Defect Type: Description:
Defect NoDefect TypeRegulationDefect DescriptionDefect Category
111001 Electricity Safety Act 1998 41A Responsible person Technical
111002 Electricity Safety Act 1998 43 (1) Safety of electrical installations Technical
112002 Electricity Safety Act 1998 43 (1) Safety of electrical installations Unsafe
111003 Electricity Safety Act 1998 43 (1A) Safety of electrical installations Technical
112003 Electricity Safety Act 1998 43 (1A) Safety of electrical installations Unsafe
111004 Electricity Safety Act 1998 43 (2) Safety of electrical installations Technical
112004 Electricity Safety Act 1998 43 (2) Safety of electrical installations Unsafe
111005 Electricity Safety Act 1998 43(4) Safety of electrical installations Technical
112005 Electricity Safety Act 1998 43(4) Safety of electrical installations Unsafe
111006 Electricity Safety Act 1998 43A Safety of electrical installations-building work Technical
112006 Electricity Safety Act 1998 43A Safety of electrical installations-building work Unsafe
111007 Electricity Safety Act 1998 44 (1)(a) Compliance and testing of electrical installation work Technical
111008 Electricity Safety Act 1998 44 (1)(b) Compliance and testing of electrical installation work Technical
111009 Electricity Safety Act 1998 44 (3) Compliance and testing of electrical installation work Technical
111010 Electricity Safety Act 1998 45(1) Inspection of electrical installation work Technical
111011 Electricity Safety Act 1998 45(2) Inspection of electrical installation work Technical
111012 Electricity Safety Act 1998 45A Certificates of Electrical Safety Technical
111013 Electricity Safety Act 1998 45A Certificates of Electrical Safety Technical
111014 Electricity Safety Act 1998 45A (6) Certificates of Electrical Safety Technical
111015 Electricity Safety Act 1998 45A (1)(b) Certificates of Electrical Safety Technical
111016 Electricity Safety Act 1998 45A (2) Certificates of Electrical Safety Technical
111017 Electricity Safety Act 1998 45A Certificates of Electrical Safety - incorrect certificate type Technical
111018 Electricity Safety Act 1998 45A Certificates of Electrical Safety - CoC errors Technical
111019 Electricity Safety Act 1998 63 Prohibition notice Technical
112020 Electricity Safety Act 1998 63 Prohibition notice Unsafe
111021 Electricity Safety Act 1998 65 Recall Notice Technical
211056 AS/NZS 3000:2018 +A1 Electrical Installations 2.1.2 Selection and installation Technical
211059 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.1.1 ARRANGEMENT OF ELECTRICAL INSTALLATION - Circuits - General Technical
211060 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.1.2 Origin of submains and final subcircuits Technical
211061 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.1.3 Common neutral Technical
211062 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.1.4 Electric vehicle charging circuits Technical
211063 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.2 Maximum demand Technical
211064 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.3 Selection and installation of conductors Technical
211065 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.4 Operating characteristics of equipment Technical
211066 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.4.1 General Technical
211067 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.4.2 Voltage Technical
211068 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.4.3 Current Technical
211069 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.4.4 Frequency Technical
211070 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.4.5 Power Technical
211071 AS/NZS 3000:2018 +A1 Electrical Installations 2.2.4.6 Effects on operator or other equipment Technical
211073 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.1 CONTROL OF ELECTRICAL INSTALLATION - General Technical
211075 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.2.1 Common control requirements - General Technical
211076 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.2.1.1 Alternating current systems Technical
211077 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.2.1.2 Direct current systems Technical
211079 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.2.2 Devices for isolation Technical
211080 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.2.2.1 General Technical
211081 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.2.2.2 Identification Technical
211083 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.3.1 Main switches - Introduction Technical
211084 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.3.2 General Technical
211085 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.3.3 Number of main switches Technical
211086 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.3.4 Location and operation Technical
211087 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.3.5 Identification Technical
211088 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.3.6 Remote control Technical
211090 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.4.1 Additional isolating switches - Electrical installation in an outbuilding Technical
211091 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.4.2 Submains and final subcircuits greater than 100 A Technical
211092 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.4.3 Alternative supply Technical
211093 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.4.4 Identification Technical
211094 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.4.5 Appliances and accessories Technical
211096 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.5.1 Emergency switching including emergency stopping - General Technical
211097 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.5.2 Emergency switching devices Technical
211098 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.5.3 Installation Technical
211099 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.5.4 Identification Technical
211101 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.6.1 Shutting down for mechanical maintenance - General Technical
211102 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.6.2 Devices for shutting down Technical
211103 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.6.3 Installation Technical
211104 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.6.4 Identification Technical
211106 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.7.1 Functional (control) switching - General Technical
211107 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.7.2 Functional switching devices Technical
211108 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.7.3 Identification Technical
211109 AS/NZS 3000:2018 +A1 Electrical Installations 2.3.7.4 Control circuits Technical
211111 AS/NZS 3000:2018 +A1 Electrical Installations 2.4.1 FAULT PROTECTION - General Technical
211112 AS/NZS 3000:2018 +A1 Electrical Installations 2.4.2 Protection by automatic disconnection of supply Technical
211113 AS/NZS 3000:2018 +A1 Electrical Installations 2.4.3 Types of devices Technical
211114 AS/NZS 3000:2018 +A1 Electrical Installations 2.4.4 Auto-reclose devices Technical
211117 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.1.1 PROTECTION AGAINST OVERCURRENT - General requirements Technical
211118 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.1.2 Consumer mains Technical
211119 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.1.3 Submains and final subcircuits-General arrangement Technical
211120 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.1.4 Omission of protective device for safety reasons Technical
211121 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.2 Devices for protection against both overload and short-circuit currents Technical
211123 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.3.1 Protection against overload current - Coordination between conductors and protective devices Technical
211124 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.3.2 Position of overload protective device-General arrangement Technical
211125 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.3.3 Alternative position of overload protective device Technical
211126 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.3.4 Omission of overload protective device Technical
211128 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.4.1 Protection against short-circuit current - Determination of prospective short-circuit current Technical
211129 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.4.2 Characteristics of short-circuit protective devices Technical
211130 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.4.3 Position of devices for short-circuit protection Technical
211131 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.4.4 Alternative position of short-circuit protective device Technical
211132 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.4.4.1 General Technical
211133 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.4.4.2 Condition 1 Technical
211134 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.4.4.3 Condition 2 Technical
211135 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.4.5 Omission of devices for short-circuit protection Technical
211137 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.5.1 Protection against switchboard internal arcing fault currents - General Technical
211138 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.5.2 Reduction of the probability of the initiation of a switchboard internal arcing fault Technical
211139 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.5.3 Limitation of the harmful effects of a switchboard internal arcing fault Technical
211141 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.6.1 Coordination of overload and short-circuit protective devices - Protection afforded by one device Technical
211142 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.6.2 Protection afforded by separate devices Technical
211144 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.7.1 Reliability of supply - General Technical
211145 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.7.2 Coordination of protective devices Technical
211146 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.7.2.1 General Technical
211147 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.7.2.2 Safety service circuit discrimination (selectivity) Technical
211148 AS/NZS 3000:2018 +A1 Electrical Installations 2.5.7.2.3 General supply circuit discrimination (selectivity) Technical
211150 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.1 ADDITIONAL PROTECTION BY RESIDUAL CURRENT DEVICES - General Technical
211151 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.2 Selection and arrangement of devices Technical
211152 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.2.1 General Technical
211153 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.2.2 Types of RCD Technical
211154 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.2.2.1 General Technical
211155 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.2.2.2 Australia Only Technical
211156 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.2.3 Protection against initiation of fire Technical
211157 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.2.4 Arrangement Technical
211159 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.1 Additional protection by residual current devices - General Technical
211160 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.2 Installation requirements-Australia only Technical
211161 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.2.1 General Technical
211164 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.2.3.1 Types of installations Technical
211165 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.2.3.2 Location of RCD protection Technical
211166 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.2.3.3 Requirements for additional protection Technical
211167 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.2.4 Home care installations-Australia only Technical
211168 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.2.5 Alterations to installations and replacement of switchboards- Aus only Technical
211169 AS/NZS 3000:2018 +A1 Electrical Installations 2.6.3.2.6 Repairs-Australia only Technical
211171 AS/NZS 3000:2018 +A1 Electrical Installations 2.7.1 PROTECTION AGAINST OVERVOLTAGE - General Technical
211172 AS/NZS 3000:2018 +A1 Electrical Installations 2.7.2 Protection by insulation or separation Technical
211173 AS/NZS 3000:2018 +A1 Electrical Installations 2.7.3 Protection by protective devices Technical
211175 AS/NZS 3000:2018 +A1 Electrical Installations 2.8.1 PROTECTION AGAINST UNDERVOLTAGE - General Technical
211176 AS/NZS 3000:2018 +A1 Electrical Installations 2.8.2 Selection of protective device Technical
211178 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.1 SWITCHBOARDS - General Technical
211180 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.2.1 Location of switchboards - General Technical
211181 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.2.2 Accessibility and emergency exit facilities Technical
211182 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.2.3 Location of main switchboard Technical
211183 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.2.4 Identification of main switchboard Technical
211184 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.2.5 Restricted locations Technical
212186 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.3.1 Construction - Access to live parts Unsafe
211187 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.3.2 Suitability Technical
211188 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.3.3 Minimum clearances and creepage distances Technical
211189 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.3.4 Orientation and location of fuses and circuit-breakers Technical
211190 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.3.4.1 Orientation of circuit-breakers Technical
211191 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.3.4.2 Location of fuses and circuit-breakers Technical
211192 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.3.5 Screw-in fuses Technical
211194 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.4.1 Bars - General Technical
211195 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.4.2 Tunnel-type terminals Technical
211196 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.4.3 Neutral bar Technical
211198 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.5.1 Equipment identification - General Technical
211199 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.5.2 Relationship of electrical equipment Technical
211200 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.5.3 Bars Technical
211201 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.5.4 Terminals of switchboard equipment Technical
211202 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.5.5 Common neutral Technical
211203 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.5.6 Fuse Technical
211204 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.6 Wiring Technical
211205 AS/NZS 3000:2018 +A1 Electrical Installations 2.10.7 Fire-protective measures Technical
211207 AS/NZS 3000:2018 +A1 Electrical Installations 3.1.2 Wiring Systems - Selection and installation Technical
211208 AS/NZS 3000:2018 +A1 Electrical Installations 3.2 TYPES OF WIRING SYSTEMS Technical
211210 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.1 EXTERNAL INFLUENCES - General Technical
211211 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2 Particular influences Technical
211212 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.1 Ambient temperature Technical
211213 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.2 External heat sources Technical
211214 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.3 Water or high humidity Technical
211215 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.4 Solid foreign bodies Technical
211216 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.5 Corrosive or polluting substances Technical
211217 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.6 Mechanical damage Technical
211218 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.7 Vibration Technical
211219 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.8 Other mechanical stresses Technical
211220 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.9 Flora Technical
211221 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.10 Fauna Technical
211222 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.11 Solar radiation (direct sunlight) Technical
211223 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.12 Hazardous areas Technical
211224 AS/NZS 3000:2018 +A1 Electrical Installations 3.3.2.13 Thermal insulation Technical
211226 AS/NZS 3000:2018 +A1 Electrical Installations 3.4.1 CURRENT-CARRYING CAPACITY - General Technical
211227 AS/NZS 3000:2018 +A1 Electrical Installations 3.4.2 Operating temperature limits Technical
211228 AS/NZS 3000:2018 +A1 Electrical Installations 3.4.3 Conductors in parallel Technical
211229 AS/NZS 3000:2018 +A1 Electrical Installations 3.4.4 Coordination between conductors and protective devices Technical
211231 AS/NZS 3000:2018 +A1 Electrical Installations 3.5.1 CONDUCTOR SIZE - General Technical
211232 AS/NZS 3000:2018 +A1 Electrical Installations 3.5.2 Neutral conductor Technical
211233 AS/NZS 3000:2018 +A1 Electrical Installations 3.5.3 Earthing conductor Technical
211235 AS/NZS 3000:2018 +A1 Electrical Installations 3.6.1 VOLTAGE DROP - General Technical
211236 AS/NZS 3000:2018 +A1 Electrical Installations 3.6.2 Value Technical
211237 AS/NZS 3000:2018 +A1 Electrical Installations 3.6.3 Conductors in parallel Technical
211239 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.1 ELECTRICAL CONNECTIONS - General Technical
211240 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2 Connection methods Technical
211241 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.1.1 Common requirements Technical
211242 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.1.2 Aluminium conductors Technical
211243 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.2 Preparation for connection Technical
211244 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.3 Loosening of connections Technical
211245 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.3.1 General Technical
211246 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.3.2 Crimp joints (compression joints) Technical
211247 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.4 Mechanical connection devices Technical
211248 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.5 Retention of stranded conductors Technical
211249 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.6 Mechanical stress Technical
211250 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.7 Soldered connections Technical
211251 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.8 Flexible cords Technical
211252 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.9 Aerial conductors Technical
211253 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.9.1 Joints and connections Technical
211254 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.9.2 Prohibited joints Technical
211255 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.10 Underground cables Technical
211256 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.2.11 Earthing conductors Technical
211257 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.3 Joints in cables Technical
211258 AS/NZS 3000:2018 +A1 Electrical Installations 3.7.4 Installation couplers Technical
211260 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.1 IDENTIFICATION - General Technical
211261 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.2 Colour identification by sleeving or other means Technical
211262 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.2.1 Colour identification by sleeving or other means Technical
211263 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.2.2 Sleeving of existing earthing and bonding conductors Technical
211264 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.2.3 Sleeving of existing live conductors Technical
211265 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.3 Exceptions and special applications Technical
211266 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.3.1 General Technical
211267 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.3.2 Protective earthing and equipotential conductors Technical
211268 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.3.3 Active and neutral conductors Technical
211269 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.3.4 Alternative and European cable identification colours Technical
211270 AS/NZS 3000:2018 +A1 Electrical Installations 3.8.3.5 Aerial earthing conductors Technical
211272 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.1 INSTALLATION REQUIREMENTS - General Technical
211273 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.2 Methods of installation Technical
211274 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.3 Support and fixing Technical
211275 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.3.1 General Technical
211276 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.3.2 Suspended ceilings Technical
211277 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.3.3 Wiring systems likely to be disturbed Technical
211278 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.3.3.1 Location Technical
211279 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.3.3.2 Support and protection Technical
211281 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.4.1 Protection against mechanical damage - General Technical
211282 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.4.2 Wiring systems near building surfaces Technical
211283 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.4.3 Wiring systems under wall lining or roofing material Technical
211284 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.4.3.1 Prohibited locations Technical
211285 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.4.3.2 Protection required Technical
211286 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.4.4 Protection methods Technical
211287 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.5 Wiring systems installed vertically Technical
211288 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.6 Change of direction Technical
211290 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.7.1 Particular installation requirements - Consumer mains Technical
211291 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.7.1.1 Protected Technical
211292 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.7.1.2 Unprotected Technical
211293 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.7.2 Insulated and sheathed cables Technical
211294 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.7.3 Mineral insulated metal sheathed (MIMS) cable Technical
211295 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.7.4 Flexible cords used as installation wiring Technical
211296 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.7.5 Low voltage track systems Technical
211297 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.7.6 Under-carpet wiring systems Technical
211299 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.8.1 Prevention of mutual detrimental effects between services - General Technical
211300 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.8.2 Different electrical installations Technical
211301 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.8.2.1 Common enclosure/cable Technical
211302 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.8.2.2 Segregation Technical
211303 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.8.3 Segregation of different voltage levels Technical
211304 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.8.4 Proximity to non-electrical services Technical
212306 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.9.1 Selection and installation to minimize the spread of fire - General Technical
211307 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.9.2 Selection and installation to minimize the spread of fire - Precautions Technical
211308 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.9.3 Penetration of fire barriers Technical
211309 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.10 Limitation of circulating and eddy currents Technical
211310 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.10.1 Limitation of circulating and eddy currents - General Technical
211311 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.10.2 Cables for a.c. circuits-Electromagnetic effects Technical
211312 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.10.3 Cables with non-ferrous metal sheathing Technical
211313 AS/NZS 3000:2018 +A1 Electrical Installations 3.9.11 Minimization of electromagnetic interference Technical
211316 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.1.1 ENCLOSURE OF CABLES - Insulated, unsheathed cables Technical
211317 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.1.2 ENCLOSURE OF CABLES - Insulated and sheathed cables Technical
211319 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.2.1 Wiring enclosures - Types Technical
211320 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.2.2 Change of wiring enclosures Technical
211321 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.2.3 Entry of water Technical
211323 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.1 Installation of wiring enclosures - General Technical
211324 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.2 Support Technical
211325 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.3 Continuity Technical
211326 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.4 Bending Technical
211327 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.5 Passage for conductors Technical
211328 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.6 Terminations Technical
211329 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.7 Installation in direct sunlight Technical
211330 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.8 Provision for expansion Technical
211331 AS/NZS 3000:2018 +A1 Electrical Installations 3.10.3.9 Cable trunking Technical
211333 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.1 UNDERGROUND WIRING SYSTEMS - Suitability and protection Technical
211334 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.2 Classification of wiring systems Technical
211336 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.3.1 Category A underground wiring systems Technical
211337 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.3.2 Category B underground wiring systems Technical
211338 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.3.3 Category C underground wiring system Technical
211340 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.4.1 Installation requirements - General Technical
211341 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.4.2 Unenclosed cables Technical
211342 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.4.3 Category B wiring system mechanical protection Technical
211343 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.4.4 Minimum depth of cover Technical
211344 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.4.5 Identification of underground wiring Technical
211345 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.4.6 Marking and recording of underground cable location Technical
211346 AS/NZS 3000:2018 +A1 Electrical Installations 3.11.5 Spacing from other underground services Technical
211348 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.1 AERIAL WIRING SYSTEMS - Types of conductor Technical
211350 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.2.1 Arrangements - Insulation of aerial conductors Technical
211351 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.2.2 Minimum size Technical
211352 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.3 Clearances Technical
211353 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.3.1 General Technical
211354 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.3.2 Safety warnings Technical
211355 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.4 Distance between supports (spans) Technical
211356 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.5 Aerial conductor supports Technical
211357 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.5.1 Aerial conductor supports - General Technical
211358 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.5.2 Pin-type insulators Technical
211359 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.5.3 Hardware Technical
211360 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.5.4 Spacing between conductors Technical
211361 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.6 Poles and posts (including supports, struts and extensions to structures) Technical
211362 AS/NZS 3000:2018 +A1 Electrical Installations 3.12.7 Joints and connections Technical
211364 AS/NZS 3000:2018 +A1 Electrical Installations 3.13.1 CABLES SUPPORTED BY A CATENARY - Types of cables Technical
211365 AS/NZS 3000:2018 +A1 Electrical Installations 3.13.2 Catenary supports Technical
211366 AS/NZS 3000:2018 +A1 Electrical Installations 3.13.3 Clearances Technical
211367 AS/NZS 3000:2018 +A1 Electrical Installations 3.14 SAFETY SERVICES Technical
211368 AS/NZS 3000:2018 +A1 Electrical Installations 3.15 BUSWAYS, INCLUDING RISING MAINS SYSTEMS Technical
211369 AS/NZS 3000:2018 +A1 Electrical Installations 3.16 EARTH SHEATH RETURN (ESR) SYSTEM Technical
211371 AS/NZS 3000:2018 +A1 Electrical Installations 4.1.2 Electrical equipment - Selection and installation Technical
211372 AS/NZS 3000:2018 +A1 Electrical Installations 4.1.3 External influences Technical
211373 AS/NZS 3000:2018 +A1 Electrical Installations 4.1.4 Adverse effects and interference Technical
211375 AS/NZS 3000:2018 +A1 Electrical Installations 4.2.1 PROTECTION AGAINST THERMAL EFFECTS - General Technical
211377 AS/NZS 3000:2018 +A1 Electrical Installations 4.2.2.1 Prevention of fire hazard - Installation of electrical equipment Technical
211378 AS/NZS 3000:2018 +A1 Electrical Installations 4.2.2.2 Storage of flammable materials Technical
211379 AS/NZS 3000:2018 +A1 Electrical Installations 4.2.2.3 Protection from high temperatures Technical
211380 AS/NZS 3000:2018 +A1 Electrical Installations 4.2.2.4 Emission of arcs or sparks Technical
211381 AS/NZS 3000:2018 +A1 Electrical Installations 4.2.2.5 Electrical equipment enclosures Technical
211382 AS/NZS 3000:2018 +A1 Electrical Installations 4.2.2.6 Prevention of spread of fire Technical
211383 AS/NZS 3000:2018 +A1 Electrical Installations 4.2.3 Protection against burns Technical
211385 AS/NZS 3000:2018 +A1 Electrical Installations 4.3.1 CONNECTION OF ELECTRICAL EQUIPMENT - General Technical
211387 AS/NZS 3000:2018 +A1 Electrical Installations 4.3.2.1 Direct connection - General Technical
211388 AS/NZS 3000:2018 +A1 Electrical Installations 4.3.2.2 Installation coupler Technical
211390 AS/NZS 3000:2018 +A1 Electrical Installations 4.3.3.1 Installation wiring connected by an installation coupler(s) - General Technical
211391 AS/NZS 3000:2018 +A1 Electrical Installations 4.3.3.2 Socket-outlets Technical
211392 AS/NZS 3000:2018 +A1 Electrical Installations 4.3.4 Socket-outlets in installation wiring Technical
211393 AS/NZS 3000:2018 +A1 Electrical Installations 4.3.5 Other connecting devices Technical
211394 AS/NZS 3000:2018 +A1 Electrical Installations 4.3.6 Equipment wiring Technical
211397 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.1.1.1 Socket-outlets-Application Technical
211398 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.1.1.2 Socket-outlets-Alternative pin configurations Technical
211399 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.1.1.3 Low voltage fixed socket-outlet Technical
211400 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.1.2 Different systems Technical
211401 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.1.3 Socket-outlets for electric vehicle charging Technical
211403 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.2.1 Location - Accessibility Technical
211404 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.2.2 Protection of socket-outlets Technical
211405 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.3 Earthing contacts Technical
213407 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.4.1 Switching device - General Testing
211408 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.4.2 Rating Technical
211409 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.4.3 Location and marking Technical
211410 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.4.4 Pendant-type socket-outlet Technical
213411 AS/NZS 3000:2018 +A1 Electrical Installations 4.4.5 Polarization and phase sequence Testing
211414 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.1.1 Lampholders, including lampholders incorporated in a luminaire - Location Technical
211415 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.1.2 Edison screw lampholders Technical
211416 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.1.3 Festoon lighting Technical
211418 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.1 Lamps and luminaires - General Technical
211419 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.2 Lamps near flammable materials Technical
211420 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.3 Recessed luminaires Technical
211421 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.3.1 General requirements Technical
211422 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.3.2 Warning sign Technical
211423 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.3.3 Installation Technical
211424 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.3.4 Classifications of recessed luminaires Technical
211425 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.3.5 Requirements for specific classifications Technical
211426 AS/NZS 3000:2018 +A1 Electrical Installations 4.5.2.4 Suspended ceilings Technical
211427 AS/NZS 3000:2018 +A1 Electrical Installations 4.6 SMOKE ALARMS Technical
211429 AS/NZS 3000:2018 +A1 Electrical Installations 4.7.1 COOKING APPLIANCES - Switching device Technical
211430 AS/NZS 3000:2018 +A1 Electrical Installations 4.7.3 Clearance from open cooking surfaces Technical
211432 AS/NZS 3000:2018 +A1 Electrical Installations 4.8.1 APPLIANCES PRODUCING HOT WATER OR STEAM - General Technical
211433 AS/NZS 3000:2018 +A1 Electrical Installations 4.8.2 Water heaters Technical
211434 AS/NZS 3000:2018 +A1 Electrical Installations 4.8.2.1 Access to easing equipment of pressure-relief and terminals of protective devices Technical
211435 AS/NZS 3000:2018 +A1 Electrical Installations 4.8.2.2 Protective devices fitted to unvented water heaters Technical
211436 AS/NZS 3000:2018 +A1 Electrical Installations 4.8.2.3 Isolating switch Technical
211438 AS/NZS 3000:2018 +A1 Electrical Installations 4.9.1 ROOM HEATERS - General Technical
211439 AS/NZS 3000:2018 +A1 Electrical Installations 4.9.2 Isolating switches Technical
211440 AS/NZS 3000:2018 +A1 Electrical Installations 4.9.3 Functional switches Technical
211442 AS/NZS 3000:2018 +A1 Electrical Installations 4.10.1 ELECTRIC HEATING CABLES FOR FLOORS AND CEILINGS AND TRACE HEATING APPLICATIONS - General Technical
211443 AS/NZS 3000:2018 +A1 Electrical Installations 4.10.2 Heating cables Technical
211444 AS/NZS 3000:2018 +A1 Electrical Installations 4.10.3 Isolating switches Technical
211445 AS/NZS 3000:2018 +A1 Electrical Installations 4.10.4 Functional switches Technical
211446 AS/NZS 3000:2018 +A1 Electrical Installations 4.10.5 Additional protection Technical
211447 AS/NZS 3000:2018 +A1 Electrical Installations 4.10.6 Signs Technical
211448 AS/NZS 3000:2018 +A1 Electrical Installations 4.11 ELECTRIC DUCT HEATERS Technical
211450 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.1 ELECTRICITY CONVERTERS - General Technical
211451 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.2 Selection and installation Technical
211452 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.3 Control Technical
211454 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.4.1 Isolation - General Technical
211455 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.4.2 Electricity converters incorporating batteries Technical
211457 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.5.1 Overcurrent protection - Electricity converter protection Technical
211458 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.5.2 Circuit protection Technical
211459 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.5.2.1 General Technical
211460 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.5.2.2 RCDs Technical
211461 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.6 Earthing Technical
211462 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.7 Neutral continuity Technical
211463 AS/NZS 3000:2018 +A1 Electrical Installations 4.12.8 Electrical equipment connected to output Technical
211465 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.1 MOTORS - Protection against injury from mechanical movement Technical
211466 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.1.1 Switching devices Technical
211467 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.1.2 Rating of switches Technical
211468 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.1.3 Devices for starting and stopping Technical
211469 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.1.4 Protection against restarting or reversal Technical
211470 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.2 Protection against overload Technical
211472 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.3.1 Protection against overtemperature - General Technical
211473 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.3.2 Protection prohibited Technical
211474 AS/NZS 3000:2018 +A1 Electrical Installations 4.13.3.3 Overtemperature protective device Technical
211476 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.1 TRANSFORMERS - General Technical
211477 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.2 Secondary circuit Technical
211478 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.2.1 General Technical
211479 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.2.2 Control and protection Technical
211480 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.3 Low voltage transformer supply Technical
211481 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.3.1 Isolating transformers Technical
211482 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.3.2 Other transformers Technical
211483 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.4 Autotransformers Technical
211484 AS/NZS 3000:2018 +A1 Electrical Installations 4.14.5 Step-up transformers Technical
211486 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.1 CAPACITORS - General Technical
211487 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.2 Electrical equipment Technical
211488 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.2.1 General Technical
211489 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.2.2 Rating of circuit-breakers, switches or contactors Technical
211490 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.2.3 Current-carrying capacity of supply conductors Technical
211491 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.3 Provision for discharge and control Technical
211492 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.3.1 General Technical
211493 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.3.2 Capacitors connected in parallel with individual appliances Technical
211494 AS/NZS 3000:2018 +A1 Electrical Installations 4.15.3.3 Capacitors not connected in parallel with individual appliances Technical
211496 AS/NZS 3000:2018 +A1 Electrical Installations 4.16.1 ELECTRICAL EQUIPMENT CONTAINING LIQUID DIELECTRICS - General Technical
211497 AS/NZS 3000:2018 +A1 Electrical Installations 4.16.2 Liquid dielectrics having a flashpoint not exceeding 250?C Technical
211498 AS/NZS 3000:2018 +A1 Electrical Installations 4.17 BATTERIES Technical
211501 AS/NZS 3000:2018 +A1 Electrical Installations 4.18.1.1 GAS APPLIANCES AND EQUIPMENT - General Technical
211502 AS/NZS 3000:2018 +A1 Electrical Installations 4.18.1.2 In Australia only Technical
211504 AS/NZS 3000:2018 +A1 Electrical Installations 4.18.2 Gas cylinders containing heavier-than-air gases-Outdoors Technical
211505 AS/NZS 3000:2018 +A1 Electrical Installations 4.18.2.1 Sources of ignition Technical
211506 AS/NZS 3000:2018 +A1 Electrical Installations 4.18.2.2 Hot particles and surfaces Technical
211507 AS/NZS 3000:2018 +A1 Electrical Installations 4.18.4 Gas relief vent terminal-Natural gas, LP Gas or Biogas Technical
211508 AS/NZS 3000:2018 +A1 Electrical Installations 4.19 AIRCONDITIONING AND HEAT PUMP SYSTEMS Technical
211510 AS/NZS 3000:2018 +A1 Electrical Installations 4.20.1 Lifts - General Technical
211511 AS/NZS 3000:2018 +A1 Electrical Installations 4.20.2 Lift supply arrangement Technical
211512 AS/NZS 3000:2018 +A1 Electrical Installations 4.20.3 Labelling Technical
211514 AS/NZS 3000:2018 +A1 Electrical Installations 4.20.4.1 Motor-room-less lifts (MRLs) - General Technical
211515 AS/NZS 3000:2018 +A1 Electrical Installations 4.20.4.2 MRL switchboards Technical
211516 AS/NZS 3000:2018 +A1 Electrical Installations 4.20.4.3 Switchgear Technical
211518 AS/NZS 3000:2018 +A1 Electrical Installations 5.1.2 Earthing - Selection and installation Technical
211519 AS/NZS 3000:2018 +A1 Electrical Installations 5.1.3 MEN earthing system Technical
211520 AS/NZS 3000:2018 +A1 Electrical Installations 5.1.4 Other earthing systems Technical
211522 AS/NZS 3000:2018 +A1 Electrical Installations 5.2.1 EARTHING FUNCTIONS - Protective earthing Technical
211523 AS/NZS 3000:2018 +A1 Electrical Installations 5.2.2 Functional earthing (FE) Technical
211524 AS/NZS 3000:2018 +A1 Electrical Installations 5.2.3 Earthing for combined protective and functional purposes Technical
211526 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.1 EARTHING SYSTEM PARTS - General Technical
211527 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2 Earthing conductor material and type Technical
211528 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2.1 Conductor material Technical
211529 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2.1.1 Copper conductors Technical
211530 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2.1.2 Aluminium conductors Technical
211531 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2.1.3 Other materials Technical
211532 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2.2 Conductor type Technical
211533 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2.3 Special conditions Technical
211534 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2.4 Insulation Technical
211535 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.2.5 Identification Technical
211538 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.3.1.1 Earthing conductor size - Protective earthing conductors - General Technical
211539 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.3.1.2 Selection Technical
211540 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.3.1.3 Calculation Technical
211541 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.3.2 Main earthing conductor Technical
211542 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.3.3 Aerial earthing conductors Technical
211543 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.3.4 Earthing conductors in cables, flexible cables or flexible cords Technical
211544 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.4 Main earthing terminal/connection or bar Technical
211546 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.5.1 MEN connection - General Technical
211547 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.5.2 Size Technical
211548 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.5.3 Identification Technical
211549 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.6 Earth electrodes Technical
211550 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.6.1 Earth electrodes - General Technical
211551 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.6.2 Types Technical
211552 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.6.3 Installation Technical
211553 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.6.4 Location Technical
211554 AS/NZS 3000:2018 +A1 Electrical Installations 5.3.7 Functional earthing conductors Technical
211558 AS/NZS 3000:2018 +A1 Electrical Installations 5.4.1.2 Conductive building materials Technical
211559 AS/NZS 3000:2018 +A1 Electrical Installations 5.4.1.3 Connection of electrical equipment to earth Technical
211560 AS/NZS 3000:2018 +A1 Electrical Installations 5.4.2 Socket-outlets Technical
211561 AS/NZS 3000:2018 +A1 Electrical Installations 5.4.3 Lighting points Technical
211562 AS/NZS 3000:2018 +A1 Electrical Installations 5.4.4 Luminaires Technical
211563 AS/NZS 3000:2018 +A1 Electrical Installations 5.4.5 Conductive supports for aerial conductors Technical
213566 AS/NZS 3000:2018 +A1 Electrical Installations 5.4.6.2 Connection to protective earthing conductors Testing
211567 AS/NZS 3000:2018 +A1 Electrical Installations 5.4.7 Submersible pumps Technical
211571 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.1.1 EARTHING ARRANGEMENTS - Main earthing conductor - Arrangement Technical
211572 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.1.2 Connection to earth electrode Technical
211573 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.1.3 Labelling Technical
211574 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.1.4 Resistance Technical
211576 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.2.1 Protective earthing conductors - Arrangement Technical
211577 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.2.2 Restricted connections Technical
211578 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.2.2.1 Circuits Technical
211579 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.2.2.2 Earthing of equipment Technical
211580 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.2.2.3 Earthing facilities for distribution boards Technical
211582 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.3.1 Particular methods of earthing - Outbuildings Technical
211583 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.3.2 Wiring systems Technical
211584 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.3.3 Electrical equipment supplied by flexible cord or flexible cable Technical
211585 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.3.4 Switchboards Technical
211586 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.3.5 Unprotected consumer mains Technical
211588 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.4.1 Continuity - General Technical
211589 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.4.2 Conductive wiring enclosures Technical
211590 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.4.3 Conductive sheaths, armours and screens of cables Technical
211591 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.4.4 Connecting devices Technical
211593 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.5.1 Installation - General Technical
211594 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.5.2 Protection against mechanical damage Technical
211595 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.5.3 Protection against corrosion Technical
211596 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.5.4 Aerial earthing conductors Technical
211597 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.5.5 Buried earthing conductors Technical
211599 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.6.1 Connections - Conductors Technical
211600 AS/NZS 3000:2018 +A1 Electrical Installations 5.5.6.2 Connections - Constructional components Technical
211602 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.1 EQUIPOTENTIAL BONDING - General Technical
211604 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.1 Arrangement - General Technical
211605 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.2 Conductive water piping Technical
211606 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.3 Other conductive piping systems Technical
211607 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.4 Conductive cable sheaths and conductive wiring enclosures Technical
211608 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.5 Showers and bathrooms Technical
211609 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.6 Swimming and spa pools Technical
211610 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.6.1 Bonding arrangement Technical
211611 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.6.2 Conductive pool structures Technical
211612 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.6.3 Pool equipotential bonding conductor connection point Technical
211613 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.6.4 Electrical equipment Technical
211614 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.6.5 Conductive fixtures and fittings Technical
211615 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.2.7 Telephone and telecommunication earthing systems Technical
211617 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.3.1 Bonding conductors - General Technical
211618 AS/NZS 3000:2018 +A1 Electrical Installations 5.6.3.2 Size Technical
211620 AS/NZS 3000:2018 +A1 Electrical Installations 5.7.1 EARTH FAULT-LOOP IMPEDANCE - General Technical
211621 AS/NZS 3000:2018 +A1 Electrical Installations 5.7.2 Disconnection times Technical
211622 AS/NZS 3000:2018 +A1 Electrical Installations 5.7.3 Earth fault-loop Technical
211623 AS/NZS 3000:2018 +A1 Electrical Installations 5.7.4 Impedance Technical
211624 AS/NZS 3000:2018 +A1 Electrical Installations 5.7.5 Supplementary equipotential bonding Technical
211625 AS/NZS 3000:2018 +A1 Electrical Installations 5.8 OTHER EARTHING ARRANGEMENTS Technical
211627 AS/NZS 3000:2018 +A1 Electrical Installations 6.1.2 Damp Situations - Selection and installation Technical
211628 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.1 BATHS, SHOWERS AND OTHER FIXED WATER CONTAINERS - Scope Technical
211629 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.2 BATHS, SHOWERS AND OTHER FIXED WATER CONTAINERS - Scope - Classification of zones Technical
211630 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.2.1 Baths and showers Technical
211631 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.2.2 Other fixed water containers Technical
212632 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.3 Protection against electric shock-Prohibited measures Unsafe
211633 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.4 Selection and installation of electrical equipment Technical
211634 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.4.1 Degree of protection required Technical
211635 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.4.2 Socket-outlets Technical
211636 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.4.3 Switches and other accessories Technical
211637 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.4.4 Luminaires Technical
211638 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.4.5 Other electrical equipment Technical
211639 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.4.6 Switchboards Technical
211640 AS/NZS 3000:2018 +A1 Electrical Installations 6.2.4.7 Electricity generation systems Technical
211642 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.2 SWIMMING POOLS, PADDLING POOLS AND SPA POOLS OR TUBS - Classification of zones Technical
211643 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.2.1 Swimming pools and paddling pools Technical
211644 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.2.2 Spa pools or tubs Technical
211645 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.2.2.1 General Technical
211646 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.2.2.2 Water capacity exceeding 5000 L Technical
211647 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.2.2.3 Water capacity not exceeding 5000 L Technical
211649 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.3.1 Prohibited measures Technical
211650 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.3.2 Supplementary equipotential bonding Technical
212651 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.3.3 Voltage gradients Unsafe
211652 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.4 Selection and installation of electrical equipment Technical
211653 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.4.1 Degree of protection required Technical
211654 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.4.2 Wiring systems Technical
211655 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.4.3 Socket-outlets Technical
211656 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.4.4 Switches and other accessories Technical
211658 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.4.6 Switchboards Technical
211659 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.4.7 Electricity generation systems Technical
211660 AS/NZS 3000:2018 +A1 Electrical Installations 6.3.4.8 Electricity distributer?s electrical equipment Technical
211662 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.2 Fountains and water features - Classification of zones Technical
212663 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.3 Protection against electric shock Unsafe
211664 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.3.1 Use of SELV Technical
212667 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.3.2.2 Prohibited measures Unsafe
211668 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.4 Selection and installation of electrical equipment Technical
211669 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.4.1 Degree of protection required Technical
211670 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.4.2 Wiring systems Technical
211671 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.4.3 Socket-outlets Technical
211672 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.4.4 Switches and other accessories Technical
211674 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.4.6 Switchboards Technical
211675 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.4.7 Electricity generation systems Technical
211676 AS/NZS 3000:2018 +A1 Electrical Installations 6.4.4.8 Electricity distributer?s electrical equipment Technical
211678 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.2 Saunas - Classification of zones Technical
211680 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.3.1 Use of SELV Technical
212681 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.3.2 Protection against electric shock - Prohibited measures Unsafe
211683 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.4 Selection and installation of electrical equipment Technical
211684 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.4.1 Degree of protection required Technical
211685 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.4.2 Requirements in classified zones Technical
211686 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.4.3 Wiring systems Technical
211687 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.4.4 Socket-outlets, switches and other accessories Technical
211688 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.4.5 Sauna heating appliances Technical
211689 AS/NZS 3000:2018 +A1 Electrical Installations 6.5.4.6 Switchboards Technical
211692 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.2.1 Refrigeration rooms - Protection against electric shock - Use of SELV Technical
212693 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.2.2 Protection against electric shock - Prohibited measures Unsafe
211694 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3 Selection and installation of electrical equipment Technical
211695 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.1 Degree of protection required Technical
211696 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.2 Wiring systems Technical
211697 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.2.1 General Technical
211698 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.2.2 Types permitted Technical
211699 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.2.3 Sealing Technical
211700 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.3 Socket-outlets, switches and other accessories Technical
211701 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.4 Luminaires, lampholders and other equipment Technical
211702 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.4.1 Luminaires Technical
211703 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.4.2 Lampholders Technical
211704 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.5 Fixed appliances and motors Technical
211705 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.6 Heating elements in door seals Technical
211706 AS/NZS 3000:2018 +A1 Electrical Installations 6.6.3.7 Switchboards Technical
211708 AS/NZS 3000:2018 +A1 Electrical Installations 6.7.2 Sanitization & Hosing down operations - Classification of zone Technical
211710 AS/NZS 3000:2018 +A1 Electrical Installations 6.7.3.1 Protection against electric shock - Use of SELV Technical
212711 AS/NZS 3000:2018 +A1 Electrical Installations 6.7.3.2 Protection against electric shock - Prohibited measures Unsafe
211712 AS/NZS 3000:2018 +A1 Electrical Installations 6.7.4 Selection and installation of electrical equipment Technical
211713 AS/NZS 3000:2018 +A1 Electrical Installations 6.7.4.1 Degree of protection required Technical
211714 AS/NZS 3000:2018 +A1 Electrical Installations 6.7.4.2 Electrical equipment Technical
211715 AS/NZS 3000:2018 +A1 Electrical Installations 6.7.4.3 Switchboards Technical
211718 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.1.2 Safety Services - General Technical
211720 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.2.1 Supply systems - General Technical
211721 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.2.2 Wiring systems (mains, submains, main switchboard and supplies to outbuildings) Technical
211722 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.2.2.1 WS classification provided Technical
211723 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.2.2.2 WS classification is not provided Technical
211724 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.2.3 Alternative supply systems Technical
211725 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.2.3.1 Continued occupation Technical
211726 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.2.3.2 Fire management system Technical
211728 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.3.1 Main switchboard and switchgear - General Technical
211729 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.3.2 Switchgear Technical
211730 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.3.3 Cables in the same enclosure Technical
211731 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.3.4 Arrangement Technical
211732 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.3.5 Discrimination (selectivity) of circuit-protective devices Technical
211734 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.4.1 Main switches - General Technical
211735 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.4.2 Number of main switches Technical
211736 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.4.3 Mechanical protection Technical
211737 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.4.4 Identification Technical
211738 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.4.5 Electrical installations in outbuildings Technical
211739 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.4.6 Fire separated portions of a building Technical
211741 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.1 Fire pumps and fire pump control equipment - General Technical
211742 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.2 Wiring systems supplying fire pumps and fire pump control equipment Technical
211743 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.2.1 Types of wiring systems Technical
211744 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.2.2 Segregation of cables Technical
211745 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.3 Switchgear for fire pumps and fire pump control equipment Technical
211746 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.4 Interposing switches for fire pumps and fire pump control equipment Technical
211747 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.5 Pump rooms for fire pumps and fire pump control equipment Technical
211748 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.6 Fire-pump motors Technical
211749 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.6.1 Isolating switches for fire-pump motors Technical
211750 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.6.2 Overcurrent protection for fire-pump motors Technical
211751 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.6.3 Overtemperature protection for fire-pump motors Technical
211752 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.5.6.4 Control circuits for fire-pump motors Technical
211754 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.6.1 Fire and smoke detection equipment and fire alarm systems - General Technical
211755 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.6.2 Wiring systems for fire detection and alarm systems Technical
211756 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.6.2.1 Types of wiring systems for fire detection and alarm systems Technical
211757 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.6.2.2 Segregation of cables for fire detection and alarm systems Technical
211758 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.6.3 Interposing switches for fire detection and alarm systems Technical
211760 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.7.1 Air-handling systems - General Technical
211761 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.7.2 Wiring systems for air-handling systems Technical
211762 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.7.2.1 Types of wiring system for air-handling systems Technical
211763 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.7.2.2 Segregation of cables for air-handling systems Technical
211764 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.7.2.3 Interposing switches for air-handling systems Technical
211766 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.8.1 Evacuation equipment - General Technical
211767 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.8.2 Wiring systems for evacuation equipment Technical
211768 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.8.2.1 Types of wiring system forevacuation equipment Technical
211769 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.7.2.2 Segregation of cables forevacuation equipment Technical
211770 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.3 Interposing switches for evacuation equipment Technical
211772 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.9.1 Emergency lifts - General Technical
211773 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.9.1.1 In Australia Technical
212774 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.9.2 Control and protection Technical
211775 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.9.3 Wiring systems for emergency lifts Technical
211776 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.9.3.1 Types of wiring system for emergency lifts Technical
211777 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.9.3.2 Segregation of cables Technical
211778 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.9.4 Interposing switches Technical
211779 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.9.5 Switchgear Technical
211781 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.10.1 Emergency motor-room-less lifts - General Technical
211782 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.10.2 Switchboards Technical
211783 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.10.3 Switchgear Technical
211784 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.10.4 Wiring systems Technical
211785 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.10.4.1 Types of wiring systems for MRL lifts Technical
211786 AS/NZS 3000:2018 +A1 Electrical Installations 7.2.10.4.2 Segregation of cables Technical
211788 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.1 ELECTRICITY GENERATION SYSTEMS - General Technical
211789 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.2 Selection and installation of system Technical
211790 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.3 Control Technical
211793 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.4.1 Isolation - General Technical
211794 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.4.2 Electricity generation systems incorporating batteries Technical
211796 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.5.1 Overcurrent protection - Electricity generation system protection Technical
211797 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.5.2 Circuit protection Technical
211798 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.5.2.1 General Technical
211799 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.5.2.2 RCDs Technical
211800 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.6 Earthing Technical
211801 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.7 Connected electrical equipment Technical
211804 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.1.1 Alternative supplies - General Technical
211805 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.1.2 Switching Technical
211806 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.2 Grid-connected inverter systems Technical
211807 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.2.1 General Technical
211808 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.2.2 Switching Technical
211809 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.2.3 Connection Technical
211810 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.3 Stand-alone power systems Technical
211811 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.3.1 General Technical
211812 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.3.2 Switching Technical
211813 AS/NZS 3000:2018 +A1 Electrical Installations 7.3.8.3.3 Connection Technical
211815 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.1 PROTECTION BY ELECTRICAL SEPARATION (ISOLATED SUPPLY) - General Technical
211816 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.2 Source of supply Technical
211817 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.3 Arrangement of circuits Technical
211818 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.4 Switching devices Technical
211819 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.5 Supply to single item of electrical equipment Technical
211820 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.6 Supply to multiple items of electrical equipment Technical
211821 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.7 Variable speed drive (VSD) EMI filters Technical
213823 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.8.1 Testing - General Testing
213824 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.8.2 Single items of electrical equipment Testing
213825 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.8.3 Multiple items of electrical equipment Testing
213826 AS/NZS 3000:2018 +A1 Electrical Installations 7.4.8.4 Bonding conductor continuity Testing
211828 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.2 EXTRA-LOW VOLTAGE ELECTRICAL INSTALLATIONS - Application Technical
211829 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.3 Sources of supply to SELV and PELV systems Technical
211830 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.4 Separation requirements for SELV and PELV circuits Technical
211831 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.5 Arrangement of SELV circuits Technical
211832 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.6 Arrangement of PELV circuits Technical
211833 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.7 Voltage drop in conductors Technical
211834 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.8 Control of an electrical installation Technical
211835 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.8.1 Main switches Technical
211836 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.8.2 Other switches Technical
211837 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.9 Overcurrent protection Technical
211838 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.9.1 General Technical
211839 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.9.2 Omission of overcurrent protection Technical
211840 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.10 Connecting devices Technical
211841 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.11 Wiring systems Technical
211842 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.11.1 General Technical
211843 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.11.2 Aerial conductors Technical
211844 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.11.3 Underground conductors Technical
211845 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.12 Testing Technical
213846 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.12.1 General Testing
213847 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.12.2 Protection by SELV Testing
213848 AS/NZS 3000:2018 +A1 Electrical Installations 7.5.12.3 Protection by PELV Testing
211850 AS/NZS 3000:2018 +A1 Electrical Installations 7.6.2 HIGH VOLTAGE ELECTRICAL INSTALLATIONS - Application Technical
211851 AS/NZS 3000:2018 +A1 Electrical Installations 7.6.2.1 In Australia Technical
211852 AS/NZS 3000:2018 +A1 Electrical Installations 7.6.3 Issues relevant to high voltage installations Technical
211854 AS/NZS 3000:2018 +A1 Electrical Installations 7.7.2 HAZARDOUS AREAS (EXPLOSIVE GAS OR COMBUSTIBLE DUSTS) - Classification of hazardous areas Technical
211855 AS/NZS 3000:2018 +A1 Electrical Installations 7.7.2.1 Responsibility for classification Technical
211856 AS/NZS 3000:2018 +A1 Electrical Installations 7.7.2.2 Hazardous areas (AS/NZS 60079 series) Technical
211857 AS/NZS 3000:2018 +A1 Electrical Installations 7.7.2.3 Reduction or elimination of the hazard Technical
211858 AS/NZS 3000:2018 +A1 Electrical Installations 7.7.2.4 Electrical equipment Technical
211859 AS/NZS 3000:2018 +A1 Electrical Installations 7.7.2.4.1 Selection Technical
211860 AS/NZS 3000:2018 +A1 Electrical Installations 7.7.2.4.2 Installation Technical
211863 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2 STANDARDS FOR SPECIFIC ELECTRICAL INSTALLATIONS - Standards containing additional requirements Technical
211864 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.1 Construction and demolition sites Technical
211865 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.2 Electro medical treatment areas Technical
211866 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.3 Transportable structures and vehicles including their site supplies Technical
211867 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.4 Marinas and recreational boats Technical
211868 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.5 Shows and carnivals Technical
211869 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.6 Telecommunication network power supplies Technical
211870 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.7 Cranes and hoists Technical
211871 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.8 Lifts Technical
211872 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.9 High voltage installations Technical
211873 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.10 Generating sets Technical
211874 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.11 Inverters Technical
211875 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.12 Low voltage switch gear and control gear assemblies Technical
211876 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.13 Stand-alone power systems Technical
211877 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.14 Photovoltaic (PV) arrays Technical
211878 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.15 Secondary battery systems Technical
211879 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.16 Mobile medical facilities (NZ only) Technical
211880 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.17 Floor and ceiling heating systems (NZ only) Technical
211881 AS/NZS 3000:2018 +A1 Electrical Installations 7.8.2.18 Explosive atmospheres and hazardous areas Technical
211883 AS/NZS 3000:2018 +A1 Electrical Installations 8.1.2 Verification - General requirements Technical
211884 AS/NZS 3000:2018 +A1 Electrical Installations 8.1.3 Periodic inspection and testing Technical
211886 AS/NZS 3000:2018 +A1 Electrical Installations 8.2.1 VISUAL INSPECTION - General Technical
211887 AS/NZS 3000:2018 +A1 Electrical Installations 8.2.2 Checklist Technical
211889 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.1 TESTING - General Technical
211890 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.2 Test methods Technical
213891 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.3 Mandatory tests Testing
211892 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.3.1 Low voltage Technical
211893 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.3.2 Extra-low voltage Technical
211894 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.3.3 Test failures Technical
213897 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.5.1 Continuity of the earthing system - General Testing
213898 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.5.2 Continuity of the earthing system - Results Testing
213900 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.6.1 Insulation resistance- General Testing
213901 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.6.2 Insulation resistance - Method Testing
213904 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.7.1 Polarity - General Testing
212905 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.7.2(a) Polarity - Results Unsafe
213907 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.8.1 Correct circuit connections - General Testing
212908 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.8.2 Correct circuit connections - Results Unsafe
211910 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.9.1 Verification of earth fault-loop impedance (EFLI) - Low voltage socket-outlet circuits Technical
211912 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.9.2.1 Methods - General Technical
213913 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.9.2.2 Supply available Testing
213914 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.9.2.3 No supply available Testing
213915 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.9.3 Results Testing
213916 AS/NZS 3000:2018 +A1 Electrical Installations 8.3.10 Operation of RCDs Testing
211917 AS/NZS 3000:2018 +A1 Electrical Installations 8.4 VERIFICATION RECORDS Technical
811001 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 1.2 APPLICATION Technical
811002 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.1 SUPPLY ARRANGEMENTS Technical
811003 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.1 Supply from service pillar Technical
811004 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.2 Underground wiring providing site supply Technical
811005 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.3 Overhead wiring providing the site supply Technical
811006 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.4 Earthing - In Australia Technical
811007 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.5 Maximum demand Technical
811008 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.6 Caravan park service pillars Technical
811009 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.7 Socket-outlets Technical
811010 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.8 Construction of caravan park service pillars Technical
811011 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.9 Other switchboards Technical
811012 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.2.10 Other socket-outlets Technical
811013 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.1 Supply from socket-outlet Technical
811014 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.2 Configuration and rating Technical
811015 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.3 Overload protection Technical
811016 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.4 Protection against earth leakage current Technical
811017 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.5 Control Technical
811018 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.6 Common overload, earth leakage and control device Technical
811019 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.7 Weatherproofing Technical
811020 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.8 Doors and covers Technical
811021 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.3.9 Strain relief Technical
811022 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.4.1 Requirements for portable generator sets or inverters Technical
811023 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.4.2 Overcurrent protection Technical
811024 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.4.3 Earth leakage protection Technical
811025 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.4.4 Combined overcurrent and earth leakage protection Technical
811026 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.6 SITES FOR LOW-CONSUMPTION TRANSPORTABLE STRUCTURES Technical
811027 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 2.7.1 Initial verification of the installation Technical
811028 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.2.1 PROVISION FOR CONNECTION TO SITE SUPPLY - General Technical
811029 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.2.2 Detachable connection at the transportable structure or vehicle Technical
811030 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.2.3 Permanent connection of the supply lead Technical
811031 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.2.4 Multiple connections Technical
811032 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.3 CONTROL AND PROTECTION Technical
811033 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.3.1 Overcurrent protection Technical
811034 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.3.2 Protection against earth leakage current Technical
811035 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.3.3 Location Technical
811036 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.3.4 Prohibited equipment Technical
811037 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.4.1 WIRING SYSTEM - Size and type of cable Technical
811038 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.4.2 Protection from damage Technical
811039 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.4.3 Fixing Technical
811040 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.4.4 Isolation and segregation Technical
811041 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.5.1 EARTHING - Detachable connection, General Technical
811042 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.5.2 Equipotential bonding Technical
811043 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.6.1 ACCESSORIES - Mounting Technical
811044 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.6.2 Switches Technical
811045 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.6.3 Socket-outlets Technical
811046 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.7.1 PERMANENTLY CONNECTED APPLIANCES - Control Technical
811047 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.7.2 Over-temperature cut-out Technical
811048 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.9 ELECTRICAL INSTALLATIONS IN DAMP AREAS Technical
811049 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 3.10.1 Initial verification of the installation Technical
811050 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.1 GENERAL Technical
811051 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.2.1 SUPPLY TO ELECTRICAL EQUIPMENT - One item to be supplied Technical
811052 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.2.2 More than one item to be supplied Technical
811053 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.3.1 CONNECTION OF SUPPLY - General Technical
811054 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.3.2 Multiple transportable structures occupying the one site Technical
811055 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.3.3 Restriction on connection Technical
811056 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.3.4 Prohibited connections Technical
811057 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.1 OUTLET BOX - General Technical
811058 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.2 Construction Technical
811059 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.3 Termination of supply lead Technical
811060 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.4 Socket-outlets Technical
811061 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.5 Earthing Technical
811062 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.6 Overcurrent protection Technical
811063 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.7 Protection against earth leakage current Technical
811064 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.8 Control switches Technical
811065 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.9 Marking Technical
811066 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.4.10 LIGHTING Technical
811067 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.5.1 Handlamps Technical
811068 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 4.5.2 Lighting equipment other than handlamps Technical
811069 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 5.1.1 SUPPLY LEAD - General Technical
811070 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 5.1.2 Technical details Technical
811071 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 5.1.3 Length Technical
811072 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 5.1.4 Coiled leads Technical
811073 AS/NZS 3001:2008 Transportable structures and vehicles including their site supplies 5.2 INSTALLATION OF SUPPLY LEAD Technical
821001 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 1.2 APPLICATION Technical
821002 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.1.1 General Technical
821003 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.1.2 Underground wiring Technical
821004 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.1.3 Overhead wiring Technical
821005 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.2 MAXIMUM DEMAND Technical
821006 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.3.1 General Technical
821007 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.3.2 Enclosure Technical
821008 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.3.3 Socket-outlets Technical
821009 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.3.4 Other connection facilities Technical
821010 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.3.5 Overload protection Technical
821011 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.3.6 RCD Protection Technical
821012 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.3.7 Control and isolation Technical
821013 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.4.1 SWITCHBOARDS - General Technical
821014 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.4.2 Enclosure Technical
821015 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.5.1 LOCATION AND MOUNTING OF SWITCHBOARD ENCLOSURES Technical
821016 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.5.2 Socket-outlets Technical
821017 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 2.5.3 Identification Technical
821018 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 3.1 GENERAL Technical
821019 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 3.2 GENERATING SETS Technical
821020 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 3.3 INVERTERS Technical
821021 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 3.4 RCD TYPE FOR GENERATOR SETS AND SWITCHBOARDS Technical
821022 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.2.1 Cable selection Technical
821023 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.2.2 Installation of cables Technical
821024 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.2.3 Connection of cables Technical
821025 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.3.1 CASCADABLE RETICULATION UNITS - General Technical
821026 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.3.2 Enclosure Technical
821027 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.3.3 Location and mounting of cascadable reticulation units Technical
821028 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.4.1 OUTLET BOXES - General Technical
821029 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.4.2 Construction Technical
821030 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.4.3 Termination of supply lead Technical
821031 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.4.4 Socket-outlets Technical
821032 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.4.5 Earthing Technical
821033 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.4.6 Overcurrent protection Technical
821035 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.4.8 Control switches Technical
821036 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.4.9 Marking Technical
821037 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.5.1 ELECTRICAL PORTABLE OUTLET DEVICES - General Technical
821038 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.5.2 Connection to low-voltage electrical power supply Technical
821039 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.5.3 Location Technical
821041 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.6.1 FESTOON AND DECORATIVE LIGHTING - General Technical
821042 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.6.2 Clearances Technical
821043 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.6.3 Loading of final subcircuits Technical
821044 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.6.4 Decorative lighting outfits Technical
821046 AS/NZS 3002:2008 Electrical installations - Shows and carnivals 4.7 RIDING DEVICES Technical
831001 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.1.1 WIRING DETAILS - General Technical
831002 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.1.2 Selection of electrical wiring systems Technical
831003 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.1.3 Earthing system Technical
831004 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.2 MAXIMUM DEMAND OF MAINS AND SUBMAINS Technical
831005 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.3.1 ISOLATING TRANSFORMERS- General Technical
831006 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.3.2 Protection Technical
831007 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.4.1 SWITCHBOARDS PROVIDING LOW-VOLTAGE ELECTRICAL SUPPLY TO BOATS - General Technical
831008 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.4.2 Service pillars Technical
831009 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.4.3 Other switchboards Technical
831010 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 2.5 OTHER SOCKET-OUTLETS Technical
831011 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 3.1.1 SUPPLY LEAD - General Technical
831012 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 3.1.2 Coiled leads Technical
831013 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 3.2 INSTALLATION OF SUPPLY LEAD Technical
831014 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 3.3.1 EARTHING - General Technical
831015 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 3.3.2 Supply through a shore-mounted isolating transformer Technical
831016 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 3.3.3 Supply through an on-board isolating transformer Technical
831017 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 3.3.4 Supply without an isolating transformer Technical
831018 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 4.1 GENERAL Technical
833019 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 4.2.1 PERIODIC VERIFICATION - Testing Testing
831020 AS/NZS 3004.1:2014 Electrical installations - Marinas and boats Marinas 4.2.2 Recording of results Technical
611001 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.1 GENERAL Technical
611002 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.1.1 Scope of Section Technical
611003 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.1.2 Rating classifications Technical
611004 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.1.3 Selection of generating set rating Technical
611005 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.1.4 Generating set system of supply Technical
611006 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.2 LOCATION Technical
611007 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.3 MECHANICAL AND THERMAL PROTECTION Technical
611008 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.3.1 Protection from mechanical damage Technical
611009 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.3.2 Protection from moving parts Technical
611010 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.3.3 Protection against thermal effects Technical
611011 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.3.4 Protection against fuel leakage Technical
611012 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.4 CONTROL OF GENERATING SET Technical
611013 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.4.1 General Technical
611014 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.4.2 Prime mover isolating devices Technical
611015 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.4.2.1 Operation Technical
611016 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.4.2.2 Location Technical
611017 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.4.3 Synchronization Technical
611018 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.4.4 Starting batteries and battery charging Technical
611019 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.5 EARTHING ARRANGEMENTS Technical
611020 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.6 ELECTRICAL INSTALLATION Technical
611021 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.6.1 General requirements Technical
611022 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.6.1.1 General Technical
611023 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.6.1.2 Isolation from the normal supply system Technical
611024 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.6.1.3 Generating set neutral conductor Technical
611025 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.6.2 Overcurrent protection Technical
611026 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.6.3 Generator output isolator Technical
611027 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7 ALTERNATIVE SUPPLY (STANDBY) Technical
611028 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.1 General Technical
611029 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.2 Operation Technical
611030 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.3 Interlocking Technical
611031 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.4 Changeover device with intermediate ?off? position Technical
611032 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.5 Changeover device without an intermediate ?off? position Technical
611033 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.6 Rating Technical
611034 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.7 Access Technical
611035 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.8 Identification Technical
611036 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.9 Automatic changeover to normal supply Technical
611037 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.10 Changeover device in the generator neutral Technical
611038 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.10.1 In Australia Technical
611039 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.11 Three pole/three pole changeover devices Technical
611040 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.12 Three pole/four pole changeover devices Technical
611041 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.7.13 Four pole/four pole changeover device Technical
611042 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8 EARTHING AND BONDING REQUIREMENTS Technical
611043 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.1 General Technical
611044 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.2 Earthing and bonding alterations to existing installations Technical
611045 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.3 Generating set bonding system Technical
611046 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.4 Generating set windings Technical
611047 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.4.1 Multi-phase and single-phase three wire centre-tapped generating sets Technical
611048 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.4.2 Single-phase portable generating sets Technical
611049 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.5 Connection of generating set windings Technical
611050 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.6 Arrangement of equipment Technical
611051 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.7 Rating Technical
611052 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.8 Provisions for securing isolating devices Technical
611053 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.8.9 Indication of switch position Technical
611054 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.9 GENERATOR SWITCHBOARDS Technical
611055 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.1 LIGHTNING PROTECTION SYSTEMS Technical
611056 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11 GENERATING SETS CONNECTED AS NORMAL SUPPLY TO A MAIN SWITCHBOARD IN A PERMANENT ELECTRICAL INSTALLATION Technical
611057 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11.1 Generating set Technical
611058 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11.2 System of supply for generating set and main switchboard Technical
611059 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11.2.1 Overcurrent protection Technical
611060 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11.2.2 Connection to the electrical installation Technical
611061 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11.2.3 Earthing and equipotential bond connections Technical
611062 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11.2.4 Unsuitable electrical equipment Technical
611063 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11.2.5 Connection details Technical
611064 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.11.3 Other systems of supply Technical
611065 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.12 GENERATING SETS CONNECTED TO AN ELECTRICAL INSTALLATION CONNECTED AS AN ALTERNATIVE SUPPLY Technical
611066 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.12.1 General Technical
611067 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.12.2 System of supply for the generating set and switchboards Technical
611068 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.12.2.1 Overcurrent protection Technical
611069 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 2.12.2.2 Connection to switchboards Technical
611070 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.1 GENERAL Technical
611071 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2 LOCATION Technical
611072 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.1 General Technical
611073 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.2 Access space for generating sets Technical
611074 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.3 Exit from generating set area Technical
611075 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.3.1 General Technical
611076 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.3.2 Number of openings Technical
611077 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.3.3 Opening and locking of doors Technical
611078 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.3.4 Size of doors and openings Technical
611079 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.4 Ventilation Technical
611080 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.5 Noise containment Technical
611081 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.2.6 Lighting Technical
611082 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.3 GUARDING OF LIVE PARTS Technical
611083 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.3.1 General Technical
611084 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.3.2 Walked on surfaces Technical
611085 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.3.3 Outdoor locations Technical
611086 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.4 TRANSFORMERS Technical
611087 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.5 GENERATING SETS SUPPLYING SAFETY AND ESSENTIAL SERVICES Technical
611088 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.5.1 General Technical
611089 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.5.2 Type Technical
611090 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.5.3 Overcurrent protection Technical
611091 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.5.4 Paralleling sources of supply Technical
611092 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.5.5 Supply of other than safety services or essential services Technical
611093 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.5.6 Automatic changeover to an emergency essential or supply system Technical
611094 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 3.5.7 Switchgear Technical
611095 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.1 GENERAL Technical
611096 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.2 CONNECTION TO AN ELECTRICAL INSTALLATION Technical
611097 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.2.1 General Technical
611098 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.2.2 Connection to an installation Technical
611099 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.2.3 Connection Technical
611100 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.3 EARTHING AND BONDING Technical
611101 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.3.1 General Technical
611102 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.3.2 Connection of generating set windings Technical
611103 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.3.2.1 Multi-phase and single-phase generating sets Technical
611104 AS/NZS 3010:2017 +A1Electrical installations - Generating sets 4.3.2.2 Earth electrode Technical
841001 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 1.2 APPLICATION Technical
841002 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.1 SUPPLY Technical
841003 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.1.1 Construction wiring Technical
841004 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.1.2 Appliances, luminaires and electrical equipment Technical
841005 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.1.3 Identification of source of supply Technical
841006 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.1.4 Connection devices Technical
841007 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.1.5 Polarization Technical
841008 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.1.6 Separate circuit requirements Technical
841009 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.2 MAXIMUM DEMAND Technical
841011 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.3.1.1 Switchboards - Location - General Technical
841012 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.3.1.2 Distribution boards Technical
841014 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.3.2.1 Switchboard construction - General requirements Technical
841015 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.3.2.2 Assemblies for Construction sites (ACS) switchboard construction Technical
841016 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.3.3 Mounting of switchboards Technical
841017 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.3.4 Socket-outlets Technical
841018 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.3.5 Support of cables entering switchboards Technical
841019 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.1 Control Technical
841020 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.2 Securing of isolating switch Technical
841021 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.3 Marking of isolating switches Technical
841022 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.4 Size of marking Technical
841023 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.5.1 Sub-mains Technical
841024 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.5.2 Final sub-circuits Technical
841027 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.6.3 Electrical equipment supplied by low-voltage generators Technical
841028 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.6.4 Electrical equipment supplied by inverters Technical
841029 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.6.5 Permanent wiring located where construction or demolition work may be carried out Technical
841030 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.4.7 Switching of single-phase socket-outlets Technical
841031 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.5.1 Cables and fittings Technical
841032 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.5.2 Installation of cables Technical
841033 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.5.3 Protection against mechanical damage Technical
841034 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.5.4 Marking Technical
841035 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.5.5 Use of unarmoured cables Technical
841036 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.5.6 Location and marking of overhead wiring (including aerial and catenary wiring) Technical
841037 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.5.7 Type of aerial conductor Technical
841038 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.5.8 Cables supported by a catenary Technical
841039 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.1 General Technical
841040 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.2 Minimum conductor size and core configuration Technical
841041 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.3 Type of flexible cord and cable Technical
841042 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.4 Colour Technical
841043 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.5 Current-carrying capacity Technical
841044 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.6 Accessories for connection Technical
841045 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.7 Maximum length Technical
841046 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.8 Limitations on the use of cord extension sets Technical
841047 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.9 Protection of flexible cords or cables Technical
841048 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.10 Portable socket-outlet assemblies (PSOAs) Technical
841049 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.11 Auxiliary socket-outlet panels Technical
841050 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.6.12 Electrical portable outlet devices (EPODS) Technical
841051 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.7.2 lighting and luminaires - Mechanical protection Technical
841052 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.7.3.1 Emergency lighting - General Technical
841053 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.7.3.2 Verification Technical
841054 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.7.4 Hand-held luminaires Technical
841055 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.7.5 Edison screw type lampholders Technical
841056 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.7.6 Festoon lighting Technical
841057 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.7.7 Portable luminaires Technical
841058 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.8.1 Lift Shafts - General Technical
841059 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.8.2 Multiple lift shafts Technical
841060 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.8.3 Emergency lighting Technical
841061 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.8.4 False-car (Guided work platform) Technical
841062 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 2.9 TRANSPORTABLE STRUCTURES Technical
841063 AS/NZS 3012:2019 Electrical installations - Construction and demolition sites 3.2 FREQUENCY OF VERIFICATION (INSPECTION AND TESTING) Technical
851001 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.1.1 Hydrogen emission Technical
851002 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.1.2 Alarms Technical
851003 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.1.3 Battery accommodation Technical
851004 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.1.4 Arrangement of cells Technical
851005 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.1.5 Ventilation Technical
851006 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.2.1 BATTERY ROOM REQUIREMENTS - General Technical
851007 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.2.2 Battery room layout and floor area Technical
851008 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.2.3 Take-off battery terminals and outgoing busbars and cables Technical
851009 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.2.4 Inter-tier and inter-row connections Technical
851010 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.2.5 Inter-cell connectors Technical
851011 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.2.6 Location of luminaires Technical
851012 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.3.1 BATTERY ENCLOSURE REQUIREMENTS - Enclosure construction Technical
851013 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.3.2 Take-off battery terminals and outgoing busbars and cables Technical
851014 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 2.3.3 Battery compartment circuits Technical
851015 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.1 INSTALLATION - GENERAL Technical
851016 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.2 CONNECTIONS Technical
851017 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.3.1 Overcurrent protection Technical
851018 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.3.2 Warning notices Technical
851019 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.3.3 Switchgear Technical
851020 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.3.4 Earth-leakage detection Technical
851021 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.3.5 Main isolating switch Technical
851022 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.3.6 Section isolating equipment Technical
851023 AS 3011.1:2019 Secondary batteries installed in buildings Vented cells 3.3.7 Fire safety and warning signs Technical
861001 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.1.1 Hydrogen emission Technical
861002 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.1.2 Alarms Technical
861003 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.1.3 Battery accommodation Technical
861004 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.1.4 Arrangement of cells Technical
861005 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.1.5 Ventilation Technical
861006 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.2.1 BATTERY ROOM REQUIREMENTS - General Technical
861007 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.2.2 Battery room layout and floor area Technical
861008 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.2.3 Take-off battery terminals and outgoing busbars and cables Technical
861009 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.2.4 Inter-tier and inter-row connections Technical
861010 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.2.5 Inter-cell connectors Technical
861011 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.2.6 Luminaires Technical
861012 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.3.1 BATTERY ENCLOSURE REQUIREMENTS - Enclosure construction Technical
861013 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.3.2 Take-off battery terminals and outgoing busbars and cables Technical
861014 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 2.3.3 Battery compartment circuits Technical
861015 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.1 INSTALLATION - GENERAL Technical
861016 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.2 CONNECTIONS Technical
861017 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.3.1 Overcurrent protection Technical
861018 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.3.2 Warning notices Technical
861019 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.3.3 Switchgear Technical
861020 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.3.4 Earth-leakage detection Technical
861021 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.3.5 Main isolating switch Technical
861022 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.3.6 Section isolating equipment Technical
861023 AS 3011.2:2019 Secondary batteries installed in buildings Sealed cells 3.3.7 Fire safety and warning signs Technical
311001 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.1 GENERAL Technical
311002 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.2 CLASSIFICATION OF PATIENT AREAS Technical
311003 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.2.1 Documentation Technical
311004 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.2.2 Patient area boundaries Technical
311005 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.2.3 Patient areas required to be wired as cardiac-protected electrical areas Technical
311006 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.2.4 Patient areas required to be wired as body-protected electrical areas Technical
311007 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.3 SUPPLY OF ELECTRICITY TO PATIENT AREAS Technical
311008 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4 LOW-VOLTAGE A.C. SUPPLIES Technical
311009 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.1 Separation of circuits Technical
311010 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.1.1 Body-protected electrical areas Technical
311011 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.1.2 Cardiac-protected electrical areas Technical
311012 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.1.3 Body-protected and cardiac-protected electrical areas Technical
311013 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.2 Protection of wiring systems and electrical equipment against mechanical damage Technical
311014 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3 Leakage protective device protection required Technical
311015 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3.1 General Technical
311016 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3.1.1 Electrical points Technical
311017 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3.1.2 Extra-low-voltage (ELV) charging sockets-outlets Technical
311018 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3.2 Socket-outlets requiring LPD protection Technical
311019 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3.2.1 General Technical
312020 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3.2.2 Locations of socket-outlets requiring LPD protection Unsafe
312021 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3.2.3 Types of socket-outlets requiring LPD protection Unsafe
312022 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.3.3 Permanently-wired medical electrical equipment requiring LPD protection Unsafe
311023 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.4 Low-voltage uninterruptible supplies (UPS) Technical
311024 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.4.1 General Technical
312025 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.4.2 Leakage protective device protection of uninterruptible supplies (UPS) Unsafe
311026 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.4.4.3 Uninterruptable power supply status indicators Technical
311027 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.5 LOW-VOLTAGE D.C. SUPPLIES Technical
311028 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.6 ACCESS TO CONTROLS AND INDICATORS Technical
311029 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7 SOCKET-OUTLETS Technical
312030 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.1 Number of socket-outlets Unsafe
311031 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.2 Socket-outlets requiring isolating switches Technical
311032 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.3 Socket-outlets for cleaning equipment Technical
311033 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.3.1 Location of socket-outlets identified ?CLEANING PURPOSES ONLY? Technical
312034 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.3.2 Protection of socket-outlets identified ?CLEANING PURPOSES ONLY? Unsafe
311035 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.4 Identification of socket-outlets Technical
311036 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.4.1 Identification of socket-outlets protected by LPDs Technical
311037 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.4.2 Switch indication Technical
311038 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.4.3 Colour coding Technical
311039 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.4.3.1 Low voltage (LV) socket-outlets Technical
311040 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.4.3.2 Extra-low-voltage (ELV) socket-outlets Technical
311041 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.4.4 Power available indication for RCD-protected socket-outlets Technical
312042 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.7.5 Socket-outlet switches Unsafe
311043 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8 RESIDUAL CURRENT DEVICES (RCDs) Technical
312044 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8.1 Type of RCD Unsafe
311045 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8.2 Discrimination Technical
311046 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8.3 Number and disposition of electrical points controlled by RCDs Technical
311047 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8.4 Indication Technical
311048 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8.5 Identification of RCDs Technical
311049 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8.6 Permanently wired equipment Technical
311050 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8.7 Test facility Technical
311051 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.8.8 Location of RCDs Technical
311052 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9 LOW-VOLTAGE ISOLATED SUPPLIES Technical
312053 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.1 General Unsafe
312054 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.2 Isolation transformers Unsafe
311055 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.3 Overcurrent circuit-breaker Technical
311056 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.4 Overload monitor Technical
311057 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.5 Line isolation monitor Technical
311058 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.5.1 General Technical
311059 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.5.2 Identification of LIMs Technical
311060 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.6 System prospective hazard current Technical
311061 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.7 Number and disposition of electrical points protected by an isolated supply Technical
311062 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.8 Permanently wired equipment Technical
311063 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.9.9 Test facility Technical
311064 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.1 ISOLATION SWITCHES Technical
311065 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.11 EXTRA-LOW-VOLTAGE (ELV) SUPPLIES Technical
311066 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.11.1 General Technical
311067 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.11.2 Source of ELV supply Technical
311068 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.12 IDENTIFICATION Technical
311069 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.12.1 General Technical
311070 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.12.2 Identification of patient areas Technical
313071 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.13 TESTING AND VERIFICATION OF ELECTRICAL WORK Testing
313072 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 2.14 ADDITIONAL DOCUMENTATION Testing
311073 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 3.1 GENERAL Technical
311074 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 3.2 EARTHING Technical
311075 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.1 GENERAL Technical
312076 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.2 EARTH-FREE ELV Unsafe
311077 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.3 DISPOSITION OF ELECTRICAL POINTS CONTROLLED BY LPDs Technical
311078 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4 EARTHING AND EQUIPOTENTIAL BONDING Technical
312079 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.1 General Unsafe
311080 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2 Equipotential earthing system Technical
311081 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.1 General Technical
311082 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.2 Provision of equipotential earthing system Technical
311083 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.3 Form of equipotential earthing system Technical
311084 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.4 Earthing of socket-outlets Technical
312085 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.4.1 General Unsafe
311086 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.4.2 Protective earthing conductor Technical
312087 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.5 Earthing of permanently installed electrical equipment Unsafe
311088 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.5.1 Points required to be earthed via the EP junction or node Technical
311089 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.5.2 Method of connecting the earthing conductor to the equipment Technical
311090 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.5.3 Method of connecting the earthing conductor to the EP junction or node Technical
311091 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.5.4 Insulation and segregation of earthing conductors Technical
311092 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.5.5 Maximum resistance of earthing conductors Technical
311093 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.6 Equipotential earthing of non-electrical equipment and fittings Technical
311094 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.7 Earthing connections Technical
311095 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.8 Equipotential (EP) junction Technical
311096 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.9 Equipotential (EP) test facility Technical
311097 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.2.10 Equipotential (EP) test terminal Technical
311098 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 4.4.3 Return earths Technical
311099 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.1 GENERAL Technical
311100 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2 HOMECARE INSTALLATIONS Technical
311101 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.1 Conformance with AS/NZS 3000 Technical
311102 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.2 Conformance with this Standard AUS Technical
312103 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.2.1 Leakage protective device (LPD) protection Unsafe
312104 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.2.2 Socket-outlets Unsafe
311105 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.2.3 Circuit protection and identification Technical
311106 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.3 Conformance with this Standard NZ Technical
312107 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.3.1 Leakage protective device (LPD) protection Unsafe
312108 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.3.2 Socket-outlets Unsafe
311109 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.2.3.3 Circuit protection and identification Technical
311110 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.3 DISABILITY AND AGED CARE INSTALLATIONS Technical
311111 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.4 INSTALLATIONS FOR SELF-HARM PATIENTS Technical
311112 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.4.1 General Technical
311113 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 5.4.2 Identification Technical
311114 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.1 INTRODUCTION Technical
311115 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2 ALTERATIONS Technical
311116 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2.1 General Technical
311117 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2.2 Patient areas not signposted as cardiac-protected or body-protected electrical areas Technical
312118 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2.3 Patient areas signposted as cardiac-protected or body-protected electrical areas Technical
311119 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2.4 Installation of new socket-outlets in patient areas wired as either body-protected or cardiac-protected Technical
311120 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2.5 Alterations to electrical installations in patient areas Technical
311121 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2.5.1 Alterations in cardiac-protected electrical areas Technical
311122 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2.5.2 Fixed electrical equipment rated at or above 2.0 kW Technical
311123 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.2.5.3 Reclassification of existing cardiac-protected electrical areas as body-protected electrical areas. Technical
311124 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.3 REPAIRS Technical
311125 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.3.1 Patient areas not wired as cardiac-protected or body-protected electrical areas Technical
311126 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.3.2 Patient areas wired as cardiac-protected or body-protected electrical areas AUS Technical
311127 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 6.4 IDENTIFICATION Technical
311128 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 7.1 GENERAL Technical
311129 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 7.2 BODY-PROTECTED ELECTRICAL AREA SIGN Technical
311130 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 7.3 CARDIAC-PROTECTED ELECTRICAL AREA SIGN Technical
311131 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.1 GENERAL Technical
311132 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2 BODY-PROTECTED ELECTRICAL AREAS Technical
311133 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1 General Technical
311134 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.1 Inspection Technical
311135 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.2 Labelling Technical
311136 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.3 Socket-outlets Technical
311137 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.3.1 Colour coding Technical
311138 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.3.2 Power-available lights Technical
311139 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.3.3 Maximum number of socket-outlets per LPD Technical
311140 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.3.4 Power ?ON? indicators Technical
311141 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.4 Switches Technical
311142 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.1.5 Wiring Technical
311143 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.2 Earthing Technical
313145 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.3.1 General Testing
313146 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.3.2 Sensitivity test Testing
313147 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.3.3 Maximum tripping time tests AUS Testing
311148 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.3.4 Maximum tripping time tests NZ Technical
311149 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.3.5 Residual current device (RCD) power-available indicator lights Technical
313150 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.3.6 Audible and visible RCD trip indicators Testing
311151 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.4 Line isolation monitors (LIMs) Technical
313152 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.4.1 Prospective hazard current of the installation Testing
313153 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.4.2 Prospective hazard current alarm Testing
313154 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.5 Overload monitors Testing
311155 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.6 Uninterruptible power supplies (UPSs) Technical
311156 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.2.7 Documentation Technical
311157 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3 CARDIAC-PROTECTED ELECTRICAL AREAS Technical
311158 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1 General Technical
311159 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.1 Inspection Technical
311160 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.2 Labelling Technical
311161 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.3 Socket-outlets Technical
311162 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.3.1 Colour coding Technical
311163 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.3.2 Power-available lights Technical
311164 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.3.3 Maximum number of socket-outlets per LPD Technical
311165 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.3.4 Power ?ON? indicators Technical
311166 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.3.5 Switches Technical
311167 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.3.6 Wiring Technical
311168 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.1.3.7 Disposition of socket-outlets protected by RCDs Technical
311169 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.2 Earthing Technical
313170 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.2.1 Inspection Testing
313171 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.2.2 Testing Testing
311172 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.3 Residual current devices (RCDs) Technical
313173 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.3.1 General Testing
313174 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.3.2 Sensitivity test Testing
313175 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.3.3 Maximum tripping time tests Testing
313176 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.3.4 Maximum tripping time tests Testing
311177 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.3.5 RCD power-available indicator lights Technical
311178 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.3.6 Audiovisual RCD trip indicators Technical
311179 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.4 Line isolation monitors (LIMs) Technical
313180 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.4.1 Prospective hazard current of the installation Testing
313181 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.4.2 Prospective hazard current alarm Testing
313182 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.5 Overload monitors Testing
311183 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.6 Uninterruptible power supplies (UPS) Technical
311184 AS/NZS 3003:2018 +A1 Electrical installations - Patient areas 8.3.7 Documentation Technical
411001 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.1.1 General requirements Technical
411002 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.1.2 Agreements between supplier (manufacturer) and user Technical
411005 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.2 Voltage classification Technical
411006 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.3 Current in normal operation Technical
411007 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.4 Short-circuit current Technical
411008 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.4.1 Mechanical and thermal effects Technical
411009 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.4.2 Types Technical
411013 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.5 Rated frequency Technical
411014 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.6 Corona Technical
411015 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.6.1 General Technical
411016 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.6.2 Radio and television interference Technical
411017 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.6.3 Audible noise Technical
411018 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.7 High voltage design practices with respect to EMF Technical
411019 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.2.8 Overvoltages Technical
411022 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.1 CIVIL AND STRUCTURAL REQUIREMENTS - General Technical
411023 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.2 Equipment and structures Technical
411024 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.2.1 General Technical
411025 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.2.2 Permanent loads (G) Technical
411026 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.2.3 Imposed and other loads (Q, W, E) Technical
411027 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.2.4 Special loads Technical
411028 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.3 Coincident temperatures Technical
411030 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.5 Load combinations Technical
411031 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.3.6 Deflections and serviceability limits Technical
411032 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4 CLIMATIC AND ENVIRONMENTAL CONDITIONS Technical
411033 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.1 General Technical
411034 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.2 Normal conditions Technical
411035 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.2.1 Indoor Technical
411036 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.2.2 Outdoor Technical
411037 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.3 Special conditions Technical
411038 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.3.1 General Technical
411039 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.3.2 Altitude Technical
411040 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.3.3 Pollution Technical
411041 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.3.4 Temperature and humidity Technical
411042 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.3.5 Vibration Technical
411043 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.3.6 Seismic vibration Technical
411044 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.4.3.7 The effect of wind Technical
411045 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.5 SPECIAL REQUIREMENTS Technical
411046 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.5.1 Effects of small animals and micro-organisms Technical
411047 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 2.5.2 Noise level Technical
411051 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.1 GENERAL Technical
411052 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.2 SELECTION OF INSULATION LEVEL Technical
411053 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.2.1 General Technical
411055 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.2.3 Consideration of rated withstand voltages Technical
411056 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.3 VERIFICATION OF WITHSTAND VALUES Technical
411057 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.4 MINIMUM CLEARANCES OF LIVE PARTS Technical
411058 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.4.1 General Technical
411059 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.4.2 Minimum clearances in voltage range I Technical
411061 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.5 MINIMUM CLEARANCES BETWEEN PARTS UNDER SPECIAL CONDITIONS Technical
411062 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 3.6 TYPE TESTED EQUIPMENT Technical
411063 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.1 GENERAL REQUIREMENTS Technical
411064 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.1.1 Selection Technical
411065 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.1.2 Equipment Safety Technical
412066 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.1.3 Personnel safety Unsafe
411067 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.1.4 Labels Technical
411068 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2 SPECIFIC REQUIREMENTS Technical
411069 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.1 Switching devices Technical
411070 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.2 Power transformers and reactors Technical
411071 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.3 Gas-insulated metal-enclosed equipment (GIE), metal-enclosed switchgear, insulation-enclosed switchgear and other prefab
ricated type-tested switchgear and fusegear assemblies
Technical
411072 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.4 Instrument transformers Technical
411073 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.4.1 General Technical
411074 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.4.2 Current transformers Technical
411075 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.4.3 Voltage transformers Technical
411076 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.5 Surge arresters Technical
411077 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.6 Capacitors Technical
411079 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.8 Insulators Technical
411080 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9 Insulated cables other than for overhead lines Technical
411081 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9.1 General requirements Technical
411082 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9.2 Temperature Technical
411083 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9.3 Stress due to temperature changes Technical
411084 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9.4 Flexible reeling and trailing cables Technical
411085 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9.5 Crossings and proximities Technical
411086 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9.6 Installation of cables Technical
411087 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9.7 Bending radius Technical
411088 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.9.8 Tensile stress Technical
411089 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.10 Conductors and accessories Technical
411090 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.11 Rotating electrical machines Technical
411091 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.12 Generating units Technical
411092 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.13 Generating unit main connections Technical
411093 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.14 Static converters Technical
411094 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.15 Fuses Technical
411095 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.15.1 Clearances Technical
411096 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.15.2 Fuse replacement Technical
411097 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 4.2.16 Electrical and mechanical interlocking Technical
411099 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.1 MINIMUM REQUIREMENTS - General Technical
411100 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.2 Circuit arrangement Technical
411101 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.2.1 Design Technical
411102 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.2.2 Protective measures Technical
411103 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.3 Documentation Technical
411104 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.4 Transport routes Technical
411105 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.5 Aisles and access areas Technical
411106 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.6 Lighting Technical
411107 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.7 Operational safety Technical
411108 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.1.8 Labelling Technical
411109 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2 OUTDOOR INSTALLATIONS OF OPEN DESIGN Technical
411110 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2.1 General Technical
412111 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2.2 Protective barrier clearances Unsafe
412112 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2.3 Protective obstacle clearances Unsafe
412113 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2.4 Boundary clearances Technical
411114 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2.5 Minimum height over access area Technical
411115 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2.6 Minimum clearances for maintenance Technical
411116 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2.7 Clearances to buildings within closed electrical operating areas Technical
411117 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.2.8 External fences or walls and access doors Technical
411118 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.3 INDOOR INSTALLATIONS OF OPEN DESIGN Technical
411119 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.4 INSTALLATION OF PREFABRICATED TYPE-TESTED SWITCHGEAR Technical
411120 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.4.1 General Technical
411121 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.4.2 Additional requirements for gas-insulated metal enclosed equipment (GIE) Technical
411122 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.4.2.1 Design Technical
411123 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.4.2.2 Erection on site Technical
411125 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.4.2.4 Earthing Technical
411126 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5 REQUIREMENTS FOR BUILDINGS Technical
411127 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.1 Introduction Technical
411128 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.2 Structural provisions Technical
411129 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.2.1 General Technical
411130 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.2.2 Specifications for walls Technical
411131 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.2.3 Windows Technical
411132 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.2.4 Roofs Technical
411133 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.2.5 Floors Technical
411134 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.3 Rooms for switchgear Technical
411135 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.4 Service areas Technical
411136 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.5 Doors Technical
411137 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.6 Draining of insulating liquids Technical
411138 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.7 Heating, ventilation and cooling Technical
411139 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.7.1 General Technical
411140 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.7.2 Ventilation of battery rooms Technical
411141 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.7.3 Rooms for emergency generating units Technical
411142 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.8 Buildings that require special consideration Technical
411143 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.5.9 Confined spaces Technical
411144 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.6 HIGH VOLTAGE/LOW VOLTAGE PREFABRICATED SUBSTATIONS Technical
411145 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 5.7 ELECTRICAL INSTALLATIONS ON A MAST, POLE OR TOWER Technical
411146 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.1 GENERAL Technical
412147 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.2.1 PROTECTION AGAINST DIRECT CONTACT - General Unsafe
411149 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.2.2 Measures for protection against direct contact Technical
411150 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.2.2.1 Recognized protection types Technical
411151 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.2.2.2 Design of protective measures Technical
411152 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.2.3 Protection requirements Technical
411153 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.2.3.1 Protection outside of closed electrical operating areas Technical
411154 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.2.3.2 Protection inside closed electrical operating areas Technical
411155 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.2.3.3 Protection during normal operation Technical
411157 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4 MEANS TO PROTECT PERSONS WORKING ON OR NEAR ELECTRICAL INSTALLATIONS Technical
411158 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.1 Construction and working procedures Technical
411159 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.2 Equipment for isolating installations or apparatus Technical
411160 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.3 Devices to prevent inadvertent closing of isolating devices Technical
411161 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.4 Devices for determining the de-energized state Technical
411162 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.5 Devices for earthing and short-circuiting Technical
411163 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.6 Equipment acting as protective barriers against adjacent live parts Technical
411164 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.6.1 General Technical
411165 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.6.2 Insertable insulated partitions Technical
411166 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.6.3 Insertable partition walls Technical
411167 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.4.7 Storage of personal protection equipment Technical
411168 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.5 PROTECTION FROM DANGER RESULTING FROM ARC FAULT Technical
411169 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.6 PROTECTION AGAINST DIRECT LIGHTNING STRIKES Technical
411170 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7 PROTECTION AGAINST FIRE AND EXPLOSION Technical
411171 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.1 Risk Technical
411172 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.1.1 General Technical
411173 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.1.2 Fire and explosion risk zones Technical
411174 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.1.3 Fire and explosion sources risk assessment Technical
411175 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.1.4 Fire and explosion risk management Technical
411176 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.1.5 Fire resistant barriers Technical
411177 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.1.6 Protection of personnel within high voltage installations Technical
411178 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.2 Buildings Technical
411179 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.2.1 General Technical
411180 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.2.2 Fire alarm systems Technical
411181 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.2.3 Fire suppression systems Technical
411182 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.3 Plant and equipment requirements Technical
411183 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.4 Transformers, reactors Technical
411184 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.4.1 General Technical
411185 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.4.2 Fire mitigation options for transformers Technical
411186 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.4.3 Transformer fire damage control measures Technical
411187 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.4.4 Outdoor transformers Technical
411188 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.4.5 Indoor transformers Technical
411189 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.5 Cables Technical
411190 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.6 Distribution substations Technical
411191 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.6.1 Special requirements for distribution kiosk/padmount cubicles and walled high voltage installations Technical
411192 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.7.6.2 Special requirements for distribution indoor high voltage installations Technical
411193 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.8 PROTECTION AGAINST LEAKAGE OF INSULATING LIQUIDS AND SF6 Technical
411194 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.8.1 Oil containment Technical
411195 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.8.2 SF6 leakage Technical
411197 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.8.4 Fire protected high voltage installation examples for distribution substations Technical
411198 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.9 IDENTIFICATION AND MARKING Technical
411199 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.9.1 General Technical
411200 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.9.2 Information plates and warning plates Technical
411201 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.9.3 Electrical hazard warning Technical
411202 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.9.4 Installations with incorporated capacitors Technical
411203 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.9.5 Emergency signs for emergency exits Technical
411204 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.9.6 Cable identification marks Technical
411205 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 6.1 PROTECTION AGAINST UNAUTHORIZED ACCESS Technical
411206 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.1 PROTECTION SYSTEMS Technical
411207 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.2 MONITORING AND CONTROL SYSTEMS Technical
411208 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3 A.C. AND D.C. SUPPLY CIRCUITS Technical
411209 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3.1 General Technical
411210 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3.2 a.c. supply Technical
411211 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3.3 d.c. supply Technical
411212 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3.3.1 Capacity Technical
411213 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3.3.2 Monitoring voltage and current Technical
411214 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3.3.3 Sizing and selection of batteries Technical
411215 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3.3.4 Battery rooms and cubicles Technical
411216 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.3.3.5 Protection against corrosion Technical
411217 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4 COMPRESSED AIR SYSTEMS Technical
411218 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4.1 Design Technical
411219 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4.2 Relative humidity Technical
411220 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4.3 Operating capacity Technical
411221 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4.4 Protection against corrosion Technical
411222 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4.5 Marking Technical
411223 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4.6 Isolation and drainage Technical
411224 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4.7 Arcing Technical
411225 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.4.8 Accessible controls Technical
411226 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.5 SF6 GAS HANDLING PLANT Technical
411229 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.6.2 Electrical noise sources in high voltage installations Technical
411230 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.6.3 Measures to be taken to reduce the effects of high frequency interference Technical
411231 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.6.4 Measures to be taken to reduce the effects of low frequency interference Technical
411232 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.6.5 Measures related to the selection of equipment Technical
411233 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.6.5.1 Zones Technical
411234 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.6.5.2 Internal circuitry Technical
411235 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.6.5.3 Gas-insulated switchgear Technical
411236 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 7.6.6 Other possible measures to reduce the effects of interference Technical
411237 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.1 GENERAL Technical
411238 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.2 FUNDAMENTAL REQUIREMENTS Technical
411239 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.2.1 General Technical
411240 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.2.2 Safety of people Technical
411241 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.2.3 Protection of equipment Technical
411242 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.2.4 Support operational security Technical
411243 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.3 RISK MANAGEMENT AND DUE DILIGENCE Technical
411244 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.3.1 General Technical
411245 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.3.2 Touch and step voltage hazards and risks Technical
411246 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4 DESIGN Technical
411247 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.1 Introduction Technical
411248 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.2 Design process overview Technical
411249 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.3 Data gathering Technical
411250 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4 Initial concept design Technical
411251 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4.1 General Technical
411252 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4.2 Fault current Technical
411253 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4.3 Earth fault duration Technical
411254 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4.4 Soil resistivity Technical
411255 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4.5 Layout practicalities Technical
411256 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4.6 Coordinated design Technical
411257 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4.7 Current injection Technical
411258 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.4.8 Special considerations Technical
411259 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.5 Determine design EPR Technical
411260 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.6 Power frequency design Technical
411261 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.6.1 General Technical
411262 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.6.2 Earthing conductor layout Technical
411263 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.6.3 Dimensioning of earthing conductors Technical
411264 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.6.4 Transferred potentials Technical
411265 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.6.5 Hazard location identification Technical
411266 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.7 Safety criteria for design Technical
411267 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.7.1 Safety criteria Technical
411268 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.7.2 Risk quantification and individually derived safety criteria Technical
411269 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.7.3 Guidance on standard safety criteria Technical
411270 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.7.4 Safety criteria within other standards and guidelines Technical
411271 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.8 Perform direct probabilistic design Technical
411272 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.9 Mitigation/redesign Technical
411273 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.4.10 Transient design Technical
411274 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.5 CONSTRUCTION Technical
411275 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.6 COMMISSIONING AND ONGOING MONITORING Technical
411276 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.7 MAINTENANCE, MODIFICATION AND REFURBISHMENT Technical
413277 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.8 TESTING Testing
413278 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 8.9 DOCUMENTATION Technical
413279 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 9.1 INSPECTIONS AND TESTS Testing
413280 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 9.2 DOCUMENTATION AND RECORDS Technical
411281 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 9.3 VERIFICATION OF SPECIFIED PERFORMANCES Technical
411282 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 9.4 TESTS DURING INSTALLATION AND COMMISSIONING Technical
411283 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 9.5 TRIAL RUN Technical
411284 AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c. 10 O P E R A T I O N A N D M A I N T E N A N C E M A N U A L Technical
511001 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 4.1 General requirements Technical
511002 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 4.2 Documentation Technical
511003 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 4.3 Initial inspection Technical
512004 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 4.4 Assurance of conformity of equipment Unsafe
511005 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 4.4.1 Equipment with certificates according to IEC standards Technical
512006 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 4.4.2 Equipment without certificates according to IEC standards Unsafe
511007 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 4.4.3 Selection of repaired, second hand or existing equipment Technical
511008 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 4.5 Qualifications of personnel Technical
511009 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.1 Information requirements Technical
511010 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.2 Zones Technical
511011 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.3 Relationship between equipment protection levels (EPLs) and zones Technical
511012 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.4.1 General Technical
512013 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.4.2 Relationship between EPLs and types of protection Unsafe
511014 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.4.3 Equipment for use in locations requiring EPL "Ga" or "Da" Technical
511015 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.4.4 Equipment for use in locations requiring EPL "Gb" or "Db" Technical
511016 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.4.5 Equipment for use in locations requiring EPL "Gc" or "Dc" Technical
511017 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.5 Selection according to equipment grouping Technical
511018 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.6.1 General Technical
511019 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.6.2 Gas or vapour Technical
511020 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.6.3.1 General Technical
511021 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.6.3.2 Temperature limitations because of the presence of dust clouds Technical
511022 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.6.3.3 Temperature limitation because of presence of dust layers Technical
511023 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.6.3.4 Unavoidable dust layers Technical
511024 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.7.1 General Technical
511025 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.7.2 Ignition process Technical
511026 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.8.1 General Technical
511027 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.8.2 Ignition process Technical
511028 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.9 Selection to cover external influences Technical
511029 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.10.1 General Technical
511030 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.10.2 Transportable and portable equipment Technical
511031 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.10.3 Personal equipment Technical
511032 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.11.1 General Technical
511033 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.11.2 Environmental Factors for "Ex" machine installation Technical
511034 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.11.3 Power and accessory connections, grounding Technical
511035 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.11.4 Motors fed from a converter supply Technical
511036 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.12 Luminaires Technical
511037 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.13.1 General Technical
511038 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.13.2 Specific requirements for explosive dust atmospheres Technical
511039 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.13.3 Location Technical
511040 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.14.1 Charging of secondary cells and batteries Technical
511041 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.14.2 Ventilation Technical
511042 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.15.1 General Technical
511043 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.15.2 Passive RFID tags Technical
511044 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.15.3 Mounting RFID tags Technical
511045 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 5.16 Gas detection equipment Technical
511046 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.1 Light metals as construction materials Technical
511047 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.2 Danger from live parts Technical
511048 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.3.2 TN type of system earthing Technical
511049 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.3.3 TT type of system earthing Technical
511050 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.3.4 IT type of system earthing Technical
511051 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.3.5 SELV and PELV systems Technical
511052 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.3.6 Electrical separation Technical
511053 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.3.7 Non Ex electrical equipment above hazardous areas Technical
511054 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.4.1 General Technical
511055 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.4.2 Temporary bonding Technical
511056 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.5.2 Avoidance of a build-up of electrostatic charge on construction and protecting parts for locations requiring EPL "Ga", "
Gb" and "Gc"
Technical
511057 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.5.3 Avoidance of a build-up of electrostatic charge on construction and protecting parts for locations requiring EPL "Da", "
Db" and "Dc"
Technical
511058 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.6 Lightning protection Technical
511059 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.7.1 General Technical
511060 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.7.2 Radio frequency received in hazardous areas Technical
511061 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.8 Cathodically protected metallic parts Technical
511062 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 6.9 Ignition by optical radiation Technical
511063 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 7 Electrical protection Technical
511064 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 8.2 Switch-off Technical
511065 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 8.3 Electrical isolation Technical
511066 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.1 General Technical
511067 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.2 Aluminium conductors Technical
511068 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.1 General Technical
512069 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.2 Cables for fixed installations Unsafe
512070 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.3 Flexible cables for fixed installations Unsafe
512071 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.4 Flexible cables supplying transportable and portable equipment Unsafe
511072 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.5 Single insulated wires Technical
511073 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.6 Overhead lines Technical
512074 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.7 Avoidance of damage Unsafe
511075 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.8 Cable surface temperature Technical
511076 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.3.9 Resistance to flame propagation Technical
512077 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.4 Conduit systems Unsafe
511078 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.5 Additional requirements Technical
511079 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.6.1 Circuits traversing a hazardous area Technical
511080 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.6.2 Terminations Technical
511081 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.6.3 Unused cores Technical
511082 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.6.4 Openings in walls Technical
511083 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.6.5 Passage and collection of flammables Technical
511084 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 9.6.6 Accumulation of dust Technical
511085 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 10.1 General Technical
511086 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 10.2 Selection of cable glands Technical
511087 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 10.3 Connections of cables to equipment Technical
511088 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 10.5 Unused openings Technical
511089 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 10.6.1 General Technical
511090 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 10.6.2 Selection of cable glands Technical
511091 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 10.7 Additional requirements for type of protection "t" - Protection by enclosure Technical
511092 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 10.8 Additional requirements for type of protection "nR" - Restricted breathing enclosure Technical
511093 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.1 General Technical
511094 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.2.1 Motors with a converter supply Technical
511095 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.2.2 Reduced-voltage starting (soft starting) Technical
511096 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.3.1 Mains-operated Technical
511097 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.3.2 Winding temperature sensors Technical
511098 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.3.3 Machines with rated voltage greater than 1 kV Technical
511099 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.3.4 Motors with converter supply Technical
511100 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.3.5 Reduced-voltage starting (soft starting) Technical
511101 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.4.1 Motors with a converter supply Technical
511102 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.4.2 Reduced-voltage starting (soft starting) Technical
511103 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.5.1 Motors with a converter supply Technical
511104 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.5.2 Reduced-voltage starting Technical
511105 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.6.1 Motors with converter supply Technical
511106 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.6.2 Reduced-voltage starting (soft starting) Technical
511107 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 11.6.3 Machines with rated voltage greater than 1 kV Technical
511108 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 12 Luminaires Technical
511109 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 13.1 General Technical
511110 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 13.2 Temperature monitoring Technical
511111 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 13.3 Limiting temperature Technical
511112 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 13.4 Safety device Technical
511113 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 13.5 Electrical trace heating systems Technical
511114 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 14.1 General Technical
512115 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 14.3 Protection of flameproof joints Unsafe
512116 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 14.4 Conduit systems Unsafe
511117 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 15.1 General Technical
511118 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 15.2 Maximum dissipated power of terminal box enclosures Technical
511119 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.1 General Technical
511120 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2 Equipment Technical
511121 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.1 General Technical
511122 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.2 Electrical parameters of cables Technical
511123 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.3 Earthing of conducting screens Technical
511124 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.4 Cable armour bonding Technical
511125 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.5.1 General Technical
511126 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.5.2 Conductors Technical
511127 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.5.3 Unused cores in cables Technical
511128 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.6 Marking of cables Technical
511129 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.7 Cables carrying more than one intrinsically safe circuit Technical
511130 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.2.8 Types of cables carrying more than one intrinsically safe circuit and applicable fault considerations Technical
511131 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.3 Earthing of intrinsically safe circuits Technical
511132 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.4.1 General Technical
511133 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.4.2 Descriptive system document Technical
511134 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.4.3 Intrinsically safe circuits with only one source of power Technical
511135 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.2.4.4 Intrinsically safe circuits with more than one associated apparatus Technical
511136 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.3 Installations to meet the requirements of EPL "Ga" or "Da" Technical
511137 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.4 Simple apparatus Technical
511138 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.5.1 General Technical
511139 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.5.3 Terminal boxes with more than one intrinsically safe circuit Technical
511140 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.5.4 Terminal boxes with non-intrinsically safe and intrinsically safe circuits Technical
511141 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.5.5 Plugs and sockets used for external connections Technical
511142 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 16.6 Special applications Technical
511143 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 17.1 General Technical
511144 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 17.2.1 General Technical
511145 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 17.2.2 Ducting Technical
511146 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 17.2.3.1 General Technical
511147 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 17.2.3.2.1 General Technical
511148 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 17.2.3.2.2 Automatic switch-off Technical
511149 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 17.2.3.2.3 Alarm Technical
511150 AS/NZS 60079.14:2017 Explosive atmospheres Design selection, erection and initial inspection 17.2.3.3 Equipment with an internal source of release Technical
511151