Omission of overcurrent protection
|
Technical
|
211840
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.10
|
Connecting devices
|
Technical
|
211841
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.11
|
Wiring systems
|
Technical
|
211842
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.11.1
|
General
|
Technical
|
211843
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.11.2
|
Aerial conductors
|
Technical
|
211844
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.11.3
|
Underground conductors
|
Technical
|
211845
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.12
|
Testing
|
Technical
|
213846
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.12.1
|
General
|
Testing
|
213847
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.12.2
|
Protection by SELV
|
Testing
|
213848
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.5.12.3
|
Protection by PELV
|
Testing
|
211850
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.6.2
|
HIGH VOLTAGE ELECTRICAL INSTALLATIONS - Application
|
Technical
|
211851
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.6.2.1
|
In Australia
|
Technical
|
211852
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.6.3
|
Issues relevant to high voltage installations
|
Technical
|
211854
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.7.2
|
HAZARDOUS AREAS (EXPLOSIVE GAS OR COMBUSTIBLE DUSTS) - Classification of hazardous areas
|
Technical
|
211855
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.7.2.1
|
Responsibility for classification
|
Technical
|
211856
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.7.2.2
|
Hazardous areas (AS/NZS 60079 series)
|
Technical
|
211857
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.7.2.3
|
Reduction or elimination of the hazard
|
Technical
|
211858
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.7.2.4
|
Electrical equipment
|
Technical
|
211859
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.7.2.4.1
|
Selection
|
Technical
|
211860
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.7.2.4.2
|
Installation
|
Technical
|
211863
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2
|
STANDARDS FOR SPECIFIC ELECTRICAL INSTALLATIONS - Standards containing additional requirements
|
Technical
|
211864
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.1
|
Construction and demolition sites
|
Technical
|
211865
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.2
|
Electro medical treatment areas
|
Technical
|
211866
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.3
|
Transportable structures and vehicles including their site supplies
|
Technical
|
211867
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.4
|
Marinas and recreational boats
|
Technical
|
211868
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.5
|
Shows and carnivals
|
Technical
|
211869
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.6
|
Telecommunication network power supplies
|
Technical
|
211870
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.7
|
Cranes and hoists
|
Technical
|
211871
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.8
|
Lifts
|
Technical
|
211872
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.9
|
High voltage installations
|
Technical
|
211873
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.10
|
Generating sets
|
Technical
|
211874
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.11
|
Inverters
|
Technical
|
211875
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.12
|
Low voltage switch gear and control gear assemblies
|
Technical
|
211876
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.13
|
Stand-alone power systems
|
Technical
|
211877
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.14
|
Photovoltaic (PV) arrays
|
Technical
|
211878
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.15
|
Secondary battery systems
|
Technical
|
211879
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.16
|
Mobile medical facilities (NZ only)
|
Technical
|
211880
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.17
|
Floor and ceiling heating systems (NZ only)
|
Technical
|
211881
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
7.8.2.18
|
Explosive atmospheres and hazardous areas
|
Technical
|
211883
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.1.2
|
Verification - General requirements
|
Technical
|
211884
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.1.3
|
Periodic inspection and testing
|
Technical
|
211886
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.2.1
|
VISUAL INSPECTION - General
|
Technical
|
211887
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.2.2
|
Checklist
|
Technical
|
211889
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.1
|
TESTING - General
|
Technical
|
211890
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.2
|
Test methods
|
Technical
|
213891
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.3
|
Mandatory tests
|
Testing
|
211892
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.3.1
|
Low voltage
|
Technical
|
211893
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.3.2
|
Extra-low voltage
|
Technical
|
211894
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.3.3
|
Test failures
|
Technical
|
213897
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.5.1
|
Continuity of the earthing system - General
|
Testing
|
213898
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.5.2
|
Continuity of the earthing system - Results
|
Testing
|
213900
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.6.1
|
Insulation resistance- General
|
Testing
|
213901
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.6.2
|
Insulation resistance - Method
|
Testing
|
213904
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.7.1
|
Polarity - General
|
Testing
|
212905
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.7.2
|
Polarity - Results
|
Unsafe
|
213907
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.8.1
|
Correct circuit connections - General
|
Testing
|
212908
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.8.2
|
Correct circuit connections - Results
|
Unsafe
|
211910
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.9.1
|
Verification of earth fault-loop impedance (EFLI) - Low voltage socket-outlet circuits
|
Technical
|
211912
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.9.2.1
|
Methods - General
|
Technical
|
213913
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.9.2.2
|
Supply available
|
Testing
|
213914
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.9.2.3
|
No supply available
|
Testing
|
213915
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.9.3
|
Results
|
Testing
|
213916
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.3.10
|
Operation of RCDs
|
Testing
|
211917
|
AS/NZS 3000:2018 +A1 Electrical Installations
|
8.4
|
VERIFICATION RECORDS
|
Technical
|
811001
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
1.2
|
APPLICATION
|
Technical
|
811002
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.1
|
SUPPLY ARRANGEMENTS
|
Technical
|
811003
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.1
|
Supply from service pillar
|
Technical
|
811004
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.2
|
Underground wiring providing site supply
|
Technical
|
811005
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.3
|
Overhead wiring providing the site supply
|
Technical
|
811006
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.4
|
Earthing - In Australia
|
Technical
|
811007
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.5
|
Maximum demand
|
Technical
|
811008
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.6
|
Caravan park service pillars
|
Technical
|
811009
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.7
|
Socket-outlets
|
Technical
|
811010
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.8
|
Construction of caravan park service pillars
|
Technical
|
811011
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.9
|
Other switchboards
|
Technical
|
811012
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.2.10
|
Other socket-outlets
|
Technical
|
811013
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.1
|
Supply from socket-outlet
|
Technical
|
811014
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.2
|
Configuration and rating
|
Technical
|
811015
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.3
|
Overload protection
|
Technical
|
811016
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.4
|
Protection against earth leakage current
|
Technical
|
811017
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.5
|
Control
|
Technical
|
811018
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.6
|
Common overload, earth leakage and control device
|
Technical
|
811019
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.7
|
Weatherproofing
|
Technical
|
811020
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.8
|
Doors and covers
|
Technical
|
811021
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.3.9
|
Strain relief
|
Technical
|
811022
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.4.1
|
Requirements for portable generator sets or inverters
|
Technical
|
811023
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.4.2
|
Overcurrent protection
|
Technical
|
811024
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.4.3
|
Earth leakage protection
|
Technical
|
811025
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.4.4
|
Combined overcurrent and earth leakage protection
|
Technical
|
811026
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.6
|
SITES FOR LOW-CONSUMPTION TRANSPORTABLE STRUCTURES
|
Technical
|
811027
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
2.7.1
|
Initial verification of the installation
|
Technical
|
811028
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.2.1
|
PROVISION FOR CONNECTION TO SITE SUPPLY - General
|
Technical
|
811029
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.2.2
|
Detachable connection at the transportable structure or vehicle
|
Technical
|
811030
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.2.3
|
Permanent connection of the supply lead
|
Technical
|
811031
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.2.4
|
Multiple connections
|
Technical
|
811032
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.3
|
CONTROL AND PROTECTION
|
Technical
|
811033
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.3.1
|
Overcurrent protection
|
Technical
|
811034
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.3.2
|
Protection against earth leakage current
|
Technical
|
811035
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.3.3
|
Location
|
Technical
|
811036
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.3.4
|
Prohibited equipment
|
Technical
|
811037
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.4.1
|
WIRING SYSTEM - Size and type of cable
|
Technical
|
811038
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.4.2
|
Protection from damage
|
Technical
|
811039
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.4.3
|
Fixing
|
Technical
|
811040
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.4.4
|
Isolation and segregation
|
Technical
|
811041
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.5.1
|
EARTHING - Detachable connection, General
|
Technical
|
811042
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.5.2
|
Equipotential bonding
|
Technical
|
811043
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.6.1
|
ACCESSORIES - Mounting
|
Technical
|
811044
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.6.2
|
Switches
|
Technical
|
811045
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.6.3
|
Socket-outlets
|
Technical
|
811046
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.7.1
|
PERMANENTLY CONNECTED APPLIANCES - Control
|
Technical
|
811047
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.7.2
|
Over-temperature cut-out
|
Technical
|
811048
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.9
|
ELECTRICAL INSTALLATIONS IN DAMP AREAS
|
Technical
|
811049
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
3.10.1
|
Initial verification of the installation
|
Technical
|
811050
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.1
|
GENERAL
|
Technical
|
811051
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.2.1
|
SUPPLY TO ELECTRICAL EQUIPMENT - One item to be supplied
|
Technical
|
811052
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.2.2
|
More than one item to be supplied
|
Technical
|
811053
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.3.1
|
CONNECTION OF SUPPLY - General
|
Technical
|
811054
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.3.2
|
Multiple transportable structures occupying the one site
|
Technical
|
811055
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.3.3
|
Restriction on connection
|
Technical
|
811056
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.3.4
|
Prohibited connections
|
Technical
|
811057
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.1
|
OUTLET BOX - General
|
Technical
|
811058
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.2
|
Construction
|
Technical
|
811059
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.3
|
Termination of supply lead
|
Technical
|
811060
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.4
|
Socket-outlets
|
Technical
|
811061
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.5
|
Earthing
|
Technical
|
811062
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.6
|
Overcurrent protection
|
Technical
|
811063
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.7
|
Protection against earth leakage current
|
Technical
|
811064
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.8
|
Control switches
|
Technical
|
811065
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.9
|
Marking
|
Technical
|
811066
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.4.10
|
LIGHTING
|
Technical
|
811067
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.5.1
|
Handlamps
|
Technical
|
811068
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
4.5.2
|
Lighting equipment other than handlamps
|
Technical
|
811069
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
5.1.1
|
SUPPLY LEAD - General
|
Technical
|
811070
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
5.1.2
|
Technical details
|
Technical
|
811071
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
5.1.3
|
Length
|
Technical
|
811072
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
5.1.4
|
Coiled leads
|
Technical
|
811073
|
AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies
|
5.2
|
INSTALLATION OF SUPPLY LEAD
|
Technical
|
821001
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
1.2
|
APPLICATION
|
Technical
|
821002
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.1.1
|
General
|
Technical
|
821003
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.1.2
|
Underground wiring
|
Technical
|
821004
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.1.3
|
Overhead wiring
|
Technical
|
821005
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.2
|
MAXIMUM DEMAND
|
Technical
|
821006
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.3.1
|
General
|
Technical
|
821007
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.3.2
|
Enclosure
|
Technical
|
821008
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.3.3
|
Socket-outlets
|
Technical
|
821009
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.3.4
|
Other connection facilities
|
Technical
|
821010
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.3.5
|
Overload protection
|
Technical
|
821011
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.3.6
|
RCD Protection
|
Technical
|
821012
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.3.7
|
Control and isolation
|
Technical
|
821013
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.4.1
|
SWITCHBOARDS - General
|
Technical
|
821014
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.4.2
|
Enclosure
|
Technical
|
821015
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.5.1
|
LOCATION AND MOUNTING OF SWITCHBOARD ENCLOSURES
|
Technical
|
821016
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.5.2
|
Socket-outlets
|
Technical
|
821017
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
2.5.3
|
Identification
|
Technical
|
821018
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
3.1
|
GENERAL
|
Technical
|
821019
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
3.2
|
GENERATING SETS
|
Technical
|
821020
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
3.3
|
INVERTERS
|
Technical
|
821021
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
3.4
|
RCD TYPE FOR GENERATOR SETS AND SWITCHBOARDS
|
Technical
|
821022
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.2.1
|
Cable selection
|
Technical
|
821023
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.2.2
|
Installation of cables
|
Technical
|
821024
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.2.3
|
Connection of cables
|
Technical
|
821025
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.3.1
|
CASCADABLE RETICULATION UNITS - General
|
Technical
|
821026
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.3.2
|
Enclosure
|
Technical
|
821027
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.3.3
|
Location and mounting of cascadable reticulation units
|
Technical
|
821028
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.4.1
|
OUTLET BOXES - General
|
Technical
|
821029
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.4.2
|
Construction
|
Technical
|
821030
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.4.3
|
Termination of supply lead
|
Technical
|
821031
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.4.4
|
Socket-outlets
|
Technical
|
821032
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.4.5
|
Earthing
|
Technical
|
821033
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.4.6
|
Overcurrent protection
|
Technical
|
821035
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.4.8
|
Control switches
|
Technical
|
821036
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.4.9
|
Marking
|
Technical
|
821037
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.5.1
|
ELECTRICAL PORTABLE OUTLET DEVICES - General
|
Technical
|
821038
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.5.2
|
Connection to low-voltage electrical power supply
|
Technical
|
821039
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.5.3
|
Location
|
Technical
|
821041
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.6.1
|
FESTOON AND DECORATIVE LIGHTING - General
|
Technical
|
821042
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.6.2
|
Clearances
|
Technical
|
821043
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.6.3
|
Loading of final subcircuits
|
Technical
|
821044
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.6.4
|
Decorative lighting outfits
|
Technical
|
821046
|
AS/NZS 3002:2008 Electrical installations - Shows and carnivals
|
4.7
|
RIDING DEVICES
|
Technical
|
831001
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.1.1
|
WIRING DETAILS - General
|
Technical
|
831002
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.1.2
|
Selection of electrical wiring systems
|
Technical
|
831003
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.1.3
|
Earthing system
|
Technical
|
831004
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.2
|
MAXIMUM DEMAND OF MAINS AND SUBMAINS
|
Technical
|
831005
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.3.1
|
ISOLATING TRANSFORMERS- General
|
Technical
|
831006
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.3.2
|
Protection
|
Technical
|
831007
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.4.1
|
SWITCHBOARDS PROVIDING LOW-VOLTAGE ELECTRICAL SUPPLY TO BOATS - General
|
Technical
|
831008
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.4.2
|
Service pillars
|
Technical
|
831009
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.4.3
|
Other switchboards
|
Technical
|
831010
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
2.5
|
OTHER SOCKET-OUTLETS
|
Technical
|
831011
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
3.1.1
|
SUPPLY LEAD - General
|
Technical
|
831012
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
3.1.2
|
Coiled leads
|
Technical
|
831013
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
3.2
|
INSTALLATION OF SUPPLY LEAD
|
Technical
|
831014
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
3.3.1
|
EARTHING - General
|
Technical
|
831015
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
3.3.2
|
Supply through a shore-mounted isolating transformer
|
Technical
|
831016
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
3.3.3
|
Supply through an on-board isolating transformer
|
Technical
|
831017
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
3.3.4
|
Supply without an isolating transformer
|
Technical
|
831018
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
4.1
|
GENERAL
|
Technical
|
833019
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
4.2.1
|
PERIODIC VERIFICATION - Testing
|
Testing
|
831020
|
AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas
|
4.2.2
|
Recording of results
|
Technical
|
611001
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.1
|
GENERAL
|
Technical
|
611002
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.1.1
|
Scope of Section
|
Technical
|
611003
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.1.2
|
Rating classifications
|
Technical
|
611004
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.1.3
|
Selection of generating set rating
|
Technical
|
611005
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.1.4
|
Generating set system of supply
|
Technical
|
611006
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.2
|
LOCATION
|
Technical
|
611007
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.3
|
MECHANICAL AND THERMAL PROTECTION
|
Technical
|
611008
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.3.1
|
Protection from mechanical damage
|
Technical
|
611009
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.3.2
|
Protection from moving parts
|
Technical
|
611010
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.3.3
|
Protection against thermal effects
|
Technical
|
611011
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.3.4
|
Protection against fuel leakage
|
Technical
|
611012
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.4
|
CONTROL OF GENERATING SET
|
Technical
|
611013
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.4.1
|
General
|
Technical
|
611014
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.4.2
|
Prime mover isolating devices
|
Technical
|
611015
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.4.2.1
|
Operation
|
Technical
|
611016
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.4.2.2
|
Location
|
Technical
|
611017
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.4.3
|
Synchronization
|
Technical
|
611018
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.4.4
|
Starting batteries and battery charging
|
Technical
|
611019
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.5
|
EARTHING ARRANGEMENTS
|
Technical
|
611020
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.6
|
ELECTRICAL INSTALLATION
|
Technical
|
611021
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.6.1
|
General requirements
|
Technical
|
611022
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.6.1.1
|
General
|
Technical
|
611023
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.6.1.2
|
Isolation from the normal supply system
|
Technical
|
611024
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.6.1.3
|
Generating set neutral conductor
|
Technical
|
611025
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.6.2
|
Overcurrent protection
|
Technical
|
611026
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.6.3
|
Generator output isolator
|
Technical
|
611027
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7
|
ALTERNATIVE SUPPLY (STANDBY)
|
Technical
|
611028
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.1
|
General
|
Technical
|
611029
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.2
|
Operation
|
Technical
|
611030
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.3
|
Interlocking
|
Technical
|
611031
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.4
|
Changeover device with intermediate ?off? position
|
Technical
|
611032
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.5
|
Changeover device without an intermediate ?off? position
|
Technical
|
611033
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.6
|
Rating
|
Technical
|
611034
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.7
|
Access
|
Technical
|
611035
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.8
|
Identification
|
Technical
|
611036
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.9
|
Automatic changeover to normal supply
|
Technical
|
611037
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.10
|
Changeover device in the generator neutral
|
Technical
|
611038
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.10.1
|
In Australia
|
Technical
|
611039
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.11
|
Three pole/three pole changeover devices
|
Technical
|
611040
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.12
|
Three pole/four pole changeover devices
|
Technical
|
611041
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.7.13
|
Four pole/four pole changeover device
|
Technical
|
611042
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8
|
EARTHING AND BONDING REQUIREMENTS
|
Technical
|
611043
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.1
|
General
|
Technical
|
611044
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.2
|
Earthing and bonding alterations to existing installations
|
Technical
|
611045
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.3
|
Generating set bonding system
|
Technical
|
611046
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.4
|
Generating set windings
|
Technical
|
611047
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.4.1
|
Multi-phase and single-phase three wire centre-tapped generating sets
|
Technical
|
611048
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.4.2
|
Single-phase portable generating sets
|
Technical
|
611049
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.5
|
Connection of generating set windings
|
Technical
|
611050
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.6
|
Arrangement of equipment
|
Technical
|
611051
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.7
|
Rating
|
Technical
|
611052
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.8
|
Provisions for securing isolating devices
|
Technical
|
611053
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.8.9
|
Indication of switch position
|
Technical
|
611054
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.9
|
GENERATOR SWITCHBOARDS
|
Technical
|
611055
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.1
|
LIGHTNING PROTECTION SYSTEMS
|
Technical
|
611056
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11
|
GENERATING SETS CONNECTED AS NORMAL SUPPLY TO A MAIN SWITCHBOARD IN A PERMANENT ELECTRICAL INSTALLATION
|
Technical
|
611057
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11.1
|
Generating set
|
Technical
|
611058
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11.2
|
System of supply for generating set and main switchboard
|
Technical
|
611059
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11.2.1
|
Overcurrent protection
|
Technical
|
611060
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11.2.2
|
Connection to the electrical installation
|
Technical
|
611061
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11.2.3
|
Earthing and equipotential bond connections
|
Technical
|
611062
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11.2.4
|
Unsuitable electrical equipment
|
Technical
|
611063
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11.2.5
|
Connection details
|
Technical
|
611064
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.11.3
|
Other systems of supply
|
Technical
|
611065
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.12
|
GENERATING SETS CONNECTED TO AN ELECTRICAL INSTALLATION CONNECTED AS AN ALTERNATIVE SUPPLY
|
Technical
|
611066
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.12.1
|
General
|
Technical
|
611067
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.12.2
|
System of supply for the generating set and switchboards
|
Technical
|
611068
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.12.2.1
|
Overcurrent protection
|
Technical
|
611069
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
2.12.2.2
|
Connection to switchboards
|
Technical
|
611070
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.1
|
GENERAL
|
Technical
|
611071
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2
|
LOCATION
|
Technical
|
611072
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.1
|
General
|
Technical
|
611073
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.2
|
Access space for generating sets
|
Technical
|
611074
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.3
|
Exit from generating set area
|
Technical
|
611075
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.3.1
|
General
|
Technical
|
611076
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.3.2
|
Number of openings
|
Technical
|
611077
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.3.3
|
Opening and locking of doors
|
Technical
|
611078
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.3.4
|
Size of doors and openings
|
Technical
|
611079
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.4
|
Ventilation
|
Technical
|
611080
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.5
|
Noise containment
|
Technical
|
611081
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.2.6
|
Lighting
|
Technical
|
611082
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.3
|
GUARDING OF LIVE PARTS
|
Technical
|
611083
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.3.1
|
General
|
Technical
|
611084
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.3.2
|
Walked on surfaces
|
Technical
|
611085
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.3.3
|
Outdoor locations
|
Technical
|
611086
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.4
|
TRANSFORMERS
|
Technical
|
611087
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.5
|
GENERATING SETS SUPPLYING SAFETY AND ESSENTIAL SERVICES
|
Technical
|
611088
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.5.1
|
General
|
Technical
|
611089
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.5.2
|
Type
|
Technical
|
611090
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.5.3
|
Overcurrent protection
|
Technical
|
611091
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.5.4
|
Paralleling sources of supply
|
Technical
|
611092
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.5.5
|
Supply of other than safety services or essential services
|
Technical
|
611093
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.5.6
|
Automatic changeover to an emergency essential or supply system
|
Technical
|
611094
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
3.5.7
|
Switchgear
|
Technical
|
611095
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.1
|
GENERAL
|
Technical
|
611096
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.2
|
CONNECTION TO AN ELECTRICAL INSTALLATION
|
Technical
|
611097
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.2.1
|
General
|
Technical
|
611098
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.2.2
|
Connection to an installation
|
Technical
|
611099
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.2.3
|
Connection
|
Technical
|
611100
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.3
|
EARTHING AND BONDING
|
Technical
|
611101
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.3.1
|
General
|
Technical
|
611102
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.3.2
|
Connection of generating set windings
|
Technical
|
611103
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.3.2.1
|
Multi-phase and single-phase generating sets
|
Technical
|
611104
|
AS/NZS 3010:2017 +A1Electrical installations - Generating sets
|
4.3.2.2
|
Earth electrode
|
Technical
|
841001
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
1.2
|
APPLICATION
|
Technical
|
841002
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.1
|
SUPPLY
|
Technical
|
841003
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.1.1
|
Construction wiring
|
Technical
|
841004
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.1.2
|
Appliances, luminaires and electrical equipment
|
Technical
|
841005
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.1.3
|
Identification of source of supply
|
Technical
|
841006
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.1.4
|
Connection devices
|
Technical
|
841007
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.1.5
|
Polarization
|
Technical
|
841008
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.1.6
|
Separate circuit requirements
|
Technical
|
841009
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.2
|
MAXIMUM DEMAND
|
Technical
|
841011
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.3.1.1
|
Switchboards - Location - General
|
Technical
|
841012
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.3.1.2
|
Distribution boards
|
Technical
|
841014
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.3.2.1
|
Switchboard construction - General requirements
|
Technical
|
841015
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.3.2.2
|
Assemblies for Construction sites (ACS) switchboard construction
|
Technical
|
841016
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.3.3
|
Mounting of switchboards
|
Technical
|
841017
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.3.4
|
Socket-outlets
|
Technical
|
841018
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.3.5
|
Support of cables entering switchboards
|
Technical
|
841019
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.1
|
Control
|
Technical
|
841020
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.2
|
Securing of isolating switch
|
Technical
|
841021
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.3
|
Marking of isolating switches
|
Technical
|
841022
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.4
|
Size of marking
|
Technical
|
841023
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.5.1
|
Sub-mains
|
Technical
|
841024
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.5.2
|
Final sub-circuits
|
Technical
|
841027
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.6.3
|
Electrical equipment supplied by low-voltage generators
|
Technical
|
841028
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.6.4
|
Electrical equipment supplied by inverters
|
Technical
|
841029
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.6.5
|
Permanent wiring located where construction or demolition work may be carried out
|
Technical
|
841030
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.4.7
|
Switching of single-phase socket-outlets
|
Technical
|
841031
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.5.1
|
Cables and fittings
|
Technical
|
841032
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.5.2
|
Installation of cables
|
Technical
|
841033
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.5.3
|
Protection against mechanical damage
|
Technical
|
841034
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.5.4
|
Marking
|
Technical
|
841035
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.5.5
|
Use of unarmoured cables
|
Technical
|
841036
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.5.6
|
Location and marking of overhead wiring (including aerial and catenary wiring)
|
Technical
|
841037
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.5.7
|
Type of aerial conductor
|
Technical
|
841038
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.5.8
|
Cables supported by a catenary
|
Technical
|
841039
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.1
|
General
|
Technical
|
841040
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.2
|
Minimum conductor size and core configuration
|
Technical
|
841041
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.3
|
Type of flexible cord and cable
|
Technical
|
841042
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.4
|
Colour
|
Technical
|
841043
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.5
|
Current-carrying capacity
|
Technical
|
841044
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.6
|
Accessories for connection
|
Technical
|
841045
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.7
|
Maximum length
|
Technical
|
841046
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.8
|
Limitations on the use of cord extension sets
|
Technical
|
841047
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.9
|
Protection of flexible cords or cables
|
Technical
|
841048
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.10
|
Portable socket-outlet assemblies (PSOAs)
|
Technical
|
841049
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.11
|
Auxiliary socket-outlet panels
|
Technical
|
841050
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.6.12
|
Electrical portable outlet devices (EPODS)
|
Technical
|
841051
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.7.2
|
lighting and luminaires - Mechanical protection
|
Technical
|
841052
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.7.3.1
|
Emergency lighting - General
|
Technical
|
841053
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.7.3.2
|
Verification
|
Technical
|
841054
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.7.4
|
Hand-held luminaires
|
Technical
|
841055
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.7.5
|
Edison screw type lampholders
|
Technical
|
841056
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.7.6
|
Festoon lighting
|
Technical
|
841057
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.7.7
|
Portable luminaires
|
Technical
|
841058
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.8.1
|
Lift Shafts - General
|
Technical
|
841059
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.8.2
|
Multiple lift shafts
|
Technical
|
841060
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.8.3
|
Emergency lighting
|
Technical
|
841061
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.8.4
|
False-car (Guided work platform)
|
Technical
|
841062
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
2.9
|
TRANSPORTABLE STRUCTURES
|
Technical
|
841063
|
AS/NZS 3012:2019 Electrical installations - Construction and demolition sites
|
3.2
|
FREQUENCY OF VERIFICATION (INSPECTION AND TESTING)
|
Technical
|
851001
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.1.1
|
Hydrogen emission
|
Technical
|
851002
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.1.2
|
Alarms
|
Technical
|
851003
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.1.3
|
Battery accommodation
|
Technical
|
851004
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.1.4
|
Arrangement of cells
|
Technical
|
851005
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.1.5
|
Ventilation
|
Technical
|
851006
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.2.1
|
BATTERY ROOM REQUIREMENTS - General
|
Technical
|
851007
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.2.2
|
Battery room layout and floor area
|
Technical
|
851008
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.2.3
|
Take-off battery terminals and outgoing busbars and cables
|
Technical
|
851009
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.2.4
|
Inter-tier and inter-row connections
|
Technical
|
851010
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.2.5
|
Inter-cell connectors
|
Technical
|
851011
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.2.6
|
Location of luminaires
|
Technical
|
851012
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.3.1
|
BATTERY ENCLOSURE REQUIREMENTS - Enclosure construction
|
Technical
|
851013
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.3.2
|
Take-off battery terminals and outgoing busbars and cables
|
Technical
|
851014
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
2.3.3
|
Battery compartment circuits
|
Technical
|
851015
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.1
|
INSTALLATION - GENERAL
|
Technical
|
851016
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.2
|
CONNECTIONS
|
Technical
|
851017
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.3.1
|
Overcurrent protection
|
Technical
|
851018
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.3.2
|
Warning notices
|
Technical
|
851019
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.3.3
|
Switchgear
|
Technical
|
851020
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.3.4
|
Earth-leakage detection
|
Technical
|
851021
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.3.5
|
Main isolating switch
|
Technical
|
851022
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.3.6
|
Section isolating equipment
|
Technical
|
851023
|
AS 3011.1:2019 Secondary batteries installed in buildings Vented cells
|
3.3.7
|
Fire safety and warning signs
|
Technical
|
861001
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.1.1
|
Hydrogen emission
|
Technical
|
861002
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.1.2
|
Alarms
|
Technical
|
861003
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.1.3
|
Battery accommodation
|
Technical
|
861004
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.1.4
|
Arrangement of cells
|
Technical
|
861005
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.1.5
|
Ventilation
|
Technical
|
861006
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.2.1
|
BATTERY ROOM REQUIREMENTS - General
|
Technical
|
861007
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.2.2
|
Battery room layout and floor area
|
Technical
|
861008
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.2.3
|
Take-off battery terminals and outgoing busbars and cables
|
Technical
|
861009
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.2.4
|
Inter-tier and inter-row connections
|
Technical
|
861010
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.2.5
|
Inter-cell connectors
|
Technical
|
861011
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.2.6
|
Luminaires
|
Technical
|
861012
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.3.1
|
BATTERY ENCLOSURE REQUIREMENTS - Enclosure construction
|
Technical
|
861013
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.3.2
|
Take-off battery terminals and outgoing busbars and cables
|
Technical
|
861014
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
2.3.3
|
Battery compartment circuits
|
Technical
|
861015
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.1
|
INSTALLATION - GENERAL
|
Technical
|
861016
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.2
|
CONNECTIONS
|
Technical
|
861017
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.3.1
|
Overcurrent protection
|
Technical
|
861018
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.3.2
|
Warning notices
|
Technical
|
861019
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.3.3
|
Switchgear
|
Technical
|
861020
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.3.4
|
Earth-leakage detection
|
Technical
|
861021
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.3.5
|
Main isolating switch
|
Technical
|
861022
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.3.6
|
Section isolating equipment
|
Technical
|
861023
|
AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells
|
3.3.7
|
Fire safety and warning signs
|
Technical
|
311001
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.1
|
GENERAL
|
Technical
|
311002
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.2
|
CLASSIFICATION OF PATIENT AREAS
|
Technical
|
311003
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.2.1
|
Documentation
|
Technical
|
311004
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.2.2
|
Patient area boundaries
|
Technical
|
311005
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.2.3
|
Patient areas required to be wired as cardiac-protected electrical areas
|
Technical
|
311006
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.2.4
|
Patient areas required to be wired as body-protected electrical areas
|
Technical
|
311007
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.3
|
SUPPLY OF ELECTRICITY TO PATIENT AREAS
|
Technical
|
311008
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4
|
LOW-VOLTAGE A.C. SUPPLIES
|
Technical
|
311009
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.1
|
Separation of circuits
|
Technical
|
311010
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.1.1
|
Body-protected electrical areas
|
Technical
|
311011
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.1.2
|
Cardiac-protected electrical areas
|
Technical
|
311012
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.1.3
|
Body-protected and cardiac-protected electrical areas
|
Technical
|
311013
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.2
|
Protection of wiring systems and electrical equipment against mechanical damage
|
Technical
|
311014
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3
|
Leakage protective device protection required
|
Technical
|
311015
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3.1
|
General
|
Technical
|
311016
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3.1.1
|
Electrical points
|
Technical
|
311017
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3.1.2
|
Extra-low-voltage (ELV) charging sockets-outlets
|
Technical
|
311018
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3.2
|
Socket-outlets requiring LPD protection
|
Technical
|
311019
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3.2.1
|
General
|
Technical
|
312020
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3.2.2
|
Locations of socket-outlets requiring LPD protection
|
Unsafe
|
312021
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3.2.3
|
Types of socket-outlets requiring LPD protection
|
Unsafe
|
312022
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.3.3
|
Permanently-wired medical electrical equipment requiring LPD protection
|
Unsafe
|
311023
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.4
|
Low-voltage uninterruptible supplies (UPS)
|
Technical
|
311024
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.4.1
|
General
|
Technical
|
312025
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.4.2
|
Leakage protective device protection of uninterruptible supplies (UPS)
|
Unsafe
|
311026
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.4.4.3
|
Uninterruptable power supply status indicators
|
Technical
|
311027
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.5
|
LOW-VOLTAGE D.C. SUPPLIES
|
Technical
|
311028
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.6
|
ACCESS TO CONTROLS AND INDICATORS
|
Technical
|
311029
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7
|
SOCKET-OUTLETS
|
Technical
|
312030
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.1
|
Number of socket-outlets
|
Unsafe
|
311031
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.2
|
Socket-outlets requiring isolating switches
|
Technical
|
311032
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.3
|
Socket-outlets for cleaning equipment
|
Technical
|
311033
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.3.1
|
Location of socket-outlets identified ?CLEANING PURPOSES ONLY?
|
Technical
|
312034
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.3.2
|
Protection of socket-outlets identified ?CLEANING PURPOSES ONLY?
|
Unsafe
|
311035
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.4
|
Identification of socket-outlets
|
Technical
|
311036
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.4.1
|
Identification of socket-outlets protected by LPDs
|
Technical
|
311037
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.4.2
|
Switch indication
|
Technical
|
311038
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.4.3
|
Colour coding
|
Technical
|
311039
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.4.3.1
|
Low voltage (LV) socket-outlets
|
Technical
|
311040
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.4.3.2
|
Extra-low-voltage (ELV) socket-outlets
|
Technical
|
311041
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.4.4
|
Power available indication for RCD-protected socket-outlets
|
Technical
|
312042
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.7.5
|
Socket-outlet switches
|
Unsafe
|
311043
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8
|
RESIDUAL CURRENT DEVICES (RCDs)
|
Technical
|
312044
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8.1
|
Type of RCD
|
Unsafe
|
311045
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8.2
|
Discrimination
|
Technical
|
311046
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8.3
|
Number and disposition of electrical points controlled by RCDs
|
Technical
|
311047
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8.4
|
Indication
|
Technical
|
311048
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8.5
|
Identification of RCDs
|
Technical
|
311049
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8.6
|
Permanently wired equipment
|
Technical
|
311050
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8.7
|
Test facility
|
Technical
|
311051
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.8.8
|
Location of RCDs
|
Technical
|
311052
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9
|
LOW-VOLTAGE ISOLATED SUPPLIES
|
Technical
|
312053
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.1
|
General
|
Unsafe
|
312054
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.2
|
Isolation transformers
|
Unsafe
|
311055
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.3
|
Overcurrent circuit-breaker
|
Technical
|
311056
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.4
|
Overload monitor
|
Technical
|
311057
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.5
|
Line isolation monitor
|
Technical
|
311058
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.5.1
|
General
|
Technical
|
311059
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.5.2
|
Identification of LIMs
|
Technical
|
311060
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.6
|
System prospective hazard current
|
Technical
|
311061
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.7
|
Number and disposition of electrical points protected by an isolated supply
|
Technical
|
311062
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.8
|
Permanently wired equipment
|
Technical
|
311063
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.9.9
|
Test facility
|
Technical
|
311064
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.1
|
ISOLATION SWITCHES
|
Technical
|
311065
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.11
|
EXTRA-LOW-VOLTAGE (ELV) SUPPLIES
|
Technical
|
311066
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.11.1
|
General
|
Technical
|
311067
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.11.2
|
Source of ELV supply
|
Technical
|
311068
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.12
|
IDENTIFICATION
|
Technical
|
311069
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.12.1
|
General
|
Technical
|
311070
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.12.2
|
Identification of patient areas
|
Technical
|
313071
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.13
|
TESTING AND VERIFICATION OF ELECTRICAL WORK
|
Testing
|
313072
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
2.14
|
ADDITIONAL DOCUMENTATION
|
Testing
|
311073
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
3.1
|
GENERAL
|
Technical
|
311074
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
3.2
|
EARTHING
|
Technical
|
311075
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.1
|
GENERAL
|
Technical
|
312076
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.2
|
EARTH-FREE ELV
|
Unsafe
|
311077
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.3
|
DISPOSITION OF ELECTRICAL POINTS CONTROLLED BY LPDs
|
Technical
|
311078
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4
|
EARTHING AND EQUIPOTENTIAL BONDING
|
Technical
|
312079
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.1
|
General
|
Unsafe
|
311080
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2
|
Equipotential earthing system
|
Technical
|
311081
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.1
|
General
|
Technical
|
311082
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.2
|
Provision of equipotential earthing system
|
Technical
|
311083
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.3
|
Form of equipotential earthing system
|
Technical
|
311084
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.4
|
Earthing of socket-outlets
|
Technical
|
312085
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.4.1
|
General
|
Unsafe
|
311086
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.4.2
|
Protective earthing conductor
|
Technical
|
312087
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.5
|
Earthing of permanently installed electrical equipment
|
Unsafe
|
311088
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.5.1
|
Points required to be earthed via the EP junction or node
|
Technical
|
311089
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.5.2
|
Method of connecting the earthing conductor to the equipment
|
Technical
|
311090
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.5.3
|
Method of connecting the earthing conductor to the EP junction or node
|
Technical
|
311091
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.5.4
|
Insulation and segregation of earthing conductors
|
Technical
|
311092
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.5.5
|
Maximum resistance of earthing conductors
|
Technical
|
311093
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.6
|
Equipotential earthing of non-electrical equipment and fittings
|
Technical
|
311094
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.7
|
Earthing connections
|
Technical
|
311095
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.8
|
Equipotential (EP) junction
|
Technical
|
311096
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.9
|
Equipotential (EP) test facility
|
Technical
|
311097
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.2.10
|
Equipotential (EP) test terminal
|
Technical
|
311098
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
4.4.3
|
Return earths
|
Technical
|
311099
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.1
|
GENERAL
|
Technical
|
311100
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2
|
HOMECARE INSTALLATIONS
|
Technical
|
311101
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.1
|
Conformance with AS/NZS 3000
|
Technical
|
311102
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.2
|
Conformance with this Standard AUS
|
Technical
|
312103
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.2.1
|
Leakage protective device (LPD) protection
|
Unsafe
|
312104
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.2.2
|
Socket-outlets
|
Unsafe
|
311105
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.2.3
|
Circuit protection and identification
|
Technical
|
311106
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.3
|
Conformance with this Standard NZ
|
Technical
|
312107
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.3.1
|
Leakage protective device (LPD) protection
|
Unsafe
|
312108
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.3.2
|
Socket-outlets
|
Unsafe
|
311109
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.2.3.3
|
Circuit protection and identification
|
Technical
|
311110
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.3
|
DISABILITY AND AGED CARE INSTALLATIONS
|
Technical
|
311111
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.4
|
INSTALLATIONS FOR SELF-HARM PATIENTS
|
Technical
|
311112
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.4.1
|
General
|
Technical
|
311113
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
5.4.2
|
Identification
|
Technical
|
311114
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.1
|
INTRODUCTION
|
Technical
|
311115
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2
|
ALTERATIONS
|
Technical
|
311116
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2.1
|
General
|
Technical
|
311117
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2.2
|
Patient areas not signposted as cardiac-protected or body-protected electrical areas
|
Technical
|
312118
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2.3
|
Patient areas signposted as cardiac-protected or body-protected electrical areas
|
Technical
|
311119
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2.4
|
Installation of new socket-outlets in patient areas wired as either body-protected or cardiac-protected
|
Technical
|
311120
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2.5
|
Alterations to electrical installations in patient areas
|
Technical
|
311121
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2.5.1
|
Alterations in cardiac-protected electrical areas
|
Technical
|
311122
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2.5.2
|
Fixed electrical equipment rated at or above 2.0 kW
|
Technical
|
311123
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.2.5.3
|
Reclassification of existing cardiac-protected electrical areas as body-protected electrical areas.
|
Technical
|
311124
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.3
|
REPAIRS
|
Technical
|
311125
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.3.1
|
Patient areas not wired as cardiac-protected or body-protected electrical areas
|
Technical
|
311126
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.3.2
|
Patient areas wired as cardiac-protected or body-protected electrical areas AUS
|
Technical
|
311127
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
6.4
|
IDENTIFICATION
|
Technical
|
311128
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
7.1
|
GENERAL
|
Technical
|
311129
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
7.2
|
BODY-PROTECTED ELECTRICAL AREA SIGN
|
Technical
|
311130
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
7.3
|
CARDIAC-PROTECTED ELECTRICAL AREA SIGN
|
Technical
|
311131
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.1
|
GENERAL
|
Technical
|
311132
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2
|
BODY-PROTECTED ELECTRICAL AREAS
|
Technical
|
311133
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1
|
General
|
Technical
|
311134
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.1
|
Inspection
|
Technical
|
311135
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.2
|
Labelling
|
Technical
|
311136
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.3
|
Socket-outlets
|
Technical
|
311137
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.3.1
|
Colour coding
|
Technical
|
311138
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.3.2
|
Power-available lights
|
Technical
|
311139
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.3.3
|
Maximum number of socket-outlets per LPD
|
Technical
|
311140
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.3.4
|
Power ?ON? indicators
|
Technical
|
311141
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.4
|
Switches
|
Technical
|
311142
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.1.5
|
Wiring
|
Technical
|
311143
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.2
|
Earthing
|
Technical
|
313145
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.3.1
|
General
|
Testing
|
313146
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.3.2
|
Sensitivity test
|
Testing
|
313147
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.3.3
|
Maximum tripping time tests AUS
|
Testing
|
311148
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.3.4
|
Maximum tripping time tests NZ
|
Technical
|
311149
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.3.5
|
Residual current device (RCD) power-available indicator lights
|
Technical
|
313150
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.3.6
|
Audible and visible RCD trip indicators
|
Testing
|
311151
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.4
|
Line isolation monitors (LIMs)
|
Technical
|
313152
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.4.1
|
Prospective hazard current of the installation
|
Testing
|
313153
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.4.2
|
Prospective hazard current alarm
|
Testing
|
313154
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.5
|
Overload monitors
|
Testing
|
311155
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.6
|
Uninterruptible power supplies (UPSs)
|
Technical
|
311156
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.2.7
|
Documentation
|
Technical
|
311157
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3
|
CARDIAC-PROTECTED ELECTRICAL AREAS
|
Technical
|
311158
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1
|
General
|
Technical
|
311159
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.1
|
Inspection
|
Technical
|
311160
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.2
|
Labelling
|
Technical
|
311161
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.3
|
Socket-outlets
|
Technical
|
311162
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.3.1
|
Colour coding
|
Technical
|
311163
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.3.2
|
Power-available lights
|
Technical
|
311164
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.3.3
|
Maximum number of socket-outlets per LPD
|
Technical
|
311165
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.3.4
|
Power ?ON? indicators
|
Technical
|
311166
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.3.5
|
Switches
|
Technical
|
311167
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.3.6
|
Wiring
|
Technical
|
311168
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.1.3.7
|
Disposition of socket-outlets protected by RCDs
|
Technical
|
311169
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.2
|
Earthing
|
Technical
|
313170
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.2.1
|
Inspection
|
Testing
|
313171
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.2.2
|
Testing
|
Testing
|
311172
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.3
|
Residual current devices (RCDs)
|
Technical
|
313173
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.3.1
|
General
|
Testing
|
313174
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.3.2
|
Sensitivity test
|
Testing
|
313175
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.3.3
|
Maximum tripping time tests
|
Testing
|
313176
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.3.4
|
Maximum tripping time tests
|
Testing
|
311177
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.3.5
|
RCD power-available indicator lights
|
Technical
|
311178
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.3.6
|
Audiovisual RCD trip indicators
|
Technical
|
311179
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.4
|
Line isolation monitors (LIMs)
|
Technical
|
313180
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.4.1
|
Prospective hazard current of the installation
|
Testing
|
313181
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.4.2
|
Prospective hazard current alarm
|
Testing
|
313182
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.5
|
Overload monitors
|
Testing
|
311183
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.6
|
Uninterruptible power supplies (UPS)
|
Technical
|
311184
|
AS/NZS 3003:2018 +A1 Electrical installations - Patient areas
|
8.3.7
|
Documentation
|
Technical
|
411001
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.1.1
|
General requirements
|
Technical
|
411002
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.1.2
|
Agreements between supplier (manufacturer) and user
|
Technical
|
411005
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.2
|
Voltage classification
|
Technical
|
411006
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.3
|
Current in normal operation
|
Technical
|
411007
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.4
|
Short-circuit current
|
Technical
|
411008
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.4.1
|
Mechanical and thermal effects
|
Technical
|
411009
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.4.2
|
Types
|
Technical
|
411013
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.5
|
Rated frequency
|
Technical
|
411014
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.6
|
Corona
|
Technical
|
411015
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.6.1
|
General
|
Technical
|
411016
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.6.2
|
Radio and television interference
|
Technical
|
411017
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.6.3
|
Audible noise
|
Technical
|
411018
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.7
|
High voltage design practices with respect to EMF
|
Technical
|
411019
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.2.8
|
Overvoltages
|
Technical
|
411022
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.1
|
CIVIL AND STRUCTURAL REQUIREMENTS - General
|
Technical
|
411023
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.2
|
Equipment and structures
|
Technical
|
411024
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.2.1
|
General
|
Technical
|
411025
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.2.2
|
Permanent loads (G)
|
Technical
|
411026
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.2.3
|
Imposed and other loads (Q, W, E)
|
Technical
|
411027
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.2.4
|
Special loads
|
Technical
|
411028
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.3
|
Coincident temperatures
|
Technical
|
411030
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.5
|
Load combinations
|
Technical
|
411031
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.3.6
|
Deflections and serviceability limits
|
Technical
|
411032
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4
|
CLIMATIC AND ENVIRONMENTAL CONDITIONS
|
Technical
|
411033
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.1
|
General
|
Technical
|
411034
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.2
|
Normal conditions
|
Technical
|
411035
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.2.1
|
Indoor
|
Technical
|
411036
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.2.2
|
Outdoor
|
Technical
|
411037
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.3
|
Special conditions
|
Technical
|
411038
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.3.1
|
General
|
Technical
|
411039
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.3.2
|
Altitude
|
Technical
|
411040
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.3.3
|
Pollution
|
Technical
|
411041
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.3.4
|
Temperature and humidity
|
Technical
|
411042
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.3.5
|
Vibration
|
Technical
|
411043
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.3.6
|
Seismic vibration
|
Technical
|
411044
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.4.3.7
|
The effect of wind
|
Technical
|
411045
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.5
|
SPECIAL REQUIREMENTS
|
Technical
|
411046
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.5.1
|
Effects of small animals and micro-organisms
|
Technical
|
411047
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
2.5.2
|
Noise level
|
Technical
|
411051
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.1
|
GENERAL
|
Technical
|
411052
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.2
|
SELECTION OF INSULATION LEVEL
|
Technical
|
411053
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.2.1
|
General
|
Technical
|
411055
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.2.3
|
Consideration of rated withstand voltages
|
Technical
|
411056
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.3
|
VERIFICATION OF WITHSTAND VALUES
|
Technical
|
411057
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.4
|
MINIMUM CLEARANCES OF LIVE PARTS
|
Technical
|
411058
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.4.1
|
General
|
Technical
|
411059
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.4.2
|
Minimum clearances in voltage range I
|
Technical
|
411061
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.5
|
MINIMUM CLEARANCES BETWEEN PARTS UNDER SPECIAL CONDITIONS
|
Technical
|
411062
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
3.6
|
TYPE TESTED EQUIPMENT
|
Technical
|
411063
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.1
|
GENERAL REQUIREMENTS
|
Technical
|
411064
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.1.1
|
Selection
|
Technical
|
411065
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.1.2
|
Equipment Safety
|
Technical
|
412066
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.1.3
|
Personnel safety
|
Unsafe
|
411067
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.1.4
|
Labels
|
Technical
|
411068
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2
|
SPECIFIC REQUIREMENTS
|
Technical
|
411069
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.1
|
Switching devices
|
Technical
|
411070
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.2
|
Power transformers and reactors
|
Technical
|
411071
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.3
|
Gas-insulated metal-enclosed equipment (GIE), metal-enclosed switchgear, insulation-enclosed switchgear and other prefab ricated type-tested switchgear and fusegear assemblies
|
Technical
|
411072
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.4
|
Instrument transformers
|
Technical
|
411073
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.4.1
|
General
|
Technical
|
411074
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.4.2
|
Current transformers
|
Technical
|
411075
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.4.3
|
Voltage transformers
|
Technical
|
411076
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.5
|
Surge arresters
|
Technical
|
411077
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.6
|
Capacitors
|
Technical
|
411079
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.8
|
Insulators
|
Technical
|
411080
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9
|
Insulated cables other than for overhead lines
|
Technical
|
411081
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9.1
|
General requirements
|
Technical
|
411082
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9.2
|
Temperature
|
Technical
|
411083
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9.3
|
Stress due to temperature changes
|
Technical
|
411084
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9.4
|
Flexible reeling and trailing cables
|
Technical
|
411085
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9.5
|
Crossings and proximities
|
Technical
|
411086
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9.6
|
Installation of cables
|
Technical
|
411087
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9.7
|
Bending radius
|
Technical
|
411088
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.9.8
|
Tensile stress
|
Technical
|
411089
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.10
|
Conductors and accessories
|
Technical
|
411090
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.11
|
Rotating electrical machines
|
Technical
|
411091
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.12
|
Generating units
|
Technical
|
411092
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.13
|
Generating unit main connections
|
Technical
|
411093
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.14
|
Static converters
|
Technical
|
411094
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.15
|
Fuses
|
Technical
|
411095
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.15.1
|
Clearances
|
Technical
|
411096
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.15.2
|
Fuse replacement
|
Technical
|
411097
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
4.2.16
|
Electrical and mechanical interlocking
|
Technical
|
411099
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.1
|
MINIMUM REQUIREMENTS - General
|
Technical
|
411100
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.2
|
Circuit arrangement
|
Technical
|
411101
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.2.1
|
Design
|
Technical
|
411102
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.2.2
|
Protective measures
|
Technical
|
411103
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.3
|
Documentation
|
Technical
|
411104
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.4
|
Transport routes
|
Technical
|
411105
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.5
|
Aisles and access areas
|
Technical
|
411106
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.6
|
Lighting
|
Technical
|
411107
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.7
|
Operational safety
|
Technical
|
411108
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.1.8
|
Labelling
|
Technical
|
411109
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2
|
OUTDOOR INSTALLATIONS OF OPEN DESIGN
|
Technical
|
411110
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2.1
|
General
|
Technical
|
412111
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2.2
|
Protective barrier clearances
|
Unsafe
|
412112
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2.3
|
Protective obstacle clearances
|
Unsafe
|
412113
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2.4
|
Boundary clearances
|
Technical
|
411114
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2.5
|
Minimum height over access area
|
Technical
|
411115
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2.6
|
Minimum clearances for maintenance
|
Technical
|
411116
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2.7
|
Clearances to buildings within closed electrical operating areas
|
Technical
|
411117
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.2.8
|
External fences or walls and access doors
|
Technical
|
411118
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.3
|
INDOOR INSTALLATIONS OF OPEN DESIGN
|
Technical
|
411119
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.4
|
INSTALLATION OF PREFABRICATED TYPE-TESTED SWITCHGEAR
|
Technical
|
411120
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.4.1
|
General
|
Technical
|
411121
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.4.2
|
Additional requirements for gas-insulated metal enclosed equipment (GIE)
|
Technical
|
411122
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.4.2.1
|
Design
|
Technical
|
411123
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.4.2.2
|
Erection on site
|
Technical
|
411125
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.4.2.4
|
Earthing
|
Technical
|
411126
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5
|
REQUIREMENTS FOR BUILDINGS
|
Technical
|
411127
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.1
|
Introduction
|
Technical
|
411128
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.2
|
Structural provisions
|
Technical
|
411129
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.2.1
|
General
|
Technical
|
411130
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.2.2
|
Specifications for walls
|
Technical
|
411131
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.2.3
|
Windows
|
Technical
|
411132
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.2.4
|
Roofs
|
Technical
|
411133
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.2.5
|
Floors
|
Technical
|
411134
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.3
|
Rooms for switchgear
|
Technical
|
411135
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.4
|
Service areas
|
Technical
|
411136
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.5
|
Doors
|
Technical
|
411137
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.6
|
Draining of insulating liquids
|
Technical
|
411138
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.7
|
Heating, ventilation and cooling
|
Technical
|
411139
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.7.1
|
General
|
Technical
|
411140
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.7.2
|
Ventilation of battery rooms
|
Technical
|
411141
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.7.3
|
Rooms for emergency generating units
|
Technical
|
411142
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.8
|
Buildings that require special consideration
|
Technical
|
411143
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.5.9
|
Confined spaces
|
Technical
|
411144
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.6
|
HIGH VOLTAGE/LOW VOLTAGE PREFABRICATED SUBSTATIONS
|
Technical
|
411145
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
5.7
|
ELECTRICAL INSTALLATIONS ON A MAST, POLE OR TOWER
|
Technical
|
411146
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.1
|
GENERAL
|
Technical
|
412147
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.2.1
|
PROTECTION AGAINST DIRECT CONTACT - General
|
Unsafe
|
411149
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.2.2
|
Measures for protection against direct contact
|
Technical
|
411150
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.2.2.1
|
Recognized protection types
|
Technical
|
411151
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.2.2.2
|
Design of protective measures
|
Technical
|
411152
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.2.3
|
Protection requirements
|
Technical
|
411153
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.2.3.1
|
Protection outside of closed electrical operating areas
|
Technical
|
411154
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.2.3.2
|
Protection inside closed electrical operating areas
|
Technical
|
411155
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.2.3.3
|
Protection during normal operation
|
Technical
|
411157
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4
|
MEANS TO PROTECT PERSONS WORKING ON OR NEAR ELECTRICAL INSTALLATIONS
|
Technical
|
411158
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.1
|
Construction and working procedures
|
Technical
|
411159
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.2
|
Equipment for isolating installations or apparatus
|
Technical
|
411160
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.3
|
Devices to prevent inadvertent closing of isolating devices
|
Technical
|
411161
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.4
|
Devices for determining the de-energized state
|
Technical
|
411162
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.5
|
Devices for earthing and short-circuiting
|
Technical
|
411163
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.6
|
Equipment acting as protective barriers against adjacent live parts
|
Technical
|
411164
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.6.1
|
General
|
Technical
|
411165
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.6.2
|
Insertable insulated partitions
|
Technical
|
411166
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.6.3
|
Insertable partition walls
|
Technical
|
411167
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.4.7
|
Storage of personal protection equipment
|
Technical
|
411168
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.5
|
PROTECTION FROM DANGER RESULTING FROM ARC FAULT
|
Technical
|
411169
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.6
|
PROTECTION AGAINST DIRECT LIGHTNING STRIKES
|
Technical
|
411170
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7
|
PROTECTION AGAINST FIRE AND EXPLOSION
|
Technical
|
411171
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.1
|
Risk
|
Technical
|
411172
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.1.1
|
General
|
Technical
|
411173
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.1.2
|
Fire and explosion risk zones
|
Technical
|
411174
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.1.3
|
Fire and explosion sources risk assessment
|
Technical
|
411175
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.1.4
|
Fire and explosion risk management
|
Technical
|
411176
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.1.5
|
Fire resistant barriers
|
Technical
|
411177
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.1.6
|
Protection of personnel within high voltage installations
|
Technical
|
411178
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.2
|
Buildings
|
Technical
|
411179
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.2.1
|
General
|
Technical
|
411180
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.2.2
|
Fire alarm systems
|
Technical
|
411181
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.2.3
|
Fire suppression systems
|
Technical
|
411182
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.3
|
Plant and equipment requirements
|
Technical
|
411183
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.4
|
Transformers, reactors
|
Technical
|
411184
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.4.1
|
General
|
Technical
|
411185
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.4.2
|
Fire mitigation options for transformers
|
Technical
|
411186
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.4.3
|
Transformer fire damage control measures
|
Technical
|
411187
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.4.4
|
Outdoor transformers
|
Technical
|
411188
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.4.5
|
Indoor transformers
|
Technical
|
411189
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.5
|
Cables
|
Technical
|
411190
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.6
|
Distribution substations
|
Technical
|
411191
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.6.1
|
Special requirements for distribution kiosk/padmount cubicles and walled high voltage installations
|
Technical
|
411192
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.7.6.2
|
Special requirements for distribution indoor high voltage installations
|
Technical
|
411193
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.8
|
PROTECTION AGAINST LEAKAGE OF INSULATING LIQUIDS AND SF6
|
Technical
|
411194
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.8.1
|
Oil containment
|
Technical
|
411195
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.8.2
|
SF6 leakage
|
Technical
|
411197
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.8.4
|
Fire protected high voltage installation examples for distribution substations
|
Technical
|
411198
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.9
|
IDENTIFICATION AND MARKING
|
Technical
|
411199
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.9.1
|
General
|
Technical
|
411200
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.9.2
|
Information plates and warning plates
|
Technical
|
411201
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.9.3
|
Electrical hazard warning
|
Technical
|
411202
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.9.4
|
Installations with incorporated capacitors
|
Technical
|
411203
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.9.5
|
Emergency signs for emergency exits
|
Technical
|
411204
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.9.6
|
Cable identification marks
|
Technical
|
411205
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
6.1
|
PROTECTION AGAINST UNAUTHORIZED ACCESS
|
Technical
|
411206
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.1
|
PROTECTION SYSTEMS
|
Technical
|
411207
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.2
|
MONITORING AND CONTROL SYSTEMS
|
Technical
|
411208
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3
|
A.C. AND D.C. SUPPLY CIRCUITS
|
Technical
|
411209
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3.1
|
General
|
Technical
|
411210
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3.2
|
a.c. supply
|
Technical
|
411211
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3.3
|
d.c. supply
|
Technical
|
411212
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3.3.1
|
Capacity
|
Technical
|
411213
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3.3.2
|
Monitoring voltage and current
|
Technical
|
411214
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3.3.3
|
Sizing and selection of batteries
|
Technical
|
411215
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3.3.4
|
Battery rooms and cubicles
|
Technical
|
411216
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.3.3.5
|
Protection against corrosion
|
Technical
|
411217
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4
|
COMPRESSED AIR SYSTEMS
|
Technical
|
411218
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4.1
|
Design
|
Technical
|
411219
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4.2
|
Relative humidity
|
Technical
|
411220
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4.3
|
Operating capacity
|
Technical
|
411221
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4.4
|
Protection against corrosion
|
Technical
|
411222
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4.5
|
Marking
|
Technical
|
411223
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4.6
|
Isolation and drainage
|
Technical
|
411224
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4.7
|
Arcing
|
Technical
|
411225
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.4.8
|
Accessible controls
|
Technical
|
411226
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.5
|
SF6 GAS HANDLING PLANT
|
Technical
|
411229
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.6.2
|
Electrical noise sources in high voltage installations
|
Technical
|
411230
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.6.3
|
Measures to be taken to reduce the effects of high frequency interference
|
Technical
|
411231
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.6.4
|
Measures to be taken to reduce the effects of low frequency interference
|
Technical
|
411232
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.6.5
|
Measures related to the selection of equipment
|
Technical
|
411233
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.6.5.1
|
Zones
|
Technical
|
411234
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.6.5.2
|
Internal circuitry
|
Technical
|
411235
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.6.5.3
|
Gas-insulated switchgear
|
Technical
|
411236
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
7.6.6
|
Other possible measures to reduce the effects of interference
|
Technical
|
411237
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.1
|
GENERAL
|
Technical
|
411238
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.2
|
FUNDAMENTAL REQUIREMENTS
|
Technical
|
411239
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.2.1
|
General
|
Technical
|
411240
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.2.2
|
Safety of people
|
Technical
|
411241
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.2.3
|
Protection of equipment
|
Technical
|
411242
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.2.4
|
Support operational security
|
Technical
|
411243
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.3
|
RISK MANAGEMENT AND DUE DILIGENCE
|
Technical
|
411244
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.3.1
|
General
|
Technical
|
411245
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.3.2
|
Touch and step voltage hazards and risks
|
Technical
|
411246
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4
|
DESIGN
|
Technical
|
411247
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.1
|
Introduction
|
Technical
|
411248
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.2
|
Design process overview
|
Technical
|
411249
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.3
|
Data gathering
|
Technical
|
411250
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4
|
Initial concept design
|
Technical
|
411251
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4.1
|
General
|
Technical
|
411252
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4.2
|
Fault current
|
Technical
|
411253
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4.3
|
Earth fault duration
|
Technical
|
411254
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4.4
|
Soil resistivity
|
Technical
|
411255
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4.5
|
Layout practicalities
|
Technical
|
411256
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4.6
|
Coordinated design
|
Technical
|
411257
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4.7
|
Current injection
|
Technical
|
411258
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.4.8
|
Special considerations
|
Technical
|
411259
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.5
|
Determine design EPR
|
Technical
|
411260
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.6
|
Power frequency design
|
Technical
|
411261
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.6.1
|
General
|
Technical
|
411262
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.6.2
|
Earthing conductor layout
|
Technical
|
411263
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.6.3
|
Dimensioning of earthing conductors
|
Technical
|
411264
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.6.4
|
Transferred potentials
|
Technical
|
411265
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.6.5
|
Hazard location identification
|
Technical
|
411266
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.7
|
Safety criteria for design
|
Technical
|
411267
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.7.1
|
Safety criteria
|
Technical
|
411268
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.7.2
|
Risk quantification and individually derived safety criteria
|
Technical
|
411269
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.7.3
|
Guidance on standard safety criteria
|
Technical
|
411270
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.7.4
|
Safety criteria within other standards and guidelines
|
Technical
|
411271
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.8
|
Perform direct probabilistic design
|
Technical
|
411272
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.9
|
Mitigation/redesign
|
Technical
|
411273
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.4.10
|
Transient design
|
Technical
|
411274
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.5
|
CONSTRUCTION
|
Technical
|
411275
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.6
|
COMMISSIONING AND ONGOING MONITORING
|
Technical
|
411276
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.7
|
MAINTENANCE, MODIFICATION AND REFURBISHMENT
|
Technical
|
413277
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.8
|
TESTING
|
Testing
|
413278
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
8.9
|
DOCUMENTATION
|
Technical
|
413279
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
9.1
|
INSPECTIONS AND TESTS
|
Testing
|
413280
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
9.2
|
DOCUMENTATION AND RECORDS
|
Technical
|
411281
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
9.3
|
VERIFICATION OF SPECIFIED PERFORMANCES
|
Technical
|
411282
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
9.4
|
TESTS DURING INSTALLATION AND COMMISSIONING
|
Technical
|
411283
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
9.5
|
TRIAL RUN
|
Technical
|
411284
|
AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.
|
10
|
O P E R A T I O N A N D M A I N T E N A N C E M A N U A L
|
Technical
|
511001
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
4.1
|
General requirements
|
Technical
|
511002
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
4.2
|
Documentation
|
Technical
|
511003
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
4.3
|
Initial inspection
|
Technical
|
512004
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
4.4
|
Assurance of conformity of equipment
|
Unsafe
|
511005
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
4.4.1
|
Equipment with certificates according to IEC standards
|
Technical
|
512006
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
4.4.2
|
Equipment without certificates according to IEC standards
|
Unsafe
|
511007
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
4.4.3
|
Selection of repaired, second hand or existing equipment
|
Technical
|
511008
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
4.5
|
Qualifications of personnel
|
Technical
|
511009
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.1
|
Information requirements
|
Technical
|
511010
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.2
|
Zones
|
Technical
|
511011
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.3
|
Relationship between equipment protection levels (EPLs) and zones
|
Technical
|
511012
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.4.1
|
General
|
Technical
|
512013
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.4.2
|
Relationship between EPLs and types of protection
|
Unsafe
|
511014
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.4.3
|
Equipment for use in locations requiring EPL "Ga" or "Da"
|
Technical
|
511015
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.4.4
|
Equipment for use in locations requiring EPL "Gb" or "Db"
|
Technical
|
511016
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.4.5
|
Equipment for use in locations requiring EPL "Gc" or "Dc"
|
Technical
|
511017
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.5
|
Selection according to equipment grouping
|
Technical
|
511018
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.6.1
|
General
|
Technical
|
511019
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.6.2
|
Gas or vapour
|
Technical
|
511020
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.6.3.1
|
General
|
Technical
|
511021
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.6.3.2
|
Temperature limitations because of the presence of dust clouds
|
Technical
|
511022
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.6.3.3
|
Temperature limitation because of presence of dust layers
|
Technical
|
511023
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.6.3.4
|
Unavoidable dust layers
|
Technical
|
511024
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.7.1
|
General
|
Technical
|
511025
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.7.2
|
Ignition process
|
Technical
|
511026
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.8.1
|
General
|
Technical
|
511027
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.8.2
|
Ignition process
|
Technical
|
511028
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.9
|
Selection to cover external influences
|
Technical
|
511029
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.10.1
|
General
|
Technical
|
511030
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.10.2
|
Transportable and portable equipment
|
Technical
|
511031
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.10.3
|
Personal equipment
|
Technical
|
511032
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.11.1
|
General
|
Technical
|
511033
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.11.2
|
Environmental Factors for "Ex" machine installation
|
Technical
|
511034
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.11.3
|
Power and accessory connections, grounding
|
Technical
|
511035
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.11.4
|
Motors fed from a converter supply
|
Technical
|
511036
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.12
|
Luminaires
|
Technical
|
511037
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.13.1
|
General
|
Technical
|
511038
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.13.2
|
Specific requirements for explosive dust atmospheres
|
Technical
|
511039
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.13.3
|
Location
|
Technical
|
511040
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.14.1
|
Charging of secondary cells and batteries
|
Technical
|
511041
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.14.2
|
Ventilation
|
Technical
|
511042
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.15.1
|
General
|
Technical
|
511043
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.15.2
|
Passive RFID tags
|
Technical
|
511044
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.15.3
|
Mounting RFID tags
|
Technical
|
511045
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
5.16
|
Gas detection equipment
|
Technical
|
511046
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.1
|
Light metals as construction materials
|
Technical
|
511047
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.2
|
Danger from live parts
|
Technical
|
511048
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.3.2
|
TN type of system earthing
|
Technical
|
511049
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.3.3
|
TT type of system earthing
|
Technical
|
511050
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.3.4
|
IT type of system earthing
|
Technical
|
511051
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.3.5
|
SELV and PELV systems
|
Technical
|
511052
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.3.6
|
Electrical separation
|
Technical
|
511053
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.3.7
|
Non Ex electrical equipment above hazardous areas
|
Technical
|
511054
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.4.1
|
General
|
Technical
|
511055
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.4.2
|
Temporary bonding
|
Technical
|
511056
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.5.2
|
Avoidance of a build-up of electrostatic charge on construction and protecting parts for locations requiring EPL "Ga", " Gb" and "Gc"
|
Technical
|
511057
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.5.3
|
Avoidance of a build-up of electrostatic charge on construction and protecting parts for locations requiring EPL "Da", " Db" and "Dc"
|
Technical
|
511058
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.6
|
Lightning protection
|
Technical
|
511059
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.7.1
|
General
|
Technical
|
511060
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.7.2
|
Radio frequency received in hazardous areas
|
Technical
|
511061
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.8
|
Cathodically protected metallic parts
|
Technical
|
511062
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
6.9
|
Ignition by optical radiation
|
Technical
|
511063
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
7
|
Electrical protection
|
Technical
|
511064
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
8.2
|
Switch-off
|
Technical
|
511065
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
8.3
|
Electrical isolation
|
Technical
|
511066
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.1
|
General
|
Technical
|
511067
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.2
|
Aluminium conductors
|
Technical
|
511068
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.1
|
General
|
Technical
|
512069
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.2
|
Cables for fixed installations
|
Unsafe
|
512070
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.3
|
Flexible cables for fixed installations
|
Unsafe
|
512071
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.4
|
Flexible cables supplying transportable and portable equipment
|
Unsafe
|
511072
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.5
|
Single insulated wires
|
Technical
|
511073
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.6
|
Overhead lines
|
Technical
|
512074
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.7
|
Avoidance of damage
|
Unsafe
|
511075
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.8
|
Cable surface temperature
|
Technical
|
511076
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.3.9
|
Resistance to flame propagation
|
Technical
|
512077
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.4
|
Conduit systems
|
Unsafe
|
511078
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.5
|
Additional requirements
|
Technical
|
511079
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.6.1
|
Circuits traversing a hazardous area
|
Technical
|
511080
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.6.2
|
Terminations
|
Technical
|
511081
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.6.3
|
Unused cores
|
Technical
|
511082
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.6.4
|
Openings in walls
|
Technical
|
511083
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.6.5
|
Passage and collection of flammables
|
Technical
|
511084
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
9.6.6
|
Accumulation of dust
|
Technical
|
511085
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
10.1
|
General
|
Technical
|
511086
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
10.2
|
Selection of cable glands
|
Technical
|
511087
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
10.3
|
Connections of cables to equipment
|
Technical
|
511088
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
10.5
|
Unused openings
|
Technical
|
511089
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
10.6.1
|
General
|
Technical
|
511090
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
10.6.2
|
Selection of cable glands
|
Technical
|
511091
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
10.7
|
Additional requirements for type of protection "t" - Protection by enclosure
|
Technical
|
511092
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
10.8
|
Additional requirements for type of protection "nR" - Restricted breathing enclosure
|
Technical
|
511093
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.1
|
General
|
Technical
|
511094
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.2.1
|
Motors with a converter supply
|
Technical
|
511095
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.2.2
|
Reduced-voltage starting (soft starting)
|
Technical
|
511096
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.3.1
|
Mains-operated
|
Technical
|
511097
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.3.2
|
Winding temperature sensors
|
Technical
|
511098
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.3.3
|
Machines with rated voltage greater than 1 kV
|
Technical
|
511099
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.3.4
|
Motors with converter supply
|
Technical
|
511100
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.3.5
|
Reduced-voltage starting (soft starting)
|
Technical
|
511101
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.4.1
|
Motors with a converter supply
|
Technical
|
511102
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.4.2
|
Reduced-voltage starting (soft starting)
|
Technical
|
511103
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.5.1
|
Motors with a converter supply
|
Technical
|
511104
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.5.2
|
Reduced-voltage starting
|
Technical
|
511105
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.6.1
|
Motors with converter supply
|
Technical
|
511106
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.6.2
|
Reduced-voltage starting (soft starting)
|
Technical
|
511107
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
11.6.3
|
Machines with rated voltage greater than 1 kV
|
Technical
|
511108
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
12
|
Luminaires
|
Technical
|
511109
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
13.1
|
General
|
Technical
|
511110
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
13.2
|
Temperature monitoring
|
Technical
|
511111
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
13.3
|
Limiting temperature
|
Technical
|
511112
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
13.4
|
Safety device
|
Technical
|
511113
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
13.5
|
Electrical trace heating systems
|
Technical
|
511114
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
14.1
|
General
|
Technical
|
512115
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
14.3
|
Protection of flameproof joints
|
Unsafe
|
512116
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
14.4
|
Conduit systems
|
Unsafe
|
511117
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
15.1
|
General
|
Technical
|
511118
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
15.2
|
Maximum dissipated power of terminal box enclosures
|
Technical
|
511119
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.1
|
General
|
Technical
|
511120
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2
|
Equipment
|
Technical
|
511121
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.1
|
General
|
Technical
|
511122
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.2
|
Electrical parameters of cables
|
Technical
|
511123
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.3
|
Earthing of conducting screens
|
Technical
|
511124
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.4
|
Cable armour bonding
|
Technical
|
511125
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.5.1
|
General
|
Technical
|
511126
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.5.2
|
Conductors
|
Technical
|
511127
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.5.3
|
Unused cores in cables
|
Technical
|
511128
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.6
|
Marking of cables
|
Technical
|
511129
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.7
|
Cables carrying more than one intrinsically safe circuit
|
Technical
|
511130
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.2.8
|
Types of cables carrying more than one intrinsically safe circuit and applicable fault considerations
|
Technical
|
511131
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.3
|
Earthing of intrinsically safe circuits
|
Technical
|
511132
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.4.1
|
General
|
Technical
|
511133
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.4.2
|
Descriptive system document
|
Technical
|
511134
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.4.3
|
Intrinsically safe circuits with only one source of power
|
Technical
|
511135
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.2.4.4
|
Intrinsically safe circuits with more than one associated apparatus
|
Technical
|
511136
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.3
|
Installations to meet the requirements of EPL "Ga" or "Da"
|
Technical
|
511137
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.4
|
Simple apparatus
|
Technical
|
511138
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.5.1
|
General
|
Technical
|
511139
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.5.3
|
Terminal boxes with more than one intrinsically safe circuit
|
Technical
|
511140
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.5.4
|
Terminal boxes with non-intrinsically safe and intrinsically safe circuits
|
Technical
|
511141
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.5.5
|
Plugs and sockets used for external connections
|
Technical
|
511142
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
16.6
|
Special applications
|
Technical
|
511143
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.1
|
General
|
Technical
|
511144
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.2.1
|
General
|
Technical
|
511145
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.2.2
|
Ducting
|
Technical
|
511146
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.2.3.1
|
General
|
Technical
|
511147
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.2.3.2.1
|
General
|
Technical
|
511148
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.2.3.2.2
|
Automatic switch-off
|
Technical
|
511149
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.2.3.2.3
|
Alarm
|
Technical
|
511150
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.2.3.3
|
Equipment with an internal source of release
|
Technical
|
511151
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
17.2.4
|
Multiple pressurized enclosures with a common safety device
|
Technical
|
511152
|
AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection
|
|